3.5 Spa Heat Pumps Electrical Wiring 

NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it 
simply prevents the flow of electricity to or from the pool water. Grounding the unit is still 
required to protect you against short circuits inside the unit. Bonding is also required.

3.INSTALLATION AND CONNECTION

3.6 Initial startup of the Unit  

NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to 
circulate water through the heat exchanger.

Start up Procedure - After installation is completed, you should follow these steps: 
1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire 
controller, It should start in  several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is 
cooler(Between 5-10  )
4. With the unit operating turn the filter pump off. The unit should also turn off automatically, 
5. Allow the unit and pool pump to run 24 hours per day until desired pool water temperature 
is reached. When the water-in temperature reach setting, The unit just 
shuts off. The unit  will now automatically restart (as long as your pool pump is running)when 
the pool temperature drops more than 2

below set temperature.  

Water Flow Switch - the unit is equipped with a flow switch that turns it on when the pool 
pump is running and shuts it off when the pump shuts off. This switch is the same type used in 
all gas pool heaters and is factory adjusted for normal pool installations. If the pool water 
level is more than a few feet above or below the thermostat knob of the unit, your dealer may 
need to adjust it at initial startup. 

Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to 
protect control circuit components and to eliminate restart cycling and contactor chatter. 
This time delay will automatically restart the unit approximately 3 minutes after each control 
circuit interruption. Even a brief power interruption will activate the solid state 3 minute 
restart delay and prevent the unit from starting until the 5 minute countdown is completed. 

The unit has a separate molded-in junction box with a standard electrical conduit nipple 
already in place. Just remove the screws and the front panel, feed your supply lines in 
through the conduit nipple and wire-nut the electric supply wires to the three connections  
already in the junction box (four connections  if three phase). To complete electrical hookup, 
connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as 
permitted by local electrical authorities) to a dedicated AC power supply branch circuit 
equipped with the proper circuit breaker, disconnect or time delay fuse protection. 

Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be 
located within sight of and readily accessible from the uni, This is common practice on 
commercial and residential air conditioners and heat pumps. It prevents remotely-energizing 
unattended equipment and permits turning off power at the unit while the unit is being 
serviced. 

Disconnect

Summary of Contents for C8b

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual...

Page 2: ......

Page 3: ...Unit 4 Usage and Operation 4 1 4 2 4 3 5 Maintenance and Inspection 5 1 5 2 Malfunction table 6 Appendix Spa Heat Pumps Location Spa Heat Pumps Plumbing Spa Heat Pumps Electrical Wiring Function of wi...

Page 4: ...comprises an efficient rotary scroll compressor and a low noise fan motor which guarantees its quiet operation 4 Advanced controlling The unit includes micro computer controlling allowing all operati...

Page 5: ...uantity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Shipping Dimensions L W H...

Page 6: ...croll 2 120 2 850 Horizontal 56 1 5 9 0 12 1120 470 1240 1200 490 1380 130 140 REFRIGERANT R410A Unit Heating Capacity Heating Power Input Running Current Power Supply Compressor Quantity Compressor F...

Page 7: ...is C25Tb Water Inlet Water Outlet A E D C B TYPE B A C D SIZE E unit mm Oasis C8b C13b H13b 650 1000 700 420 400 255 101 Horizontal vision Vertical vision Oasis C17b H17b 850 1120 720 470 440 400 97 T...

Page 8: ...asis C35T Vb Oasis C50T Vb Models EH9b 1002 658 430 455 630 Water Inlet Water Outlet Horizontal vision Vertical vision 1130 1490 1464 480 735 Water inlet Water outlet Drainage Horizontal vision Vertic...

Page 9: ...or the installer 3 1 Installation illustration 3 INSTALLATION AND CONNECTION Chlorinator cell Water outlet Pool Valve Water supply Water inlet Water pump Sand filter or other type filter By pass valv...

Page 10: ...O NOT place the unit to shrubs which can block air inlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Spa He...

Page 11: ...n and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 3 4 clear vinyl tubing which can be pushed on by hand and run to a s...

Page 12: ...e type used in all gas pool heaters and is factory adjusted for normal pool installations If the pool water level is more than a few feet above or below the thermostat knob of the unit your dealer may...

Page 13: ...on NO Symbol Name Function On off Mode Up Press this button can start up or shut down the unit cancel the current operation or back to the upper interface Press this button can switch modes or save pa...

Page 14: ...in display area gives the inlet water temperature measured value Outlet water It is showed when the AUX display area gives the outlet water temperature measured value Minute It is showed when the main...

Page 15: ...ressing Attention The modes switching is useless if the unit you buy is single cold single heat unit For example Press Press Press Press TEMP OUT MODE SET TEMP IN C TEMP OUT MODE SET TEMP OUT MODE SET...

Page 16: ...ng press to increase value or press to decrease value and press to save setting Press can not save setting parameter and back to main interface Attention If there is no operation for 5s system will re...

