24 Malfunctions
Malfunction
Cause
Remedy
No display
−
No 24V voltage supply
−
Unit poles reversed
−
Check the voltage supply and ensure all
connections are properly established
No network connection, WECS not online
(no
Linked
symbol on the display)
−
Network IP address incorrect
−
More than one WEPS in the network
with the same IP address
−
The default IP address at delivery is
192.168.003.011
−
Ensure that the computer is allocated a
fixed IP address. Ensure that the first
three numbers of the IP address of the
computer and the WECS match.
e.g.192.169.003.XXX
No DMX on Universe 1
−
DMX terminal incorrectly connected to
the terminal block
−
Both Universes are set to Universe 2 in
the setup menu
−
Check the terminals
DMX 1/DMX 2
−
Access 8.Setup and set Universe 1 to 1
and Universe 2 to 2
RDM not functional
−
DMX terminal incorrectly connected to
the terminal block
−
The connected devices are not RDM
capable
−
There is a DMX Splitter connected
between the WECS and the devices
which are not RDM capable
−
RDM deactivated
−
Check the terminals
DMX 1/DMX 2
−
Access main menu 8.Setup and set RDM
Active 1 to ON and RDM Active 2 to ON
The output is always accessed
−
The manual setting of the
Toggle Out
function is given priority over access by
the WEPS software
4.Port Out
function: Reset the output by
means of the
Toggle Out
function.
Date or time are wrong after interrupting the
power supply
−
The internal battery is low
−
Send in the unit for maintenance.
22188-10-14_GA_WECS II-512-1024-41 41
06.10.2014 12:53:00
Summary of Contents for WECS II 512 DMX/02
Page 6: ... DE 4 Abmessungen 22188 10 14_GA_WECS II 512 1024 6 6 06 10 2014 12 52 58 6 ...
Page 27: ...27 GB 4 Dimensions 22188 10 14_GA_WECS II 512 1024 27 27 06 10 2014 12 52 59 ...
Page 48: ... FR 4 Dimensions 22188 10 14_GA_WECS II 512 1024 48 48 06 10 2014 12 53 00 48 ...
Page 69: ...69 ES 4 Dimensiones 22188 10 14_GA_WECS II 512 1024 69 69 06 10 2014 12 53 01 ...