background image

Date/Time:

 The date/time column reports the time at which data was logged from the Modbus device. Note: this is not 

necessarily the time at the start of the log cycle. Users with large number of devices may notice some of the Modbus devices 
at higher address numbers report 1 or 2 seconds after the first Modbus devices. This is because the 9600baud speed of the 
Modbus loop is not fast enough to log all Modbus devices in less than 1 second. If a device does not respond during a log 
cycle, the AcquiLite will attempt to query the device several more times. If a subsequent query is successful, the time of the 
successful query will be used in the log file but may be several seconds after the initial log cycle.

The log date/time is in Universal time. (UTC) This means that the data is logged with no shift for daylight savings time, and 
must be converted to local time for reporting purposes. When importing into a database, data should be kept in UTC time for 
ease of use. When reporting the final data, you should adjust the time to reflect the local timezone for which you are 
reporting. The data export option on the BMO website will prompt you for a timezone when you export the data, and will 
adjust the log date/time accordingly. Note: UTC is sometimes referred to as GMT. (Greenwich Mean Time)

Modbus Error:

 If the error value is not 0, the remainder of the columns for this line will be reported as NULL.

1

Operation not permitted

2

No such file or directory

3

No such process

4

Interrupted system call

5

Input/output error

6

No such device or address

9

Bad file descriptor

11 Resource temporarily unavailable
12 Cannot allocate memory
13 Permission denied
16 Device or resource busy
19 No such device
23 Too many open files in system
24 Too many open files
26 Text file busy
28 No space left on device
32 Broken pipe
52 Invalid Exchange
101 Network is unreachable
110 Connection timed out
111 Connection refused
113 No route to host
129 Illegal Function (function was not allowed by the slave device)
130 Illegal Data Address (the data address is not allowed by the slave device)
131 Illegal Data Value
132 Illegal Response Length
138 Gateway Path Unavailable (the Modbus/TCP gateway may be misconfigured)
139 Device Failed to Respond (the Modbus device may be off or disconnected)
140 Received invalid Modbus data checksum
141 Received response from unexpected device
142 Received unsolicited query, assume another Modbus master device is present.
143 Modbus device probe function received some good responses and some failures.
160 Start log (Entry in log file after AcquiLite starts up)
161 Stop log (Entry in log file if AcquiLite is shut down properly)
162 System time changed, caused logger to restart logging for intervals.
163 System auto-restart
164 Log entry corrupt.
165 Modbus device restart detected. 
192 Modbus device does not match the device type in the configuration file.
193 Modbus device's serial number changed.  (could be two devices with the same Modbus address)

Low/High Range Alarms:

 This number is a hex representation showing which data points are out of range. 0x01 shows 

data point 1 in alarm state. 0x04 shows data point 3 in alarm state.

Data Points:

 Data points are shown in the same order as the Modbus device configuration display in the Modbus/device list 

page. Data is displayed in floating point form. When a specific point is unavailable (A8332-8F2D broken wire alarm) or the 
point is not supported as part of the configuration (phase B current on a single phase H8163 meter hookup) the point will be 
logged as blank. This preserves the column structure of the file, and allows notation of invalid data. SQL databases often 

Page 24

A7810 AcquiLite – Data Acquisition Server

www.calcert.com

[email protected]

1.800.544.2843

0

5

10

15

20

25

30

Summary of Contents for AcquiLite EMB

Page 1: ...Data Acquisition Server Obvius LLC Installation and Operation Manual Model A7810 Date Aug 10 2011 Page 1 A7810 AcquiLite Data Acquisition Server www calcert com sales calcert com 1 800 544 2843 0 5 1...

Page 2: ...utside of Obvius s authorized facilities 4 has not been sold subject to other warranty terms specified at the time of sale and 5 is still owned by the original purchaser This warranty provides specifi...

Page 3: ...oting Ethernet Problems 18 System Options 18 Status 18 Processes 18 Date and Time 18 Universal Time Is Your Friend 19 System logs 19 Firmware Update 20 Diagnostics 20 Host Lookup 20 Connection Test 20...

Page 4: ...it connection point hub or switch IP address and Netmask check with system administrator Gateway address check with system administrator DNS server address check with system administrator HTTP Proxy a...

Page 5: ...ms Pulse rate option 100hz minimum pulse width 5ms Contact closure threshold 100 to 2 5k user selectable Pulse count values are stored in non volatile memory Isolation2 The RJ45 Ethernet is isolated t...

