Operation
©2022 nVent
89217391 Rev. A
87
10.6.16 Page 7683, environment/primary circuit settings
/ Unit / Setup /
Controller parameters / Environment / Primary circuit
•
Adjustment of process-relevant parameters.
Screen contents:
Description
Environment / Primary circuit
Environment
Min. outside temp.
[°C]
Minimum outside temperature
Max. outside temp.
[°C]
Maximum outside temperature
Min. relative humidity
[%]
Minimum relative humidity
Max. relative humidity
[%]
Maximum relative humidity
Primary circuit
Min. outlet flow rate
[l/min]
Minimum flow rate (outlet)
Min. inlet temp.
[°C]
Minimum temperature (inlet)
Max. inlet temp.
[°C]
Maximum temperature (inlet)
Max. outlet temp.
[°C]
Maximum temperature (outlet)
Min. inlet pr.
[bar]
Minimum pressure (inlet)
Max. outlet pr.
[bar]
Maximum pressure (outlet)
Max. diff. pr.
[bar]
Maximum differential pressure
Pressure fault message
delay
[s]
Setting of the time during which a fault message is suppressed
after a pressure fault.
Cp
[kJ(kgxK)] Specific heat capacity of the medium
Density
[g/ccm]
Density of the medium
Calc. cooling capacity
[kW]
Indication of the calculated cooling capacity