d1 information group - general information
d1.1
ROOM UNIT TYPE (DD3)
d1.2
ROOM UNIT SOFTWARE VERSION
d1.3
TYPE OF CONTROLLER CONNECTED TO ROOM UNIT
KMS-D = 0 KMS-D+ = 1
KSF-D = 10 KSF-D+ = 11
WHMS = 92
d1.4
SOFTWARE VERSION OF THE CONTROLLER
d1.5
HYDRAULIC SCHEME OF THE CONTROLLER
d1.6
LIGHT SENSOR
Light measured in the room where the room unit is installed is displayed.
t1.12
T12 CONTROLLER SENSOR
Measured and calculated temperatures for T12 sensor are displayed alternately.
t1.13
THE FIRST HEATING CIRCUIT TR1
Measured and desired room temperatures of the first heating circuit are displa
-
yed alternately.
t1.14
THE SECOND HEATING CIRCUIT TR2
Measured and desired room temperatures of the second heating circuit are
displayed alternately.
t1.15
DIRECT CIRCUIT
Calculated temperature of the flow for direct circuit is displayed.
P1 parameter group - basic parameters
No. Description
Range
P1.1
TEMPERATURE DISPLAY ROUND-OFF
With this setting, we can determine the value the
measured temperature display will be rounded to.
0 - 0.1 °C
1 - 0.2 °C
2 - 0.5 °C
3 - 1.0 °C
P1.2
AUTOMATIC EXIT TIME
This setting determines the time before the display
returns to basic mode.
3 ÷ 180 s (
15
)
P1.3
DISPLAY ILLUMINATION SHUT-OFF TIME
This setting determines the time before display
lighting is reduced or shut off.
10 ÷ 180 s (
30
)