7.12 SETPOINTS
All the following are user adjustable within engineered limits:
Point Name
Description
Range
Default
ENABLE
Software enable switch
Off / On
Off
RUNONTIME
Run-on timer value
0-3600 Seconds
0
TRICKLEMODE
When On, fans will trickle even with no enable signal
Off / On
Off
SETTEMP
Desired temperature setpoint
10 to 30°C
22
DEADBAND
Dead-band for temp control
0.5°K to 10°K
3
BOOST
Software boost switch
Off/On
Off
BOOSTRUNON
Boost Run On
0-3600 Seconds
0
FROSTPROTEMP
Temperature, below which, any water valves will be overridden open
-40°C to 10°C
4
MINFROSTPROTECTPERIOD
Minimum time frost protection will be enabled
0-600 Seconds
300
DAMPERDELAY
Startup delay to allow I/O dampers to open
0-300 Seconds
0
ALARMDELAY
Alarm hold-off delay
0-20 Seconds
5
HIGHAIRTEMPALARM
High supply air temp alarm temperature
30 to 70°C
50
LOWTEMPALARM
Low supply air temp alarm temperature
-40°C to 20°C
8
FORCESTOPONLOWTEMP
Stops fans upon LOWTEMPALARM
Off/On
Off
ALARMRESET
Resets any latched alarms (Resets to Off Automatically)
Off/On
Off
SUPPLYFANMAX
Individual fan maximum speed setting
20-100%
100
SUPPLYFANMIN
Individual fan minimum speed setting. (Trickle speed)
0-100%
20
EXTRACTFANMAX
Individual fan maximum speed setting
20-100%
100
EXTRACTFANMIN
Individual fan minimum speed setting. (Trickle speed)
0-100%
20
SUPPLYFANBOOST
Supply fan boost speed
20-100%
100
EXTRACTFANBOOST
Extract fan boost speed
20-100%
100
SUPPLYFANSTARTVOLTAGE
The voltage threshold of passing 0% rotational speed
0-5V
1
EXTRACTFANSTARTVOLTAGE
The voltage threshold of passing 0% rotational speed
0-5V
1
SUPPLYFANVOLTAGELIMIT
The maximum voltage to be supplied to the fan motor
6-10V
10
EXTRACTFANVOLTAGELIMIT
The maximum voltage to be supplied to the fan motor
6-10V
10
CO2TARGET
The target setpoint for CO
2
control
0-10000PPM
650
CO2RANGEMIN
The lower limit CO
2
value corresponding to the limit voltage
0-10000PPM
0
CO2VOLTAGEMIN
The lower limit voltage corresponding to the limit of range
0-10VDC
0
CO2RANGEMAX
The upper limit CO
2
value corresponding to the limit voltage
0-10000PPM
2000
CO2VOLTAGEMAX
The upper limit voltage corresponding to the limit of range
0-10VDC
10
CO2-LOOPGAIN
CO
2
Loop Gain
0 to -30
-0.5
CO2-LOOPINTEGRAL
CO
2
Loop Integral
0 to 30
10
CO2-LOOPDERIVATIVE
CO
2
Loop Derivative
0 to 30
0
17
nuaire.co.uk
XBOXER XBC
ECOSMART2 (NT) MODELS
7.0 DESCRIPTION OF CONTROL - UNIT CONTROLLED BY AN ECOSMART2 CONTROLLER
25. 02. 16. Leaflet Number 671704
Summary of Contents for XBOXER XBC 10 NT Series
Page 27: ...27 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 28: ...029 2085 8200 28 XBOXER XBC ECOSMART2 NT MODELS Figure 19 9 0 DIAGRAMS 9 3 PHYSICAL LAYOUT ...
Page 29: ...29 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 31: ...31 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 33: ...33 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 35: ...35 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...
Page 37: ...37 nuaire co uk XBOXER XBC ECOSMART2 NT MODELS 25 02 16 Leaflet Number 671704 ...