nVent Hoffman X2302 Instruction Manual Download Page 26

26 

|

  nVent.com/HOFFMAN

TROUBLE SHOOTING

Verify that wire 

connections from 

controller are secure

NO

YES

YES

YES

NO

NO

NO

NO

NO

NO

Compressor won't start

Is controller calling for 

compressor?

Do you have voltage at 

compressor?

Check for open windings

Replace compressor

Are there any alarms on 

the controller?

Refer to alarm chart in 

manual

Replace run capacitor

Is cooling relay closing?

Is there voltage from 

controller?

Replace overload

Replace relay

Check run capacitor for 

correct capacitance.

Check overload to ensure 

it is closed

Check cooling set point. 

Compressor should start 

when greater than 

7

 

degrees of set temp.

YES

YES

YES

YES

NO

YES

YES

NO

NO

NO

NO

YES

YES

YES

NO

YES

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

NO

Unit Won't Turn on and/or Cool

Does the unit have 

correct supply voltage? 

(Correct voltage 

displayed on nameplate)

Correct voltage and 

retest or contact 

certified electrician.

Is the controller 

illuminated?

Is there correct supply 

voltage to controller 

(

24

 V DC)?

Possible Causes: 

• 

24

 V Transformer

• Rectifier

• Check Wiring

Replace 

controller

Are there 

any alarms 

displayed 

on the 

controller?

Is compressor 

running?

Refer to alarms 

chart in controller 

section of manual

Is enclosure temp 

7

° above cooling 

setpoint and 

controller is calling 

for cooling?

Possible Causes:

• Start Cap

•  Open Motor 

Winding

• Contactor

Are the 

filter and 

condenser 

coil are 

clean?

Condenser fan - 

is the HPC Switch 

closed? The HPC 

switch closes at 

165

°F and opens 

at 

95

°F.

Clean accordingly. 

Contact Customer 

Service for new 

filter if needed.

Possible Causes:

• HPC

•  Low Charge in 

System

Are BOTH fans 

running?

Possible low charge.  

Verify pressures, contact 

HVAC certified Technician.

Verify 

voltage to 

fans.

Replace fan and 

re-test or contact 

Technical Support

Evaporator 

Fan-Possible 

Causes:

•  Evap fan 

Capacitor

• Loose wires

Contact 

Technical 

Support 

763

-

422

-

221

ext 

1

,

2

,

3

Adjust settings; 

See controller 

section of manual.

Summary of Contents for X2302

Page 1: ...Extreme AC Air Conditioner X2302 Model Instruction Manual P N 89215748 Rev E...

Page 2: ......

Page 3: ...rgizing the controller 10 Control status indication 10 Displaying and changing program settings 13 To view or access the settings 13 Heat cool operating parameters 13 Alarm parameters 13 Displaying te...

Page 4: ...ing the air conditioner to the enclosure Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity...

Page 5: ...in upright position during operation 5 To avoid cross threading mounting inserts start bolts by hand before tightening with a wrench or ratchet driver 6 Refer to the top of the nameplate for electrica...

Page 6: ...g cutout dimensions 22 22 564 3X 48 12 95 24 3X 5 00 127 3X 10 63 270 3X 16 25 413 3X 21 25 540 3X 43 11 3X 4 58 116 3X 9 15 232 12X 31 8 20 32 516 8 40 213 80 20 89215771 Cutout Dimensions Mounting G...

Page 7: ...nVent com HOFFMAN 7 Wire diagram 89206067 REV C...

Page 8: ...8 nVent com HOFFMAN Schematics 89206866 REV B J3...

Page 9: ...3016SP 89083016SP 6 Switch MALF 89096948SP 89096948SP 7 Filter Drier 52602803SP 52602803SP 8 Coil Condenser 20102001SP 20102001SP 9 Coil Evaporator 89204519SP 89204519SP 10 Controller Smart 89202719SP...

Page 10: ...ssures to equalize in order for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate...

Page 11: ...on Indication Icon Status C White When operating temperature in degrees Celsius ON F White When operating temperature in degrees of Fahrenheit ON Main Field Line 1 White Display inlet temperature ON M...

Page 12: ...12 nVent com HOFFMAN...

Page 13: ...ain screen wait one minute with no action or Press arrow few times until ESC displays then press button to return to UoF screen From the UoF screen Press arrow few times until LOG Out message displays...

Page 14: ...creen will be automatically revert to the main screen Note if no alarms are present then only ESC will be displayed in the folder There are seven possible alarms non latching detectable by the control...

Page 15: ...ature data on screen There are two temperature probes in the air conditioner where one is reading the enclosure air temperature incoming to the air conditioner and other is reading the cooled air leav...

Page 16: ...secondary units 2 The primary unit monitors the enclosure temperatures of all the units and manages the ON OFF status of cooling and heating based on the unit reporting the highest temperature 3 When...

Page 17: ...utton to access to parameter H menu Parameter Description Available Range PS Settings Default H01 Mode SA stand alone PS primary secondary SA PS primary secondary LL lead lag H02 Device ID 1 up to 10...

Page 18: ...conditioner unit remote communication features Air conditioners that include the optional nVent HOFFMAN network card RAC module have remote communication capabilities utilizing SNMP Modbus TCP EtherN...

Page 19: ...west or higher number of the Comm Port To view the controller data information from the A C unit In the nVent HOFFMAN A C Monitor main screen select Single ACU Monitor tab Click on Enable Comm button...

Page 20: ...enclosure air temperature and other temperature settings information include the unit of measure The Enable Comm text on the button now changes to Disable Comm To stop the communication click on the D...

Page 21: ...e allows to read and write Click on Enable Comm button to communicate to the network card and read the temperature information from the controller Now the temperature settings information in the contr...

Page 22: ...8 J1 GROUND G0 1 BLK40 POWER 24VAC G 2 WHT41 J2 NA 5V 1 NA S3 2 INLET TEMP PROBE S1 3 RED NA Y1 4 DOOR OPEN SWITCH ID1 5 WHT63 GROUND O 6 WHT RESERVED S5 7 OUTLET TEMP PROBE S2 8 RED45 NA Y2 9 MAL FUN...

Page 23: ...e and convenience of reputable refrigeration repair service personnel for recharging the air conditioner Inlet air filter Proper maintenance of the ambient air filter is critical to normal operation o...

Page 24: ...c Contact nVent Equipment Protection for special recommendations Refrigerant loss Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks Shipping...

Page 25: ...cabinet and surrounding area to ensure adequate airflow to and from the unit on both the inlet and outlet air channels for the ambient and cabinet air Comments Seals Gaskets and Leaks Inspect and repa...

Page 26: ...tage and retest or contact certified electrician Is the controller illuminated Is there correct supply voltage to controller 24 V DC Possible Causes 24 V Transformer Rectifier Check Wiring Replace con...

Page 27: ...and wiring Clean replace filter and clean condenser coil Replace seals and gaskets on enclosure Monitor for normal operation Possible Causes Low Refrigerant Leak Check controller settings YES YES YES...

Page 28: ...nVent com en us cooling field service request F GAS INFORMATION X230216GXXX X230226GXXX Refrigerant K hlmittel Ch odziwo R134a R134a GWP 1430 1430 Factory Charge F llmenge durch Hersteller Op ata Fab...

Reviews: