TERRA 27
LOW TEMPERATURE
35°C
A++
colder
medi-
um
warmer
ηs
190
184
186
Energy consumption
[kWh] 12794
11034
7088
P rated
[kW]
26
26
26
SCOP
[-]
4,95
4,81
4,84
MEDIUM TEMPERATURE
55 °C
A++
colder
medi-
um
warmer
ηs
130
127
128
Energy consumption
[kWh] 16235
13947
8995
P rated
[kW]
23
23
23
SCOP
[-]
3,46
3,38
3,39
DHW
SP500
A
colder
medi-
um
warmer
ηWH
84
84
84
Energy consumption
[kWh]
1651
1651
1651
Draw-off profile
XL
Tank losses
[W]
117
indoor outdoor
Sound power level
[dBA]
60,1
Controller class, with remote
controller
VII
Controller contri-
bution [%]
3,5
Controller class, without remote
controller
III
Controller contri-
bution [%]
1,5
14.4 Limits of use
Limits of use for heating
TERRA 6 HPL
-
TERRA 27 HPL
Spread
[K]
5
7
10
Max. heat pump flow temperature (heat-
ing)
[°C]
65
65
65
Max. flow temperature for sizing (heat-
ing)
[°C]
60
60
60
Max. evaporator inlet temperature
(WQA)
[°C]
20
20
20
Min. evaporator inlet temperature
(WQA)
[°C]
-5
-5
-5
Limits of use for cooling
TERRA 6 CPL
-
TERRA 27 CPL
Spread
[K]
5
7
10
Max. heat pump flow temperature (cool-
ing)
[°C]
7
10
13
Max. flow temperature for sizing (cool-
ing)
[°C]
9
12
15
Max. evaporator inlet temperature
(WQA)
[°C]
20
20
20
Min. evaporator inlet temperature
(WQA)
[°C]
-5
-5
-5
Summary of Contents for TERRA 6
Page 2: ......
Page 80: ...80 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity...
Page 81: ...982001 TERRA M2 M4 EN04 1 www ochsner com 81 INSTALLATION Declaration of conformity...
Page 82: ...82 www ochsner com 982001 TERRA M2 M4 EN04 1 INSTALLATION Declaration of conformity...
Page 90: ...90 www ochsner com 982001 TERRA M2 M4 EN04 1...