background image

PIPING SCHEMATIC 

21 

Summary of Contents for OWC6012QC

Page 1: ...ENGINEERING INSTALLATION AND SERVICE MANUAL OWC6012 6032 6034QC 5 Ton Deluxe Portable Water Cooled Cooler With Quick Connect EISM OWC60QC 10012021...

Page 2: ...ss of continuous improvement the items and procedures described in this manual are subject to change without notice Please note model and serial number of the OWC60QC unit when contacting the factory...

Page 3: ...ected to the proper source of electrical power the OWC60QC is controlled by a solid state electronic device with numerous options of temperature and airflow controls that will provide the desired leve...

Page 4: ...C 6012QC 6032QC 6034QC COOLING CAPACITY VOLTAGE V Phase at 60Hz 208 230 1 208 230 3 460 3 AMPS 23 7 16 5 6 3 TOTAL WATTS IN RUSH CURRENT AMPS 165 149 75 PLUG TYPE 6 30P LCDI L15 30P L16 20P EER COMPRE...

Page 5: ...TE PUMP Each OWC60QC unit comes equipped with an Automatic Condensate Pump that removes the condensate The pump discharges through a check valve located on top of the condensate pump assembly The viny...

Page 6: ...60 QC is it operates as a room air conditioner because water is used as the means for heat rejection The major advantage of water cooled air conditioning is the convenience of connecting water hoses o...

Page 7: ...ELECTRICAL CONFIGURATION CAUTION DO NOT USE THE LCDI AS AN ON OFF SWITCH FOR THE OWC6012QC UNIT 5...

Page 8: ...6 OWC60 QC INTERIOR Motor Digital Controller Compressor Evaporator Coil Blower Wheel Condensate Pump Cubby for the Hose Kit Drain Water In Water Out Drain High Pressure Switch Reset Button...

Page 9: ...IT ON IMPROPER VOLTAGE WILL VOID THE WARRANTY ACCESSORIES Verify that all accessories are correct for the model and are installed in accordance with all instructions START UP Install the unit in accor...

Page 10: ...de edge guards By removing the OWC60 QC discharge grille the nozzle kit can then be installed in the grille opening Evaporator return air plenum is available for installations where it is required to...

Page 11: ...placed in the grille opening 2DDA 16 for OWC60 QC converts the evaporator discharge to a 16 inch diameter round duct When used in conjunction with the evaporator return air plenum DEP 16 the unit can...

Page 12: ...for the condensate pump discharge to a drain A QC lanyard is supplied with each QC Coupling When engaged this device releas es the internal valve of the coupling allowing for air to break the vacuum...

Page 13: ...on and sink adapter if needed 3 Install WATER OUT line in drain allowing for free drain conditions with an air space around the opening 4 Install DRAIN line in drain allowing for free drain conditions...

Page 14: ...e Standard QC Hose Kit cannot accommodate the installation The kit provides a means of connecting garden hose to a QC Model unit when the water source and drain are located in separate areas or where...

Page 15: ...ever comes first This cycle repeats every four hours FAN SPEED The operator can select between AUTO or MANUAL fan speed control Pressing the FAN SPEED button will switch speed from AUTO to MANUAL In M...

Page 16: ...peed Limit Setting 30 55 P4 Temperature Sensor Calibration 10 P10 Temperature Display F or C P13 Supply Fan Operation Cycling or Continuous P1 P2 To adjust fan speed settings P1 represents the high fa...

Page 17: ...742 hours 6 Add the 2 number sets together to get total hours 03 and 486 3486 hours 01 and 59 1059 hours TOTAL HOURS REPRESENTS COMPRESSOR RUN TIME MODEL CODE SETTINGS OWC60 QC P1 80 P2 45 OWC PROGRAM...

Page 18: ...in the water supply line In these cases it is recommended that the water valve be adjusted 1 Disconnect the unit power 2 Remove water valve cover plate or back panel depending on model to locate the...

Page 19: ...w controller and secure in place C POWER MODULE To remove the power module remove the rear control box cover Disconnect wires one at a time and re attach each wire while holding replacement module in...

Page 20: ...START CAUSE Thermostat set point is too high REMEDY Make sure set point is lower than room temperature Look for a red dot to the right of the temperature displayed for cooling Note there is a time del...

Page 21: ...re Cut Out will shut down the compressor Wait 15 minutes depress the HI PRESSURE RESET and repeat this process until ALL of the water is out of the system When completed depress the HIGH PRESSURE RESE...

Page 22: ...d electrical circuits of the system should only be serviced by a fully qualified service technician 20 Oceanaire Three Phase units are be equipped with phase monitors for compressor motor protection T...

Page 23: ...PIPING SCHEMATIC 21...

Page 24: ...WIRING SCHEMATIC FOR OWC6012QC 22...

Page 25: ...WIRING SCHEMATIC FOR OWC6032QC 23...

Page 26: ...WIRING SCHEMATIC FOR OWC6034QC 24...

Page 27: ...ten instructions or has been altered or modified in any way b Product that has been subjected to any abnormal power conditions such as loss of power power surges voltage irregularities such as brown o...

Page 28: ...____________________________ Purchased from _______________________________ Date Installed _________________________________ For Technical Support or service parts contact our Keep Cool Team at 847 58...

Reviews: