background image

 
 
 

BA_GMLW OTE bis V3.4 SHORT_EN_20090408_V1 

Page 12 of 25 

 
 

4.6.4 Sensor 

wiring 

 

De-icing sensors

 
2 de-icing sensors (

TQA

,

 TQE

) are to be in-

stalled in the fin-packet of the evaporator. (See 
the  wiring diagram for the exact positioning of 
the sensors) For this, a 4-pole cable is to be run 
from the indoor unit to the evaporator. The sen-
sors are then connected together with the 4-
pole cable in a terminal box which is protected 
against moisture (not supplied with heat pump).  
 
The external sensor (

TA

) of the control system 

is to be installed at approximately 2.5 m height 
on the outer side of the building wall (North or 
West side). Care must be taken that the ther-
mometer is not exposed to direct solar radiation 
or wind; as such placement influences the op-
erational characteristics of the control system. 
 
The heat generator sensor  (

TPO

) is normally 

included with the heat pump at delivery. If a 
buffer storage tank or a low loss header is to be 
implemented, the sensor is to be mounted in-
ternally in the storage device. Placement 
should occur in the top third of the tank. If there 
is no low loss header, the heat generator sen-
sor (

TPO

) will not be installed. See separate 

Instruction „Wiring diagram“  
 
The hot water sensor 

(TB) 

is included with the 

heat pump at delivery. Placement should occur 
in the bottom third, to max. the middle of the 
tank. OCHSNER hot water tanks have suitable 
sleeve fittings for this installation.  
 
Should a mixing circuit be installed additionally 
to the heating circuit, then the mixing circuit 
sensor  (

TMK

) is included in the delivery along 

with strapping and heat conducting paste. The 
sensor is to be installed directly after the mixing 
circuit pump.  
 

Do not expose the sensor terminals 
to a voltage > 10 V. This may dam-
age or destroy the control. 

 

 

4.6.5 

Pumps, motors 230 VAC 

 
Pumps (heating circuit pumps, water charging 
pumps) as well as motors (mixing valves, etc.) 
are to be wired directly to the control. 
 

 Warning:

 A test-run may only be 

undertaken on a fully-prepared sys-
tem that is ready for commissioning! 
(Hydraulically connected, correct 
compressor rotation ensured). 

 

4.7 

Utility control contact 

 
In the case of tariff switching (interrupted power 
supply) the heat pump will be temporarily 
switched off by the utility. A control input (bridge 
on terminal EVU, terminal strip X3) is present in 
the control. If the tariff switching takes place in 
the meter (Night Tariff), the EVU contact must 
not be activated. 
 
 
 
 
 
 
 
 
 
 

Fig. 8: Tariff switching contact on terminal X3 

 

Summary of Contents for GMLW

Page 1: ...Installation and Operating Instructions GMLW Heat Pump Heating Cooling Hot Water...

Page 2: ...4 6 Electrical connection 10 4 6 1 Supply voltage to heat pump 10 4 6 2 Evaporator wiring 11 4 6 3 Cable cross sections 11 4 6 4 Sensor wiring 12 4 6 5 Pumps motors 230 VAC 12 4 7 Utility control con...

Page 3: ...BA_GMLW OTE bis V3 4 SHORT_EN_20090408_V1 Page 3 of 25...

Page 4: ...by a specialist authorised by the manufacturer All circuit breakers in the heating system are to be turned off before any work is carried out on the terminal strips or electrical con nections wiring T...

Page 5: ...hangers 3 2 Heat Pumps GMLW Heat pumps of the type GMLW are split appli ances where the compressor unit is installed inside and the evaporator outside the building The compressor unit is suitable for...

Page 6: ...k Read this instruction manual care fully before you start commission ing the heat pump 4 Installation 4 1 Delivery The heat pump is delivered on a non returnable palette and pack in cling film The cl...

Page 7: ...ead to increased noise sensitivity A possible noise transfer to adjoin ing rooms cannot be ruled out and must be considered during the design 4 3 1 Installation of split outdoor unit The installation...

Page 8: ...eating system circulation pump buffer charge pump take the internal pressure dif ference in the heat pump condenser into account see technical data Integrated heating circulation pumps are designed as...

