Installation instructions
V50-...-385
OBO Bettermann GmbH & Co. KG
9
EN
ensuring that the lockable hat rail holder is un-
locked (Figure
2
).
• Maintain the stripping length and tightening
torque (Figure ).
• Connection according to the circuit diagram
(TN systems or TN-S / TT systems).
Dismantling
Figure :
• Unlock and remove arresters in the manner
shown.
• Open the hat rail holder with a flat screwdriver
and engage it (see also Figure
2
). Remove
the protection devices.
Faults
If the integrated cut-off unit trips (e.g. due to age
on account of multiple, very high overvoltages),
the visual display (Figure ) switches from green
(grey) to red. In this case, remove the arrester
and insert a new arrester (available separately,
V50: item no. 5093 508, C50: item no. 5095 609).
In the case of devices with multiple arresters, it
must be assumed that the other arresters of this
device have experienced the same load. We rec-
ommend that you check them and, if necessary,
also replace them. Dispose of replaced arrest-
ers.
Remote signalling
Figure (only V50-..+FS..):
When at least one arrester is disconnected, the
changeover contact in the remote signalling mod-
ule switches from 11/12 to 11/14. Remote signal-
ling can be switched as an NO or NC contact.
This allows control of suitable signalling compo-
nents (e.g. central error messages, light or
acoustic signal).
• Connect the remote signalling cables as
shown, in so doing maintaining the specified
cable cross-section and the stripping length.
Maintenance
We recommend carrying out a visual check of
the visual display every 2-4 years or after light-
ning strikes.
Disposal
– Packaging as household waste
– Protection device/arrester as electronic waste.
Comply with the local waste disposal regulations.
Technical data
V50 ... 385
C50
IEC / DIN EN
61643-11
Class I + II / Type 1 + 2
U
C
385 V AC
255 V AC
U
N
230 V AC (± 10 %)
U
P
≤ 1700 V
U
res
@
1 kA
8/20
1100 V
–
5 kA
8/20
1200 V
–
7 kA
8/20
1200 V
–
12,5 kA
8/20
1400 V
–
I
imp
12.5 kA
50 kA
I
n
30 kA
50 kA
I
max
50 kA
80 kA
I
SCCR
50 kA
eff
IP code
IP 20 (built-in)
installation point
indoor
Number of Ports
One-Port-SPD
System
TN-, TT
TN-, TT (NPE)
-40 – +80 °C
-40 – +176 °F
5 – 95 %
Protection path
Protection path
L – PEN
L – N
L – PE
N – PE
N – PE
x
x
x ≥ 1,5 mm (0 in)
to metal parts/devices
F1
F2
+
F1 >160 A
gL / gG
F2 ≤ 160 A
gL / gG
– (NPE)
F1
F2
2
F1 ≤ 160 A
gL / gG
– (NPE)
1.5 – 35 mm
2
(AWG 16 – 2)
1.5 – 35 mm
2
(AWG 16 – 2)
1.5 – 35 mm
2
(AWG 16 – 2)
Accessories
a
a ≤ 15.5 mm (0.6 in)
5012 010
3 x 16 mm
2
(3 x AWG 6)
T1
T2