background image

18 

|

  nVent.com/HOFFMAN

To configure the controller from single mode to LL mode, simply follow below procedures. Perform this configuration for both air conditioners. 

1.  Before proceeding the LL mode configuration for each controller, make sure that the communication cable is connected from one ACU to 

another using a shielded cable with the shield grounded.

2.  Press 

 button to display passcode screen, the screen displays 

PSd

 on line 

1

 and 

0000

 on line 

2

.

3.  Press 

 button to access to passcode, the first digit of 

0

000

 is flashing and press 

2

 more times until the third digit 

00

0

0

 flashes. Press 

 arrow two times to change 

0

 to 

2

, then press 

 button to move to the last digit 

002

0

.

4.  Press 

 arrow two times to change the 

0

 to 

2

.

5.  Press 

 button to access to folder menu and then, the screen displays 

ALrF

.

6.  Press 

 arrow to navigate to 

PArF

, then press 

 button to access to parameter menu.

7.  The screen displays 

C

, press 

 arrow to navigate to parameter 

H

 and then, press 

 button to access to parameter 

H

 menu.

Parameter

Description

Available Range

LL Settings

Default

H

01

Mode

SA (stand alone)  

PS (primary-secondary)  

LL (lead-lag)

LL (lead-lag)

SA

H

02

Device ID

1

 up to 

10

1

 or 

2

1

H

03

Total number of the units  

in the group network

1

 up to 

10

2

1

H

14

LL strategy selection

0

-

250

0

 (Alternate each cycle)  

1

-

250

 (Alternate hours)

0

8.  Set parameter 

H

01

 to 

LL

 (lead-lag).

9.  Set parameter 

H

02

 (device ID) to 

1

 for one unit and 

2

 for the other unit.

10. Set parameter 

H

03

 (total number of controllers connected) to 

2

.

11. Set parameter H

14

 (LL strategy selection) to 

0

 to 

250

. This is the run time in hours before ACU

1

 and ACU

2

 will alternate being the lead 

unit. When set to zero ACU

1

 and ACU

2

 will automatically alternate every cycle.

Air conditioner unit remote communication features 

Air conditioners that include the optional nVent HOFFMAN network card (RAC module) have remote communication capabilities utilizing 

SNMP, Modbus TCP, EtherNet/IP, Profinet Protocol via Ethernet connection, and Modbus RTU protocol via USB connection.  

nVent provides Windows interface application software that is available to download free from nVent support link  

https://go.nVent.com/remote-access-control-support-center. The Windows interface application software supports both  

Ethernet and USB communication.

USB communication 

This communication mode allows direct connection from a laptop (or PC) to the air conditioning unit using a Mini-b USB cable. As stated 

above, Modbus RTU is used to communicate between the two devices via USB connection.

Ethernet communication

This communication mode allows remote connection to the air conditioning unit utilizing SNMP, Modbus TCP, EtherNet/IP, and Profinet 

protocol. Customers that use their own software can download an MIB file for SNMP, EDS or EtherNet/IP Object file for EtherNet/IP, Coil 

Register file for Modbus TCP, and Data Point for Profinet.

Note:

 the Ethernet card (RAC module) has a default IP Address of 

192

.

168

.

1

.

2

Both Ethernet and USB communication allow the ability to: 

•  Read ACU inlet and outlet air temperature
•  Read and change cooling and cooling differential setpoints
•  Read and change heating and heating differential setpoints
•  Read and change the high and low temperature alarm settings
•  Read and change the Gateway IP address, Device IP address, Subnet MASK, Trap IP address, and community string
•  Read and change unit identification
•  Read and change the state of IP address from static to dynamic or vice versa
•  Read and change the air temperature unit of measure (from F to C or vice versa)
•  Read current alarm status
•  Evaporator fan control setting
•  Read and change the control of door open switch

Summary of Contents for X2302

Page 1: ...Extreme AC Air Conditioner X2302 Model Instruction Manual P N 89215748 Rev E...

Page 2: ......

Page 3: ...rgizing the controller 10 Control status indication 10 Displaying and changing program settings 13 To view or access the settings 13 Heat cool operating parameters 13 Alarm parameters 13 Displaying te...

Page 4: ...ing the air conditioner to the enclosure Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity...

Page 5: ...in upright position during operation 5 To avoid cross threading mounting inserts start bolts by hand before tightening with a wrench or ratchet driver 6 Refer to the top of the nameplate for electrica...