Page 17: ...our minute Flashing TEMP IN C TEMP OUT MODE SET Flashing Press TEMP IN C TEMP OUT MODE SET Press or TEMP IN C TEMP OUT MODE SET Press to save hour value setting TEMP IN C TEMP OUT MODE SET Press or TE...

Page 18: ...erface press to cancel Attention 1 If there is no operation for 5s system will remember clock setting and back to the main interface 2 By pressing till the off flashing you can set the timer off witho...

Page 19: ...OFF TEMP IN C TEMP OUT MODE SET ON OFF TEMP IN C TEMP OUT MODE SET ON OFF Press Press or TEMP IN C TEMP OUT MODE SET ON OFF TEMP IN C TEMP OUT MODE SET Press ON OFF The timer on and off has been set F...

Page 20: ...ample TEMP IN C TEMP OUT MODE SET ON OFF The timer on off has been set Press for 2s TEMP IN C TEMP OUT MODE SET ON OFF ON is flashing TEMP IN C TEMP OUT MODE SET OFF The setting of timer on has been c...

Page 21: ...locked NOTES When the unit is in alarming state the key lock can be removed automaticly TEMP IN C TEMP OUT MODE SET Hold on Locked TEMP IN C TEMP OUT MODE SET MODE SET 8 Malfunction display There will...

Page 22: ...19 28 28 27 Meaning Heating inlet target temp Adjustable Adjustable Adjustable 4 3 Parameter table Cooling inlet target temp Auto inlet target temp Remark Default 4 USAGE AND OPERATION...

Page 23: ...pressure of the refrigerant system should only be serviced by a certified technician Discharge all water in the water pump and water system so that freezing of the water in the pump or water system do...

Page 24: ...ide antifreezing protection The secondary anti freezing protection Discharge Temp Of system 2 is too high The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit The temp S...

Page 25: ...25 26 27 28 29 30 31 32 Electric heater overload protection input Compressor 1 overload protection input Water flow switchprotection input Compressor 2 overload protection input System protection inp...

Page 26: ...e handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 9...

Page 27: ...0 1 sec 30mA less than 0 1 sec 13 25A 25 30A 30 40A 40 55A 55 70A Phase line 2 3 1 5mm 2 3 4mm 2 3 6mm 2 3 10mm 2 3 16mm 2 3 25mm 2 1 5mm 2 1 5mm 2 4mm 2 6mm 2 10mm 2 16mm MCB 20A 40A 40A 63A 80A 100...

Page 28: ...nel 50 connector PVC elbow wire fixer Thermostatic expansion valve wire fixer water proof cover wire controller pressure meter chassis filter Drainage pipe fittings compressor 4 way valve Note Code 35...

Page 29: ...capacitor soft start PCB plastic cover pressure switch 4 way valve needle valve pressure switch chassis wire controller water proof cover Note Code 2001 1116 32012 210080 3500 2701 32008 220040 3404...

Page 30: ...8 2178 2000 3502 3512 2126 3512 2155 2000 3116 2000 3619 95005 310114 32008 210009 2000 3603 3512 2121 20000 140003 Part name female branch tee condenser water flow switch heat exchanger right panel 5...

Page 31: ...t exchanger right panel 50 connector PVC elbow wire fixer wire fixer water proof cover wire controller chassis filter Drainage pipe fittings compressor AC contactor Note Code 3512 2158 4000 3901 2000...

Page 32: ...dle right panel chassis wire fixer compressor wire fixer wire controller water proof cover 4 way valve pressure meter thermostatic expansion valve needle valve pressure switch filter Note Code 2000 36...

Page 33: ...r 3 terminal Gas Liquid Separators handle right panel chassis wire fixer compressor wire fixer wire controller water proof cover needle valve pressure switch filter Note Code 2000 3602 3509 2156 3512...

Page 34: ...fixer wire fixer filter drainage pipe fittings pressure switch 4 way valve needle valve pressure switch Thermostatic expansion valve wire controller water prrof cover Gas Liquid Separators Code 32018...

Page 35: ...ssure gage 3 way valve right panel water proof sheath water proof sheath filter 4 way valve pressure gage needle valve TX valve pressure switch LCD wire controller water proof box Code 2000 1440 32018...

Page 36: ...e gage 3 way valve right panel water proof sheath water proof sheath filter 4 way valve pressure switch needle valve TX valve pressure switch LCD wire controller water proof box Code 2000 1440 32018 2...

Page 37: ...or compressor 4 way valve left condenser Part Code 32006 210047 35005 210012 35005 210017 35005 210002 35005 210006 4000 7707 35005 210010 20000 220068 95005 310156 95005 310114 20000 360023 2001 3602...

Page 38: ...7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 NO 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 PartName pipe connector PVC 3 way valve PVC elbow PVC pipe PVC fixe...

Page 39: ......

Page 40: ...Code 20120807 0001 Code 20120807 0001...

Reviews: