2
SPECIFICATIONS
2OACH
MODEL: 2OACH
1211 1811 2412 3612 3632 3634 6012
6032 6034
COOLING CAPACITY
11,800
16,800
24,020
HEATING CAPACITY
11,000
15,600
22,000
VOLTAGE (V/Phase) at 60Hz
208-230/3 460/3 208-230/1 208-230/3 460/3
AMPS
10.4
14.1
14.9
19.6
17.2
8.7
32.0
20.4
14.8
TOTAL WATTS
1180
1670
2700
IN-RUSH CURRENT (AMPS)
60
75
68
113
93
60
178
162
87
PLUG TYPE
5-15P
5-20P
6-20P
6-30P
L15-30P L16-20P
6-50P
L15-30P L16-20P
EER
8.9
COMPRESSOR HP
1
1 1/2
2
COMPRESSOR RLA
9.5
12.3
10.5
13.6
8.8
5.0
27.6
18.1
9.0
COMPRESSOR LRA
50
63
48
83
77
35
158
137
62
EVAP CFM
400
600
810
EVAP MOTOR HP
CONDENSER CFM
580
930
1010
COND MOTOR HP
1/3
CONDENSATE
R-410A CHARGE (oz.)
18
40
37
(A) HEIGHT (in.)
37-3/4
(B) WIDTH (in.)
20
(C) DEPTH (in.)
25
NET WEIGHT (lb.)
180
400
520
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
2OACHSPECS010119
115/1
1200
1950
208-230/1
60,100
53,500
36,050
32,500
3620
6000
10.0
10.0
3
5
5 Gallon Condensate Tank - STANDARD (Pump Optional)
Pump - STANDARD (20 ft. Lift)
66
80
45-3/4
50-1/4
51-3/4
24
27-1/2
365
30
35
39-1/2
260
485
2200
1
1
1/8
1/3
1390
1/8
NOTES
* Dedicated Circuit and Time Delay fuse or Circuit Breaker are recommended
* Cooling Capacity is total BTUH at 80°DB/67°WB return air, with 95° DB Condenser Air
* Heating Capacity is total BTUH at 70°DB/60°WB Indoor, 47° DB/43° WB Outdoor
* CFM with free discharge
* Cooling EER is determined at high fan speed, with condenser air ducted into another area
* Sound Pressure, dB at 5 feet, commercial operation
* Amps and Watts at 208 Volts (208-230V Models)
COOLING AMBIENT OPERATING RANGE 65° TO 105°
May COOL down to 55° if equipped with hot gas bypass (factory installed)
HEATING AMBIENT OPERATING RANGE 45° TO 85°
Summary of Contents for 2OACH SERIES
Page 26: ...24 PIPING SCHEMATIC ...
Page 27: ...25 WIRING SCHEMATIC FOR 2OACH12 18 and 24 DISCHARGE TEMP SENSOR ...
Page 28: ...26 WIRING SCHEMATIC FOR 2OACH3612 DISCHARGE TEMP SENSOR ...
Page 29: ...27 WIRING SCHEMATIC FOR 2OACH6012 DISCHARGE TEMP SENSOR ...
Page 31: ...29 WIRING SCHEMATIC FOR 2OACH3632 DISCHARGE TEMP SENSOR ...
Page 32: ...30 WIRING SCHEMATIC FOR 2OACH3634 DISCHARGE TEMP SENSOR ...
Page 33: ...31 WIRING SCHEMATIC FOR 2OACH6032 DISCHARGE TEMP SENSOR ...
Page 34: ...32 WIRING SCHEMATIC FOR 2OACH6034 DISCHARGE TEMP SENSOR ...