GENERAL

Supply voltage

24 Vdc ± 10%

Internal power consumption

< 3.6 W per NGC-40-BRIDGE

Ambient operating temperature

–40ºC to 65ºC (–40ºF to 149ºF)

Ambient storage temperature

–40ºC to 75ºC (–40ºF to 167ºF)

Environment

PD2, CAT III

Max. altitude

2,000 m (6,562 ft)

Humidity

5 – 90% noncondensing

Mounting

Din Rail – 35 mm

ELECTROMAGNETIC COMPATIBILITY

Emissions

EN 61000-6-3   Emission standard for residential, commercial and light industrial environments

Immunity

EN 61000-6-2   Immunity standard for industrial environments

COMMUNICATIONS COM1, COM2

Type

2-wire RS-485

Cable

One shielded twisted pair

Length

1,200 m (4,000 ft) maximum

Quantity

Up to 255 devices per port

Data rate

9600, 19.2K, 38.4K, 57.6K, 115.2K baud

Data bits

7 or 8

Parity

None, even, odd

Stop bits

0, 1, 2

Tx delay

0 – 5 sec.

Protocol

Modbus RTU or ASCII

Connection terminals

Wago cage clamp terminals

COMMUNICATIONS COM3

Type

RS-232

Cable

Custom TTC# 10332-005

Length

15 m (50 ft) maximum

Data rate

9600, 19.2K, 38.4K, 57.6K, 115.2K baud

Data bits

7 or 8

Parity

None, even, odd

Stop bits

0, 1, 2

Tx delay

0 – 5 sec.

Protocol

Modbus RTU or ASCII

Connection terminals

RJ-11

CAN NETWORKING PORT

Type

2-wire isolated CAN-based peer-peer network. Isolated to 300 V.

Connection

Two 8-pin RJ-45 connectors (both may be used for Input or Output connections)

Protocol

Proprietary NGC-40

Topology

Daisy chain

Length

10 m (33 ft) maximum

Quantity

Up to 80 CAN nodes per network segment

Address

Unique, factory assigned

ETHERNET

Type

10/100 BaseT Ethernet network

Length

100 m (328 ft)

Data rates

10 or 100 MB/s

Protocol

Modbus/TCP

Connection terminals

Shielded 8-pin RJ-45 connector on front of module

PROGRAMMING AND SETTING

LED indicators

Alarm conditions

RESET, Configuration lost, CAN communications fail

Configuration switch

SET/RUN slide switch on front of module

CONNECTION TERMINALS

Wiring terminals

Cage clamp, 0.5 to 2.5 mm² (24 to 12 AWG)

CAN networking and module power

Two RJ-45s, one each IN and OUT. Provides CAN bus signals and +24 Vdc power.

HOUSING

Size

45.1 mm (1.78 in) wide x 87 mm (3.43 in) high x 106.4 mm (4.2 in) deep

Summary of Contents for Raychem NGC-40-BRIDGE

Page 1: ...D 1 NGC 40 BRIDGE serial cable TTC 10332 005 This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire For technical support call...

Page 2: ...50 ft maximum Data rate 9600 19 2K 38 4K 57 6K 115 2K baud Data bits 7 or 8 Parity None even odd Stop bits 0 1 2 Tx delay 0 5 sec Protocol Modbus RTU or ASCII Connection terminals RJ 11 CAN NETWORKING...

Page 3: ...s CAN network activity Off No link detected Green Link OK receive data packets Yellow Transmit data packets Red flashing Network error COM Indicates COM1 2 RS 485 activity Off No activity Green flashi...

Page 4: ...e terminated on terminals 9 11 Terminate Com shields at the panel mounted field terminal block chassis ground Wiring for Com 1 Com 2 must be terminated on a panel mounted terminal block No ground wire...

Page 5: ...device RESET NGC 40 BRIDGE MODULE COM 1 Out COM 1 Out 2 2 6 6 10 10 COM 2 Out COM 2 Out 4 4 8 8 12 12 120 ohm termination resistor 120 ohm termination resistor 120 ohm termination resistor 120 ohm ter...

Page 6: ...11 11 Earth grounding bar located at the bridge module Earth grounding bar located at the bridge module Panel Terminal Block Panel Terminal Block Panel Panel To next RMM2 To next RMM2 Field Field Whe...

Page 7: ...n Module CAN 24 Vdc Primary Supply 24 Vdc Primary Supply 24 Vdc Power supply shall have a means for disconnect from line voltage Power supply shall have a means for disconnect from line voltage Redund...

Page 8: ...emperature is outside this range a space heater and or cooling fan will be required in the panel 2 Determine locations for the NGC 40 BRIDGE assembly in the electrical panel The NGC 40 BRIDGE should b...

Page 9: ...23 IN IN OUT OUT CAN 24 Vdc HTC HTC3 or I O Module 22 IN IN OUT OUT CAN 24 Vdc HTC HTC3 or I O Module 21 20 Modules per Power Supply 20 Modules per Power Supply 100 240 Vac In 100 240 Vac In 20 Modul...

Page 10: ...426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its a...

Reviews: