ICM
408
3-PHASE PLUG-IN VOLTAGE MONITOR
LII263-2
www.icmcontrols.com
800-365-5525
ICM CONTROLS
7313 William Barry Blvd.
North Syracuse, NY 13212
1. Disconnect or turn off power.
2. Tap off the main 3-phase line voltage and run field-installed
wires to the ICM408 control.
3. Connect the field-installed wires to the L1, L2 and L3
connections.
4. Set the DOM time delay to a minimum for testing purposes.
5. Break one line of your control circuit and connect to the
COM and N.O. connections on the ICM408.
6. The N.C. connection can be used as an alarm output.
7. Reapply or reconnect power.
8. After the DOM time delay, the unit should energize and the
green (load) LED should light.
9. If the red (status) LED is on solid, reverse any 2 line
voltage wires
at the ICM408
.
DO NOT CHANGE THE
WIRING SEQUENCE TO THE UNIT
.
10. If the red (status) LED is flashing, make sure the voltage
and unbalance levels are set correctly.
The ICM408 continuously monitors the
incoming line voltage for errors. When the line
voltage is appropriate, the ICM408 closes a set
of N.O. contacts and lights a green LED. When
the incoming voltage is outside of the user-set
parameters, the N.O. contacts open and the
red LED will flash a code for the particular fault
present. The control will also interrogate the
line voltage during the fault condition to avoid
short cycling and nuisance trips.
User Selectable Universal Voltage
: 190-480 VAC
Operating Frequency
: 50-60 Hz
User Selectable Unbalance Voltage:
2 to 8% (trips after 6 seconds of unbalance condition)
Power/Phase Loss Detection:
Within 100 mS
High/Low Voltage Cut-out:
± 12% – Detects within 100 mS
Phase Reversal Detection:
Detects phase reversal condition on power-up
User Selectable Delay on Make (staggered start) Timer:
.1 to 5 minutes
User Selectable Anti-Short Cycle/Delay on Break Timer:
.1 to 5 minutes
Heavy Duty SPDT Relay Output:
10A output to operate control circuitry.
Relay Contact Ratings:
N.C. contacts: 10A resistive @ 250VAC, N.O. contacts: 10A resistive @ 250VAC
Connection Terminals:
Screw down terminals on plug in base provide easy hookup for both line voltage and
control circuit wires.
Conformal Coated Circuit:
Conformal coated circuit provides protection in extreme environmental conditions.
Storage Temperature Range
: -40°C to +85°C
Maximum Operating/Storage Relative Humidity
: 95% non-condensing
WIRING DIAGRAM
SPECIFICATIONS
INSTALLATION
MODE OF OPERATION
STATUS LED INDICATORS
•
GREEN LED
= Load ON
•
RED LED
:
• Solid = Phase reversal
• 1 flash = DOM time
• 2 flashes = Low voltage
• 3 flashes = High voltage
• 4 flashes = Unbalance voltage
L1
L3
L2
Control Voltage
3-Phase
Load
8
7
6
5
4
3
2
1
8 2
1
(Optional alarm output)