Page 9: ...d by gravel and is bevelled from the top to the bottom Fig 4 Wall conduit into free air Fig 5 Wall conduct into ground Fig 6 Foundation This hinders the water from entering the build ing in the event...

Page 10: ...s no guarantee 4 6 1 Supply voltage to heat pump The protection for the main electrical circuit is to be provided by a three pole circuit breaker which in case of failure shuts off all poles amperage...

Page 11: ...ndoor unit to the evaporator Motors Sensors Cable 3 phase supply to fan incl signal contact winding protec tion 7 x 1 5 De ice sensor TQA TQE 4 x 0 75 Electronic expansion valve 4 x 0 75 1Rotation spe...

Page 12: ...will not be installed See separate Instruction Wiring diagram The hot water sensor TB is included with the heat pump at delivery Placement should occur in the bottom third to max the middle of the tan...

Page 13: ...control circuit 230V 50Hz and other electrical installa tions on the building site are complete Confirmation of proper field rotation no provisional modifications Details see check list supplied in p...

Page 14: ...g to user re quirements and document these set tings 13 Hand over system to operator 6 Operating the system The heat pump operation takes place by means of the basic operating panel This is easily ac...

Page 15: ...is free from leaves and twigs or any other foreign bodies the condensation can drain off the heating circuit contains enough water Pointer On request OCHSNER can offer a maintenance contract If inter...

Page 16: ...your contracting partner or the OCHSNER customer service de partment with the heat pump model and product number at the following numbers Customer service Austria Tel 0043 0 504245 14 E Mail kundendie...

Page 17: ...ct Contact heating installer free replace pump 4 Evaporator iced despite defrost function ER 47 Poor weather conditions Remove ice with the help of warm water or air Never remove ice mechanically Too...

Page 18: ...10 Operation condition Utility block 11 Phase failure Utility blocking time active Compressor rotates in the wrong direction at relay K7 the LED DEF is lit Contact electrician to change wiring test t...

Page 19: ...30 bar Relative Humidity 80 80 80 80 Air Volume Flow Rate 4000 4000 8000 8000 m h Working Fluid Temperature Difference 5 0 5 0 5 0 5 0 K Operating Range 15 40 15 40 15 40 15 40 C Fan Power Consumption...

Page 20: ...its Power settings 1 1 1 1 1 units Max Operating Current 6 0 9 6 13 8 17 7 23 2 A Max Starting Current 28 0 45 49 5 70 90 0 A Max Starting Current w Discharge 14 0 23 25 35 45 0 A Evaporator Type Buil...

Page 21: ...B gen 90 Fl ssigL Saugg L Fl ssigL Saugg L Fl ssigL Saugg L Fl ssigL Saugg L 284050 GMLW 9 2 bis 8 12 22 12 22 12 22 12 22 284060 GMLW 9 plus 2 bis 8 12 18 12 18 12 22 12 22 284100 GMLW 14 2 bis 8 12...

Page 22: ...urce Return Vorlauf Quellenergie Heat Source Supply R cklauf Heizung Heating Return Vorlauf Heizung Heating Supply RLQ EA VLH VLQ RLH 5 4 5 4 GMLW 25 GMLW 25 plus GMLW 35 plus RLH EA VLH 155 385 85 62...

Page 23: ...9 35 Operating data Heat pump type GMLW 9 plus GMLW 19 plus GMLW 25 plus GMLW 35 plus Evaporator Type MSV 14 MSV 19 MSV 25 MSV 35 Flow rate m3 h 4000 8000 8000 9800 Number of fans 1 2 2 2 Power consum...

Page 24: ...GMBW 113 VX GMSW 6 11 GMSW 15 38 OSWP 46 96 GMSW 7 VX GMSW 18 VX GMSW 6plus 10plus GMSW 12plus 17plus GMSW 38R OSWP 46R 96R GMWW 6 11 GMWW 15 38 OWWP 46 96 GMWW 8plus 13plus GMWW 15plus 23plus GMWW 3...

Page 25: ...pany Address Tel Service engineer OCHSNER W rmepumpen GmbH Autobahnstr 2 A 3350 Haag Tel 43 0 5 042458 Fax 43 0 5 04245 30 www ochsner at kontakt ochsner at OCHSNER W rmepumpen GmbH Elxlebenerweg 10 D...

Reviews: