background image

10 

                                            CHECKOUT OF UNIT OPERATION 
 

POWER BUTTON: 

Press the 

power button

 once to toggle the unit to the on mode. Press the power button 

again to toggle the unit to the off mode. 

FAN BUTTON:

 Press and release the 

fan button 

to advance from auto to manual fan. Press and 
release to increase the manual fan speeds, 1 
through 6. Press and release again returns to the 
auto fan mode. The selected fan mode is indicated 
by the Auto and Manual fan LED’s. 
 

UP BUTTON:

 Momentarily press and the set 

point will appear in the temperature display. The 
set point increases one degree each time the up 
button is pressed and released. 
 

DOWN BUTTON:

 Momentarily press and 

release to display the set point. The set point is 

decreased one degree each time the button is pressed and released. 
 

MODE BUTTON:

 The 

Mode Button

 is used to select one of 2 Operating Modes. Press and release to 

advance to the next mode. Continue to press and release until the desired Operating Mode is reached. The 
mode selected is indicated by the Mode LED. 
 

TEMP SELECT BUTTON:

 Press and release to view inside (supply) air temperature, discharge air 

temperature or set point. The appropriate LED will be lit indicating which temperature is displayed. 
 

THREE DIGIT DISPLAY:

  The inside (supply) temperature is displayed whenever the control is turned 

on. The display provides a readout of the inside air temperature which is located in the supply airflow. 
 

COOL MODE LED:

 The Cool Mode LED is lit when Cooling is selected. 

 

MOISTURE CONTROL LED: 

The Moisture LED is lit when the Moisture Control is selected. 

 

MANUAL FAN LED:

 The Manual Fan LED is lit when a manual fan speed is selected. 

 

AUTO FAN LED: 

The Auto Fan LED is lit when automatic fan speed operation is selected. 

 

FAN SPEED BAR GRAPH:

 There are six(6) individual fan speed LED’s. Each LED represents one (1) 

fan speed. Low fan (1) is indicated by illuminating the first LED. High fan speed is indicated by 
illuminating all six (6) LED’s. 
 

LED: 

The system operating status (Compressor On or Off) is indicated by turning On the right most 

decimal point in the 3 Digit Display. 

INSIDE 
 
OUTSIDE 
 
SETPOINT 

https://appliancetechmanuals.com

Summary of Contents for AquaCooler OWC1211

Page 1: ...https appliancetechmanuals com...

Page 2: ...SCRIPTION Standard Features 4 5 Accessories 6 Unit Construction 7 8 Installation 9 10 Parts Replacement Procedure 11 12 Troubleshooting Guide 13 15 Preventive Maintenance 15 16 DIAGRAMS Piping Schemat...

Page 3: ...o achieve the desired high and low refrigeration system pressures Condenser water is regulated by a refrigeration system head pressure actuated water regulating valve GENERAL REQUIREMENTS A MINIMUM WA...

Page 4: ...C 24 1 2 OCEANAIRE VOLTAGE WATER COOLED SINGLE PHASE CAPACITY SELECTION CAPACITY SELECTION NUMBER CODE 12 13780 BTU HR 18 18840 BTU HR 24 23950 BTU HR 36 36100 BTU HR 60 60100 BTU HR 2 https appliance...

Page 5: ...50 5 50 at 85 F inlet 3 0 4 5 6 0 9 0 9 0 15 0 15 0 Condenser Coil Pressure Drop PSI 40 40 20 40 40 40 40 Water Valve Pressure Drop PSI Water Valve Connection4 Drain Connection Condensate Pump Head St...

Page 6: ...is constructed of 18 gauge galvanized steel with a platinum texture poly ester powder coated finish that will compliment any decor The entire cabinet is insulated with a sound absorbent insulation for...

Page 7: ...he tank and automatically switches off when the tank drains to a level of approximately 1 1 4 inches A built in pump safety switch turns off the air conditioner if the condensate line becomes plugged...

Page 8: ...rmanent drain When using a hose kit avoid sharp corners hot water pipes and kinking to assure proper water flow of the supply and return lines HIGH PRESSURE WATER VALVE High pressure water regulating...

Page 9: ...UNIT CONSTRUCTION 7 CONTROLLER EVAPORATOR FAN MOTOR EVAPORATOR COIL FAN MOTOR CAPACITOR EVAPORATOR DRAIN PAN COMPRESSOR CONDENSATE PUMP ELECTRICAL PANEL CASTERS https appliancetechmanuals com...

Page 10: ...er voltage will void the warranty CAUTION the use of an extension cord rated at least 15 Amps 115 volts for OWC12 and OWC18 20 Amps 250 volts for OWC3612 15 Amps 250 volts for OWC 12 24 30 Amps 250 vo...

Page 11: ...supply valve 3 Connect shut off valve to T branch 4 Insert a 3 8 pipe nipple in discharge end of water shut off valve 5 Thread coupling onto 3 8 pipe nipple and secure An alternate installation metho...

Page 12: ...d The mode selected is indicated by the Mode LED TEMP SELECT BUTTON Press and release to view inside supply air temperature discharge air temperature or set point The appropriate LED will be lit indic...

Page 13: ...nect the thermostat cable to the new thermostat 4 Reverse procedure to re install C CONDENSATE PUMP 1 Remove cabinet s left hand side panel 2 Remove front bracket securing condensate pump in base pan...

Page 14: ...e performed only by a qualified refrigeration serviceman PROBLEM THE ENTIRE UNIT DOES NOT RUN 1 CAUSE POWER INTERRUPTION REMEDY Check external power supply Look for blown fuses or tripped circuit brea...

Page 15: ...nd repair Evacuate unit and recharge 6 CAUSE Loose or defective wires FIXING Tug on wires to see if they will separate from connections 7 REASON Defective compressor REMEDY Check for shorts opens and...

Page 16: ...unit is properly sized for load Add supplemental unit if required PROBLEM NOISY OPERATION 1 CAUSE Copper tubing vibrating REMEDY Adjust by bending slightly to firm position Segregate tubes touching c...

Page 17: ...st 20 ft of water total head pressure on pump If combination of vertical height and horizontal drain line exceeds 20 ft of water pressure drop problems will occur PREVENTIVE MAINTENANCE AquaCooler Ser...

Page 18: ...efore attempting to service or remove any component 2 Be sure the floats move freely Clean as necessary 3 Remove the volute and check for obstructions Clean as needed 4 Clean the tank with warm water...

Page 19: ...17 PIPING SCHEMATIC WATER COOLED AIR CONDITIONER https appliancetechmanuals com...

Page 20: ...AquaCooler Water Cooled Air Conditioners Models OWC12 OWC18 OWC24 OWC36 OWC60 18 https appliancetechmanuals com...

Page 21: ...h the furnished written instructions or has been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any workmans...

Page 22: ...Form OWC ESM 05 00 https appliancetechmanuals com...

Reviews: