background image

Solarion 

M210P

 EN V1.0 2015-10-20 © OC3 AG

Figure 3: Welding multiple solar panels on to roofing membrane or other membrane surface 

Multiple solar panels can be connected in series and parallel to reach desired power generation.  
As accepted good practice, the following installation recommendations should be abided by: 

The solar modules should be welded to each other by their neighbouring edges as shown in Figure 3.

There must be 150 mm of distance between glass edges of solar panels

In a group of solar modules there space between horizontal groups must be at least 150 mm

Use Solarion M210P series module for PVC based polymeric installation surface.

 This is crucial for

 

proper welding of the solar

 

module on to installation membrane. 

Electrical Installation

 

Modules  of  the  same  type  (i.e.  Solarion  M230  KEE)  and  power  class  (i.e.  235  Watt)  must  be  used  within  a  serially-
connected  module  string.  A Multicontact junction box is glued to the front side of the module on to membrane backing.  Removing 
the  junction  box  from  the  membrane,  or  opening  the  junction  box  will  void  the  module  guarantee.    The  male  and 
female connectors are labeled with “+” and “-“, respectively.  Same-type connectors must be used in the interconnection of Solarion solar 
modules.  All cables used in the solar system must be appropriate for long-term outdoor use (i.e. UV-resistant)   The insulation rating of the 
cable  must  be  equal  to  or  greater  than  the  highest  expected  open  circuit  voltage  (Voc)    Please  observe  all  local  regulations,  such  as 
building  and  electrical  codes,  in  your  region.    In  order  to  avoid  damage  to  the  cables,  do  not  lay  the  cables  on  sharp  edges,  and  it  is 
strongly  recommended  to  use  cable  ties  on  the  cables  such  that  they  are  not  able  to  sit  in  standing  or  run-off  water.    The  cable  cross 
sections for module interconnections must abide by standard practice with professional standards. 
Under  certain  circumstances,  Solarion  modules  may  generate  more  current  or  higher  voltage  as  the  current  and  voltage  measured  at 
standard test conditions (STC is defined as an irradiance of 1000 W/m2 at 25°C).  It is therefore important to use a minimum safety factor 
of 1.25 when specifying string fuses, string diodes, cables and inverters.  The maximum system voltage found on the module labels must 
not be exceeded. 
The use of additional system components such as fault detectors (e.g. RCD, GFDI, etc.), fuses, diodes or circuit breakers may be required 
due to local electrical or safety ordnances.  Thus safety regulations of these components must likewise be met.  Since the glass-membrane 
solar panels do not have any accessible conductive parts (i.e. frame), they need not be electrically grounded.  Please  be  aware  that 
local regulations and codes for functional grounding or substructure bonding of solar systems shall prevail. 
Each module string requires the use of serially-connected string diodes in order to avoid the flow of reverse current 
from  parallel  strings  or  from  defective  inverters.    It is recommended to use rectifier diodes with blocking voltages in accordance 
with the appropriate system voltage. The use of string fuses is not mandatory. 
For  a  system  voltage  of  1000  Volt,  a  maximum  32  modules  are  allowed  to  be  serially  connected  in  a  single  module 
string.    Based  on  the  aforementioned  requirements  for  the  use  of  string  diodes,  there  is  no  limit  to  the  number  of 
strings wired in parallel. 

Operation and Maintenance 

OC3  AG  recommends  that  a  specialist  perform  any  possible  required  maintenance  of  your  solar  system.    Routine 
maintenance is not necessary; however, it is recommended that the solar system be checked at least once per year for damage, soiling, 
etc.  Defective modules must be taken out of operation and immediately replaced.  Soiling (i.e.  pollen,  vegetation,  bird  lime,  etc.) 
on the front side of the module can be removed with a damp sponge or cotton cloth at  ambient  temperatures  between  10°C  and 
30°C.  De-mineralized  water  (i.e.  soft  water)  should  be  used  to  avoid  water  stains.    Under  no  circumstances  should 
abrasive detergents or soaps (i.e. surfactants) be used! 

Module Disposal 

Module disposal must be done in agreement with local ordinances.  The end customer is therefore responsible to correctly dispose of the 
modules.  If you have any questions on this matter, please contact OC3 AG, and we will consult on proper methods of disposal. 

Reviews: