7.12 SETPOINTS (CONTINUED)
All the following are user adjustable within engineered limits:
Point Name
Description
Range
Default
SUMMERNIGHTFREECOOLACTIVE
Set night cooling mode as active
Off / On
0
SUMMERNIGHTFREECOOLMINTEMP
Night cooling lower cut-off temperature
5-30°C
10
SUMMERNIGHTFREECOOLFANSPEED
Night cool fan speed
20-100%
80
STC-COOLLOOPGAIN
Supply Temp Control - Cool Loop Gain
0 to -30
-5
STC-COOLLOOPINTEGRAL
Supply Temp Control - Cool Loop Integral
0 to 30
2
STC-COOLLOOPDERIVATIVE
Supply Temp Control - Cool Loop Derivative
0 to 30
0
STC-HEATLOOPGAIN
Supply Temp Control - Heat Loop Gain
0 to -30
-5
STC-HEATLOOPINTEGRAL
Supply Temp Control - Heat Loop Integral
0 to 30
2
STC-HEATLOOPDERIVATIVE
Supply Temp Control - Heat Loop Derivative
0 to 30
0
HEATINGTYPE
Heating Type 0=None, 1=LPHW, 2=Electric
0-2
0
COOLINGTYPE
Cooling Type 0=None, 1=CW, 2=DX
0-2
0
UI4FUNCTION
Input 4 Function, 0 = None, 1 = CO
2
/T/D, 2 = Trend Occ, 3=FSC
0-3
0
UI5FUNCTION
Input 5 Function, 0 = None, 1 = CO
2
/T/D, 2 = Trend Occ, 3=FSC
0-3
0
TACHOFITTED
Is a tacho signal monitor PCB fitted?
Off / On
Model Dependant
SOFTWAREVERSION
Shows the software number & Version
N / A
0
FANANDHEATERTEST
Factory Use Only (This resets on power cycle)
Off / On
Off
WIRINGVERIFICATION
Factory Use Only (This resets on power cycle)
Off / On
Off
FORCEOVERHEAT
Factory Use Only (This resets on power cycle)
Off / On
Off
DAMPERBYPASS
Force bypass damper into bypass mode (This resets on power cycle)
Off / On
Off
DAMPEROUTOFBYPASS
Force bypass damper out of bypass mode (Pump failure or
DAMPERBYPASS switch will override this) (This resets on power cycle)
Off / On
Off
FANDAMPERTEST
Factory Use Only
Off / On
Off
XBOXER XBC
ECOSMART2 (NT) MODELS
7.0 DESCRIPTION OF CONTROL - UNIT CONTROLLED BY AN ECOSMART2 CONTROLLER
Summary of Contents for XBOXER XBC 10 NT Series
Page 27: ...27 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 28: ...029 2085 8200 28 XBOXER XBC ECOSMART2 NT MODELS Figure 19 9 0 DIAGRAMS 9 3 PHYSICAL LAYOUT ...
Page 29: ...29 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 31: ...31 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 33: ...33 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 35: ...35 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 37: ...37 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...