background image

7

nuaire.co.uk 

029 2085 8400

04. 09. 19. Leaflet Number  671789

Installation and Maintenance

Student Accommodation Ventilation Unit

8.0 COMMISSIONING

The unit is supplied with independent fan speed control via the potentiometers 
(see Figure 6) for both normal and boost and maximum airflows. 

Commissioning should be carried out in accordance with building regulations 
document “domestic ventilation compliance guide”.

A calibrated moving vane anemometer and hood will be required for the 
commissioning, and adjustment valves should be locked in place to prevent 
further adjustment. 

Once commissioned the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and mould 
growth. The label covering the control has an adhesive panel which should be 
removed post commissioning to prevent tampering.

+

-

-

+

-

+

-

+

-

+

Power

Post commissioning remove

adhesive backing under 

this section

060905

Ventilation Controls

For commissioning: 

refer to user manual

+

-

Control module

Figure 10.  Commissioning control.

9.0 STATUS INDICATION

The status of the unit is indicated by a series of LED’s on the front cover. The 
variants are listed below.

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

9.1 Frost Protection

In the event of the intake air temperature at the unit dropping below the 
predetermined set point (-5°C as standard) the supply fan will reduce to 
minimum speed, once the temperature rises above the set point the fan will 
return to its commissioned speed.

Please note this mode will only activate after ten days of continuous run time. 
If commissioning of the unit is outside of this time frame please notify the after 
sales department prior to site visit.

9.2 HX Bypass

The HX bypass damper shall open automatically under certain scenarios 
allowing the supply air to bypass the heat exchanger. These scenarios are 
described below.

1. Outdoor temp >10°C 
   

AND

 

   Indoor temp > Outdoor temp 
   

AND

 

   Inside temp > 25°C

2. Outdoor temp > 10°C 
   

AND

 

   Outdoor temp > Indoor temp 
   

AND

 

   Outdoor temp < 25°C

Note: An amount of hysteresis is included in the strategy such that the 
"current" condition is maintained until 1°C past the control point.

10.0 MAINTENANCE

We recommend that the two G3 filters are inspected after 6 months and 
replaced every 12 months; this interval may need to be shortened, if the unit is 
operating under adverse environmental conditions. 

The filters can be removed from the unit by removing the two filter covers on 
the bottom panel of the unit. Take hold of the two circular tabs either end of the 
filter covers and pull to remove (see Figure 7).

The filter can now be extracted by pulling the removal loop on the edge of the 
filter. Once the filters have been inspected return or replace them as necessary 
and refit the filter cover.

To fit the filter cover, insert both ends of the cover into the filter slot and press 
down on the centre (see Figure 8). Ensure that a full seal is made between the 
unit and the cover.  Any incorrectly fitted covers will cause a performance drop 
of the unit.

Inspect the heat exchanger every 5 years. Generally check for damage and 
security of components. 

Access to
second filter

Filter cover and 

filter being removed

Control
module

MVHR-DRAIN
condensate drain 
running to svp

Figure 11.  Filter replacement.

Summary of Contents for UNI-X Series

Page 1: ...uld be connected to a fixed wiring installation via a fused isolator in accordance with current IEE wiring regulations The electrical wiring should be carried out by competent persons in accordance wi...

Page 2: ...aging Some of the modules have an uneven weight distribution and this will be indicated by labelling where appropriate Offloading and positioning of the equipment is the responsibility of the purchase...

Page 3: ...ng for the full compression socket depth using an appropriate pipe cutter such as a Hepworth ratchet pipe cutter 2 Remove any swarf from the end of the plastic pipe Ream the copper pipe end to remove...

Page 4: ...4 75 57 152 40 UNI X360 720 1072 300 1100 53 163 53 130 57 160 53 194 55 UNI X580 985 1136 300 1216 60 233 52 103 60 243 52 268 65 P Q R N Plan View Condensate Pipe Connection F E H G C D A B Plan Vie...

Page 5: ...2 64 75 57 152 40 UNI X360 C 720 1072 300 1100 53 163 53 130 57 160 53 194 55 UNI X580 C 985 1136 290 1216 60 233 52 103 60 243 52 268 65 P Q R N Plan View Condensate Pipe Connection Condensate Pipe C...

Page 6: ...y cord from unit Grey Green yellow MAINS 230V 50Hz Room lights Light Double switches Pole N L 3 Pole isolator Kitchen switch Blue Green yellow Brown Black Supply cord from unit Optional boost switch G...

Page 7: ...ase note this mode will only activate after ten days of continuous run time If commissioning of the unit is outside of this time frame please notify the after sales department prior to site visit 9 2...

Page 8: ...re parts please quote the serial number of the unit and the ARC number of the purchase if possible this information will be available on the fan label In the unlikely event of motor failure the unit m...

Reviews: