Mounting instructions, PYROLINE
®
BSK fire protection duct
Planning an installation
6 3
Approved cables
PYROLINE
®
Con BSK fire protection duct for fire encapsulation (I90/
I120)
All cable types up to a rated voltage of 1 kV can be routed.
Note!
Cables with integrated maintenance of electrical function may not be
routed in the same duct with cables for general power supply.
PYROLINE
®
Con fire protection duct for maintenance of electrical
function (E30/E90)
All cable types up to a rated voltage of 1 kV can be routed. There are no
special requirements for the fire behaviour of the cables.
Note!
When dimensioning the cables, note that the electrical resistance of the
conductors in the cable is increased through heating. A larger conductor
cross-section may be required.
Comply with the maximum approved cable load (see Table 5). The
approved cable load is dependent on the classification and the mounting
version of the fire protection ducts:
Classification
Wall/ceiling mounting
Mounting
with
support
system
Cable load
Cable
directly on
top
Cable mounting
with separating
bracket/separat-
ing clamp
Maintenance
of electrical
function E
–
X
–
≤ 18.0 kg/m
Maintenance
of electrical
function E
X
–
–
≤ 11.0 kg/m
Maintenance
of electrical
function E
–
–
X
≤ 35.0 kg/m
Fire resist-
ance class I
–
X
–
≤ 35.0 kg/m
Fire resist-
ance class I
X
–
–
≤ 11.0 kg/m
Fire resist-
ance class I
–
–
X
≤ 35.0 kg/m
Tab 5:
Maximum approved cable load