3 14 SP1 Range
3 14 SP1 Range
3 13 Sensor Break Alarm
3 13 Sensor Break Alarm
SP1L ( SP1 low limit value ) and SP1H ( SP1 high limit value ) in setup menu
are used to confine the adjustment range of SP1.
SP1L ( SP1 low limit value ) and SP1H ( SP1 high limit value ) in setup menu
are used to confine the adjustment range of SP1.
Example : A freezer is working in its normal temperature range -10 °C to -15 °C.
In order to avoid an abnormal set point, SP1L and SP1H are set with the
following values:
SP1L = -15 °C
SP1H = -10 °C
Now SP1 can only be adjusted within the range from -10 °C to -15 °C.
Example : A freezer is working in its normal temperature range -10 °C to -15 °C.
In order to avoid an abnormal set point, SP1L and SP1H are set with the
following values:
SP1L = -15 °C
SP1H = -10 °C
Now SP1 can only be adjusted within the range from -10 °C to -15 °C.
SP1
IN1H ( or sensor range high )
IN1H ( or sensor range high )
SP1H
SP1L
IN1L ( or sensor range low )
IN1L ( or sensor range low )
Figure 3.19 SP1 Range
Figure 3.19 SP1 Range
Setup : SP1L, SP1H
Setup : SP1L, SP1H
54
Alarm 1 or alarm 2 can be configured as a sensor break alarm by selecting
SENB
for A1FN or A2FN.
The sensor break alarm is activated as soon as a failure mode occurs. Refer to
for failure mode conditions. Note that A-D failure also creates a
sensor break alarm.
One of 4 alarm modes can be selected for the sensor break alarm. These
are: Normal alarm, Latching alarm, Holding alarm and Latching/Holding alarm.
However, the Holding alarm and Latching/Holding alarm are not valid for use
with the sensor break alarm
See
for the descriptions of these alarm modes.
Section 3-16
Section 3-8
even if it is set with holding or latching/holding
mode.
Alarm 1 or alarm 2 can be configured as a sensor break alarm by selecting
SENB
for A1FN or A2FN.
The sensor break alarm is activated as soon as a failure mode occurs. Refer to
for failure mode conditions. Note that A-D failure also creates a
sensor break alarm.
One of 4 alarm modes can be selected for the sensor break alarm. These
are: Normal alarm, Latching alarm, Holding alarm and Latching/Holding alarm.
However, the Holding alarm and Latching/Holding alarm are not valid for use
with the sensor break alarm
See
for the descriptions of these alarm modes.
Section 3-16
Section 3-8
even if it is set with holding or latching/holding
mode.
Sensor Break Alarm 1
Setup:
Hidden:
Sensor Break Alarm 2
Setup:
Hidden:
A1FN=SENB
A1MD=NORM, LTCH
TIME, A1SP, A1DV
A1HY
OUT2= =AL2
A2FN=SENB
A2MD=NORM, LTCH
TIME , A2SP, A2DV
A2HY
Sensor Break Alarm 1
Setup:
Hidden:
Sensor Break Alarm 2
Setup:
Hidden:
A1FN=SENB
A1MD=NORM, LTCH
TIME, A1SP, A1DV
A1HY
OUT2= =AL2
A2FN=SENB
A2MD=NORM, LTCH
TIME , A2SP, A2DV
A2HY