APPENDIX A

Specific Conditions of Safe Use

The enclosure of the device shall be fitted with a locking mechanism such that it is only accessible with the 
use of a tool.

To maintain an internal pollution degree 

2

 environment, after opening the enclosure, make sure there is no visible 

condensation or dust. Power the device and let it heat up for 

5

 minutes before closing the enclosure door.

Only install in areas with low risk of mechanical impact.

Enclosure openings must be filled by equipment marked for use in ATEX / IECEx Zone 

2

 areas, and match or 

exceed the IP rating of the enclosures. General Guide to Cable Entry Positions into Cable Gland or Enclosure Side: 

•  Maximum hole diameter is major thread diameter of cable gland plus 

0

.

7

 mm (.

03

")

•  Minimum material to be maintained between holes: Glands M

16

 through M

32

15

mm (

0

.

59

") Glands 

M

35

 through M

75

20

 mm (

0

.

79

") Glands M

75

 through M

100

35

 mm (

1

.

38

"). Prior to making holes in the 

enclosure wall or gland plate, verify that the selected gland will not interfere with the sealing washer  
and locknut

•  Select a gland for the correct application with the proper certifications. Make certain all cable gland 

accessories are included for through hole installation. Additional accessories may include locknut and 
sealing washers

•  Install the gland in accordance to the manufacturer’s instructions

•  Holes must be located to prevent sealing washer and locknut from interfering with gasket

•  Externally mounted antennas and accessories must be suitable for ATEX / IECEx Zone 

2

 areas, and match 

or exceed the IP rating of the enclosures

•  The fuse for incoming power shall be considered user replaceable. Refer to Enclosure Drawing Bill of 

Materials for the correct Current Rating, Model, and Part Number of the fuse. Prior to replacing the fuse, 
disable or disconnect from power. Upon replacing the fuse, remove the fuse plug / housing, replace the 
fuse per note above, close and re-seat the fuse plug / housing securely

Summary of Contents for Elexant 9200i

Page 1: ...nVent com RAYCHEM 1 RAYCHEM AR H60819 Elexant9200i EN 2009 Elexant 9200i Wireless Communications Interface...

Page 2: ...enna Package Variants 5 1 1 4 Product Features 5 1 2 Vital Information 6 1 3 Technical Support 6 1 4 Supporting Services 6 2 INSTALLATION AND WIRING 6 2 1 Initial Inspection 6 2 2 Operator Safety Cons...

Page 3: ...be defined at the time of purchase Engineering Services typically define the equipment that is needed in order to meet a specific application Additional copies of this user manual may be ordered sepa...

Page 4: ...A PC 900 SW EXT Elexant 9200i 900 MHz Phoenix Contact module in SS enclosure with window and external antenna connection antenna coax sold separately 10392 108 9200i A PC 024 FW Elexant 9200i 2 4 GHz...

Page 5: ...GI antenna with 3 meter coaxial cable antenna bracket and gland 9200i ANT C 9200i ANT C Customized Antenna Package Accessory Table 2 Elexant 9200i Antenna Packages Notes 1 Many countries restrict the...

Page 6: ...cal Support Contact nVent Customer Care at North America Email thermal info nVent com Tel 1 800 545 6258 Europe Middle East Africa Email thermal info nVent com Tel 32 16 213 511 Asia Pacifc Email cn t...

Page 7: ...plays the different physical assemblies for the common Variants of the Elexant 9200i Fiberglass Enclosure Pre mounted Antenna Stainless Steel Pre mounted Antenna Fiberglass Enclosure Externally mounte...

Page 8: ...No supply voltage present On Supply voltage OK DAT Green LED indicating status of bus communications Off No communication Flashing Unit in Configuration mode On Cyclic data communication ERR Red LED i...

Page 9: ...ode Overload 0 VDC 868 MHz Radio Levels LED Bar Graph 1 2k 9 6k 19 2k 60k 120k RSSI voltage nVent RAYCHEM Elexant 9200i RM RSSI LED 1G 90 dBm 85 dBm 80 dBm 75 dBm 70 dBm 2 5 V nVent RAYCHEM Elexant 92...

Page 10: ...K 1 0 V nVent RAYCHEM Elexant 9200i RM RSSI LED 1W Not Connected Configuration more or overload 0 V 2 5 Mounting and Removal Procedures The ideal mounting method is to secure the enclosure to channel...

Page 11: ...on Terminal Block TB 2 Figure 3 RS 485 Connections 2 6 3 Antenna Coaxial Connection Depending on the package purchased an external antenna may need to be connected TNC m TNC f TNC m Connector RP TNC m...

Page 12: ...st information pertaining to this procedure 4 FIRMWARE UPGRADE 4 1 Firmware Upgrade Procedure Please reference Phoenix Contact s User Manual RAD XXXX IFS or equivalent for the latest information perta...

Page 13: ...rough M75 20 mm 0 79 Glands M75 through M100 35 mm 1 38 Prior to making holes in the enclosure wall or gland plate verify that the selected gland will not interfere with the sealing washer and locknut...