Page 6: ...erous if wire scraps come into contact with high voltage wires Step 4 Power up and diagnostics A power supply is not provided with the AcquiLite EMB therefore it is up to the installer to provide the...

Page 7: ...e AcquiLite or Dynamic Host Configuration Protocol DHCP address this process assigns an IP address dynamically to the AcquiLite when it is connected to the network from a host DHCP server or Direct co...

Page 8: ...ained automatically Simply select the Enable DHCP from the first TCP IP configuration menu Step 4 After the address information has been set you must reboot the AcquiLite Select the Previous Menu opti...

Page 9: ...d the scope of this document however A From the Windows start menu select the Settings Network Connections option Double click the Local Area network connection icon in the network folder then click t...

Page 10: ...steps for each Modbus device Step 7 Select the Modbus Setup menu option Specify the Modbus Loop Name This will become the name of the AcquiLite This is the name that will appear on the BMO website se...

Page 11: ...ord for read only access Log information is stored in var log modbus For read write delete access use the login name root and the admin password The three usernames specified are not able to be change...

Page 12: ...used to configure a Modbus device that is not presently connected to the system add a framework configured device or add a Modbus TCP connected device See the section on manually adding a device below...

Page 13: ...the page several buttons are present Done returns you to the device list page Log File This icon will display a table view of the most recent data in the current log file Use the log file export page...

Page 14: ...ta points are rotated about every 10 seconds The values on the LCD console are updated when the next log interval occurs Point Config Some devices have configurable point features Most data points are...

Page 15: ...dress already listed in the device list page Modbus TCP Gateway IP This option allows the AcquiLite to log data from a remote Modbus device that is attached to the LAN via a Modbus TCP gateway device...

Page 16: ...control based on the IP address of the system making the request The Modbus TCP protocol does not have provisions for any authentication password or other methods of security By default the gateway fe...

Page 17: ...the wireless diagnostics options will be present in the AcquiLite Please refer to the AcquiSuite A8812 or A8810 user manuals for further details on the wireless diagnostic features Networking Network...

Page 18: ...mmon mistake is configuring the Laptop IP to the same address as the IP address of the AcquiLite In order for the laptop and AcquiLite to communicate the IP addresses should not be identical see the b...

Page 19: ...data in the database in UTC format and then convert the information when generating a report for the user For example if you wish to draw a graph of KW over Time prompt the user for a date range say J...

Page 20: ...es will be displayed If any firmware updates are available a button to the right will be shown labeled Download The firmware files are asarm cramfs The main AcquiLite firmware file including the modbu...

Page 21: ...failure is due to the password not being correct LCD Console The AcquiLite has an LCD console and two push buttons labeled Menu and Select These can be used to configure some of the basic features of...

Page 22: ...ng requests This test does not verify if the DNS servers can actually resolve DNS names to IP addresses For a more complete test use the Connection Test web page in the AcquiLite diagnostics menu Modb...

Page 23: ...ame starts with mb xxx where xxx is the Modbus device address number One file with the log extension is the file where the most recent data is being stored Other log files have a gz extension These ar...

Page 24: ...No space left on device 32 Broken pipe 52 Invalid Exchange 101 Network is unreachable 110 Connection timed out 111 Connection refused 113 No route to host 129 Illegal Function function was not allowe...

Page 25: ...log files to your server you must manually delete them To delete log files refer to the FTP method of downloading log files One step detailed in the FTP section is how to delete a log file from the Ac...

Page 26: ...nformation about the transfer process use the Connection Test page in the Testing Diags menu on the AcquiLite for a full report of the data upload progress Retrieving Data From the AcquiLite Overview...

Page 27: ...s uploaded Designed for integration with existing energy reporting systems Contact Obvius technical support for further details and sample scripts Removing Data From the AcquiLite When using an HTTP P...

Page 28: ...be shown on that dialog Simply copy paste this URK into your link The AcquiLite can provide Modbus device data in XML format This feature coupled with browser based AJAX Javascript can provide a very...

Page 29: ...roximately 4 x 4 25 x 2 deep The AcquiLite has 4 mounting holes for use with a 6 screw The drawing above shows the relative position of the mounting holes Page 29 A7810 AcquiLite Data Acquisition Serv...

Reviews: