3.4 Commissioning
The cabinet is completely wired and preconfigured. After connecting the power and water
supply, it can be put into operation.
ATTENTION
Damage due to leaking water!
Fittings may have loosened due to transport or during installation.
Before commissioning, all fittings of the water circuit must be checked and tightened if
necessary.
The leaktightness must be checked during filling of the system.
ATTENTION
Damage due to condensation and spraying water!
The cabinet doors must be closed for operation. If the cooling module is operated in an
open cabinet, condensation water will be produced around the heat exchanger, which is
distributed by the fans in the enclosure and can damage the electronics components.
The cabinet is equipped with door contact switches. When the doors are
open, the cooling module is shut off, the fans are disabled.
To ensure proper function and cooling performance, the front 19" plane must
be sealed off from the rear part of the cabinet by suitable air baffle plates and
seals.
Summary of Contents for 10130-325
Page 1: ...1 nVent SCHROFF Cooling Cabinet LHX User Manual Release 1 0 07 04 2021 Doc No 61130 210...
Page 27: ...Date 2021 04 07 Page 27 of 47...
Page 28: ...Date 2021 04 07 Page 28 of 47 Screen Upgrade...
Page 31: ...Date 2021 04 07 Page 31 of 47 4 2 2 Display menu...
Page 44: ...Date 2021 04 07 Page 44 of 47 23130 662 Water hoses duct for rear panel...
Page 46: ...Date 2021 04 07 Page 46 of 47 8 5 Air flow Air flow LHX 5 kW Air flow LHX 10 kW...
Page 47: ...Date 2021 04 07 Page 47 of 47 8 7 Noise Level Noise level LHX 5 kW Noise level LHX 10 kW...