background image

Smart ‘S’  

TWINFAN CONTROL

Installation and Maintenance   

3

Fig. 4. A typical Quietwin  graph 

Commissioning Procedure (see fig. 2).

1. 

Switch on the supply to the  QTI Quietwin fan.

2. 

Locate the control module panel  Care  must be taken if 

the module has any covering panels removed as live 
230v incoming supply terminals may be exposed. 
Note covers MUST be properly replaced when commission
ing has been completed.

3. 

Wait approximately 60 seconds for the system to complete 

its self test’

4. 

Press the step sequencing button several times until  only

the ‘FAN 1’ light is illuminated and the ‘AUTO’ light is 
off. (See detail of control panel Fig. 2).

5. 

Connect a manometer across the tappings provided on the 

outside of the fan casing. Reading the manometer and using 
the graph, determine the airflow. The fan is factory set at       

full speed. Using the rotary graduated control,reduce  the 

speed to the desired setting (may require a screwdriver).
NOTE: allow 30 seconds for the fan to reach the set speed.   

6. 

Set the Run on timer control. (Adjustable 5-60 min).

(See detail of control panel Fig. 2).

7. 

Press the step button through the sequence until ‘AUTO’ 

light shows.

COMMISSIONING IS NOW COMPLETE.

Using the graphs  
(SPECIFIC GRAPHS FOR YOUR 
QUIETWIN FAN ARE SHOWN IN THE
FAN INSTALLATION & MAINTENANCE
LEAFLET). 

The graphs are designed to assist you in establishing an AIR
VOLUME FLOW RATE  for your fan installation.
The curves shown indicate performance at 100%, 75% and 50%. 
Assuming that the ventilation system is installed and the fan is
connected to all ductwork. Connect a manometer across the 
tappings provided on the outside of the fan unit casing.
The fan is factory set for full speed. With the fan operating at this
full speed (100%) take a pressure reading in Pa from the
manometer. Refer to the relevant graph for your size of unit and
with your Pa figure, read across the graph to where the line 
intersects the 100% curve. 
Drop a line vertically down from this point and the air volume
flow is indicated on the base line of the graph.

See the fan Installation & Maintenance leaflet supplied.

Using the Step button (see fig 2).

Refer to the label on the controls inside cover for more guidance.
Pressing the step button will sequence through the options and
change the modes as follows:

1.    FAN 1 in manual mode  (used for commissioning)

2.    FAN 2 in manual mode  (used for commissioning)

3.    SYSTEM OFF

4.    SYSTEM IN AUTOMATIC   (normal selection)

To clear a fail, press the STEP button until the fail has cleared.

IMPORTANT After commissioning, press the STEP but-
ton through until AUTO is illuminated. 

System is now in automatic mode. 

EXTERNAL  USE QUIETWINS WITH THE SMART
CONTROL OPTION ARE PROVIDED WITH A  COM-
MISSIONING BOX ON THE OUTSIDE OF THE CASE
The main control  module  is inside the fan (See fig 5).

Control Module Connections /Inputs and
their uses (see fig 2)

SENSOR INPUT 1:
This is the Master on/off control input and is usually ‘linked out’
with a  special plug unless:
A Timeclock can be connected into this input e.g. ST-TC
During ON times the unit is allowed to operate.
During OFF times the unit is off- zero duty.
Note: The ST-TC Timeclock must always be plugged into the fan
mounted control module NOT into a ST-JB junction box.

SENSOR INPUTS 2, 3 & 4 
Any sensor can be connected to these inputs to allow activation
of the unit. If any of these inputs is activated, the unit will run at
the maximum set duty.  These sensors include ST-PIR, 
ST-HUM, ST-TEMP.  
Note: Additional sensors may be added by using an ST-JB Junction Box.

SWITCH LIVE terminals
This acts just like the sensor inputs 2,3,4.  If 230v ac is detected
on the SW - Live terminals, the unit will run at the max. set duty

DAMPER  terminals (2 sets)
When the fan is running at full duty, both these damper connec-
tions will be activated.  i.e. power will be available on the OP
terminals of the damper connections. The fan will not go to full
duty until the RET terminals have 230v ac (Limit Switch).

FAILURE RELAY 
This relay is normally closed when there are no faults. When
faults occur this relay will open and break the circuit. This
method of operation allows all types of failure to be detected for
example ‘Power failed’, ‘Fan/s fail.
This connection is a volt free switch. it can handle power up to
5A (230v) and is fused for protection.

NO FAULT:             The volt free switch is closed i.e. the two       

terminals are connected.

FAN FAULT:            The volt free switch is opened. i.e. the two

terminals are disconnected.

Reviews: