Version 5.1_2021 (31 March 2021)
11
5.6.1.
Drip tray maintenance
Dirt, possibly including substances of a biological or microbiological nature, collects in the drip trays of
coolers. These substances may pose a threat to health. Therefore, be careful when cleaning these drip
trays. The drip tray under the cooler must be checked for dirt and cleaned if necessary.
5.7.
Droplet eliminator/separator
The droplet eliminator is mounted at the end of the drip tray to keep condensation away from the cooling
element. The droplet eliminator guides this to the drip tray.
5.7.1.
Droplet eliminator maintenance
Check the droplet eliminator for contamination every six months, dismantle and clean if necessary.
5.8.
Siphon
The draining of condensation (drip-tray) must be carried out using the siphon provided. This siphon serves
as a water shut-off to prevent possible unpleasant odours and to drain possible excess water from the drip
tray.
5.8.1.
Siphon maintenance
The negative pressure siphon (silicone rubber non-return valve) must be cleaned. Please ensure correct
assembly. See picture.
5.9.
Fan
The air flow through the heat exchangers is provided by directly driven plug fans with EC motors. The fans
are speed-controlled by means of a rotary knob located on the control panel.
Position number Description
1-2-3
3-piece coupling
4
diaphragm seat
5
Silicone diaphragm
6
Reducing ring 32-25
7
PVC pipe 32 L=40 / L=260
8
PVC elbow 32
9
PVC pipe 25 L=50
10
Hose coupling PVC 32 glue 30 hose
11
Flat ring (rubber)
12
Simplex plug 5/4"