Page 6: ...g cutout dimensions 22 22 564 3X 48 12 95 24 3X 5 00 127 3X 10 63 270 3X 16 25 413 3X 21 25 540 3X 43 11 3X 4 58 116 3X 9 15 232 12X 31 8 20 32 516 8 40 213 80 20 89215771 Cutout Dimensions Mounting G...

Page 7: ...nVent com HOFFMAN 7 Wire diagram 89206067 REV C...

Page 8: ...8 nVent com HOFFMAN Schematics 89206866 REV B J3...

Page 9: ...3016SP 89083016SP 6 Switch MALF 89096948SP 89096948SP 7 Filter Drier 52602803SP 52602803SP 8 Coil Condenser 20102001SP 20102001SP 9 Coil Evaporator 89204519SP 89204519SP 10 Controller Smart 89202719SP...

Page 10: ...ssures to equalize in order for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate...

Page 11: ...on Indication Icon Status C White When operating temperature in degrees Celsius ON F White When operating temperature in degrees of Fahrenheit ON Main Field Line 1 White Display inlet temperature ON M...

Page 12: ...12 nVent com HOFFMAN...

Page 13: ...ain screen wait one minute with no action or Press arrow few times until ESC displays then press button to return to UoF screen From the UoF screen Press arrow few times until LOG Out message displays...

Page 14: ...creen will be automatically revert to the main screen Note if no alarms are present then only ESC will be displayed in the folder There are seven possible alarms non latching detectable by the control...

Page 15: ...ature data on screen There are two temperature probes in the air conditioner where one is reading the enclosure air temperature incoming to the air conditioner and other is reading the cooled air leav...

Page 16: ...secondary units 2 The primary unit monitors the enclosure temperatures of all the units and manages the ON OFF status of cooling and heating based on the unit reporting the highest temperature 3 When...

Page 17: ...utton to access to parameter H menu Parameter Description Available Range PS Settings Default H01 Mode SA stand alone PS primary secondary SA PS primary secondary LL lead lag H02 Device ID 1 up to 10...

Page 18: ...conditioner unit remote communication features Air conditioners that include the optional nVent HOFFMAN network card RAC module have remote communication capabilities utilizing SNMP Modbus TCP EtherN...

Page 19: ...west or higher number of the Comm Port To view the controller data information from the A C unit In the nVent HOFFMAN A C Monitor main screen select Single ACU Monitor tab Click on Enable Comm button...

Page 20: ...enclosure air temperature and other temperature settings information include the unit of measure The Enable Comm text on the button now changes to Disable Comm To stop the communication click on the D...

Page 21: ...e allows to read and write Click on Enable Comm button to communicate to the network card and read the temperature information from the controller Now the temperature settings information in the contr...

Page 22: ...8 J1 GROUND G0 1 BLK40 POWER 24VAC G 2 WHT41 J2 NA 5V 1 NA S3 2 INLET TEMP PROBE S1 3 RED NA Y1 4 DOOR OPEN SWITCH ID1 5 WHT63 GROUND O 6 WHT RESERVED S5 7 OUTLET TEMP PROBE S2 8 RED45 NA Y2 9 MAL FUN...

Page 23: ...e and convenience of reputable refrigeration repair service personnel for recharging the air conditioner Inlet air filter Proper maintenance of the ambient air filter is critical to normal operation o...

Page 24: ...c Contact nVent Equipment Protection for special recommendations Refrigerant loss Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks Shipping...

Page 25: ...cabinet and surrounding area to ensure adequate airflow to and from the unit on both the inlet and outlet air channels for the ambient and cabinet air Comments Seals Gaskets and Leaks Inspect and repa...

Page 26: ...tage and retest or contact certified electrician Is the controller illuminated Is there correct supply voltage to controller 24 V DC Possible Causes 24 V Transformer Rectifier Check Wiring Replace con...

Page 27: ...and wiring Clean replace filter and clean condenser coil Replace seals and gaskets on enclosure Monitor for normal operation Possible Causes Low Refrigerant Leak Check controller settings YES YES YES...

Page 28: ...nVent com en us cooling field service request F GAS INFORMATION X230216GXXX X230226GXXX Refrigerant K hlmittel Ch odziwo R134a R134a GWP 1430 1430 Factory Charge F llmenge durch Hersteller Op ata Fab...

Reviews: