nvent Raychem NGC-40-BRIDGE Installation Instructions Manual Download Page 5

nVent.com | 5

RESET

NGC-40 BRIDGE MODULE

Ethernet

Ethernet

To upstream 

device

To upstream 

device

RS-232

RS-232

Local RS-232 

to Laptop

Local RS-232 

to Laptop

Local RS-232 (COM 3) & Ethernet

Switch Setting RS-232

User Interface – Configuration Switch
A slide switch is provided on the front of the module to allow 

the user to set the bridge into a known state for configuration 

of the communication ports, as shown in the following table:

Switch Position

Bridge  

Module Settings

SET 

Configuration mode

RUN  

Normal operating 

mode

Modbus address

1

Settings based on the 

user configuration 

parameters

Local RS-232

Protocol

RTU

Data rate

9600 baud

Data bits

8

Stop bits

2

Parity

No parity

COM 1 In

COM 1 In

11

55

99

++

––

RESET

NGC-40 BRIDGE MODULE

Field

terminal

block

Field

terminal

block

COM 2 In

COM 2 In

33

77 11

11

++

––

++

––

++

––

Earth grounding

bar located at the

bridge module

Earth grounding

bar located at the

bridge module

Earth grounding

bar located at the

bridge module

Earth grounding

bar located at the

bridge module

To upstream

device

To upstream

device

To upstream

device

To upstream

device

RESET

NGC-40 BRIDGE MODULE

COM 1 Out

COM 1 Out

22

66 10

10

++

––

COM 2 Out

COM 2 Out

44

88 12

12

++

––

120 ohm 

termination

resistor

120 ohm 

termination

resistor

120 ohm 

termination

resistor

120 ohm 

termination

resistor

Field

terminal

block

Field

terminal

block

Earth grounding

bar located at the

bridge module

Earth grounding

bar located at the

bridge module

Earth grounding

bar located at the

bridge module

Earth grounding

bar located at the

bridge module

Wiring for Com 1 & Com 2 must be terminated on a panel 

mounted terminal block. No ground wires should be 

terminated on terminals 9 & 11. Terminate Com shields 

at the panel mounted field terminal block chassis ground. 

The Com cable shield from the field terminal block to the 

Bridge should be terminated at the earth ground bar.

Wiring for Com 1 & Com 2 must be terminated on a panel 

mounted terminal block. No ground wires should be terminated 

on terminals 10 & 12. Terminate Com shields and 120 Ω 

termination resistors (included) at the panel mounted field 

terminal block as shown. The Com cable shield from the field 

terminal block to the Bridge should be terminated at the earth 

ground bar.

RS-485 Connection Diagrams – European Installation Technique

COM 1&2 Connections (In)

COM 1&2 Connections (Out) and RS-485 Termination Resistor 

Summary of Contents for Raychem NGC-40-BRIDGE

Page 1: ...D 1 NGC 40 BRIDGE serial cable TTC 10332 005 This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire For technical support call...

Page 2: ...50 ft maximum Data rate 9600 19 2K 38 4K 57 6K 115 2K baud Data bits 7 or 8 Parity None even odd Stop bits 0 1 2 Tx delay 0 5 sec Protocol Modbus RTU or ASCII Connection terminals RJ 11 CAN NETWORKING...

Page 3: ...s CAN network activity Off No link detected Green Link OK receive data packets Yellow Transmit data packets Red flashing Network error COM Indicates COM1 2 RS 485 activity Off No activity Green flashi...

Page 4: ...e terminated on terminals 9 11 Terminate Com shields at the panel mounted field terminal block chassis ground Wiring for Com 1 Com 2 must be terminated on a panel mounted terminal block No ground wire...

Page 5: ...device RESET NGC 40 BRIDGE MODULE COM 1 Out COM 1 Out 2 2 6 6 10 10 COM 2 Out COM 2 Out 4 4 8 8 12 12 120 ohm termination resistor 120 ohm termination resistor 120 ohm termination resistor 120 ohm ter...

Page 6: ...11 11 Earth grounding bar located at the bridge module Earth grounding bar located at the bridge module Panel Terminal Block Panel Terminal Block Panel Panel To next RMM2 To next RMM2 Field Field Whe...

Page 7: ...n Module CAN 24 Vdc Primary Supply 24 Vdc Primary Supply 24 Vdc Power supply shall have a means for disconnect from line voltage Power supply shall have a means for disconnect from line voltage Redund...

Page 8: ...emperature is outside this range a space heater and or cooling fan will be required in the panel 2 Determine locations for the NGC 40 BRIDGE assembly in the electrical panel The NGC 40 BRIDGE should b...

Page 9: ...23 IN IN OUT OUT CAN 24 Vdc HTC HTC3 or I O Module 22 IN IN OUT OUT CAN 24 Vdc HTC HTC3 or I O Module 21 20 Modules per Power Supply 20 Modules per Power Supply 100 240 Vac In 100 240 Vac In 20 Modul...

Page 10: ...426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its a...

Reviews: