Target group
Mounting and installation of the device may only be
carried out by an electical technician .
General safety information
– Before working on power cables, ensure that they
are deenergised, and secure them against uninten-
tional switch-on!
– Do not carry out mounting work during a storm!
– Comply with national laws and regulations (e . g . IEC
60364-5-53; VDE 0100 part 534)!
Mounting and installation
– Mounting of single device on mounting plate
(accessory):
Fig .
4
: MCF-MS-P1 for bus bar mounting (item no .
5096 994),
Fig .
5
: MCF-MS-M10 for direct bus bar mounting
(item no . 5096 990) .
– 3-pole design MCF-MS-P3 as shown on fig .
6
mounted on a bus bar
1
or on the wall
2
. When
mounted on the wall, connect the mounting plate to
the equipotential system by a PE conductor .
– Push the heat-shrinkable sleeve over the conductor .
– Use cable lug and conductor connection set to fasten
the conductor L to the device (fig .
3
) .
– Push the heat-shrinkable sleeve over the conductor
L, flush to the upper part of the device, and shrink it
(fig .
2
) .