REPLACEMENT PROCEDURE FOR PARTS
A. FAN MOTOR
1. Remove cabinet's left-hand (when looking at the front of the unit) side panel.
2. Disconnect motor wires from evaporator contactor and fan speed rocker switch.
3. Remove screws securing motor and O-ring to blower housing. All screws are external and visible.
4. Loosen clamp around motor and remove motor.
5. Install new motor, reversing the removal procedure.
B. THERMOSTAT AND BATTERIES
1. No batteries are used in the thermostat.
C. PANEL INDICATOR LIGHT
1. To replace pilot light on all models, disconnect wire from control panel, bend tinnerman clip retaining
light and pull out. Install new light, reversing the procedure.
D. CONDENSATE PUMP
1. Remove cabinet's left hand side panel.
2. Remove front bracket securing condensate pump in base pan by removing nut from weld stud.
3. Disconnect pump wire leads from terminal block. Remove retainer clamp and tubing. Replace pump,
install by reversing procedure.
E. PRESSURE ACTUATED WATER VALVE
1. Remove back panel.
2. Remove nut that secures sensing capillary to the refrigeration system's high pressure side. A built in
schrader valve allows removal without need to remove refrigerant charge..
3. Remove two screws that retain valve to right side panel.
13