Installation and Maintenance
QUIETWIN QTR BELT DRIVE TWINFAN
3
General
Electrical Weight
1 Phase (230v) 3 Phase (400V)
kg
(nominal)
Unit
Speed
Power
f lc
sc
Code
*
rpm
(kw)
(amps)
(amps)
QTR*A 1-3*
535
0.18
0.75
2.3
73
QTR*A 2-3*
705
0.18
0.75
2.3
73
QTR*A 3-1*
835
0.25
2.1
5.3
75.4
QTR*A 3-3*
835
0.25
0.95
3.0
75.4
QTR*A 4-1*
835
0.37
2.9
7.3
77.5
QTR*A 4-3*
835
0.37
1.3
4.6
77.5
QTR*A 5-1*
935
0.25
2.1
5.3
75.4
QTR*A 5-3*
935
0.25
0.95
3.0
75.4
QTR*A 6-1*
935
0.37
2.9
7.3
77.5
QTR*A 6-3*
935
0.37
1.3
4.6
77.5
QTR*A 7-1*
1045
0.25
2.1
5.3
75.4
QTR*A 7-3*
1045
0.25
0.95
3.0
75.4
QTR*A 8-1*
1045
0.37
2.9
7.3
77.5
QTR*A 8-3*
1045
0.37
1.3
4.6
77.5
QTR*A 9-1*
1045
0.55
3.4
9.3
84.4
QTR*A 9-3*
1045
0.55
1.7
6.8
84.4
QTR*A 10-1* 1125
0.37
2.9
7.3
77.5
QTR*A 10-3*
1125
0.37
1.3
4.6
77.5
QTR*A 11-1*
1125
0.55
3.4
9.3
82.4
QTR*A 11-3*
1125
0.55
1.7
6.8
82.4
QTR*A 12-3*
1125
0.75
2.1
9.5
84.4
QTR*A 13-1*
1225
0.37
2.9
7.3
77.5
QTR*A 13-3*
1225
0.37
1.3
4.6
77.5
QTR*A 14-1*
1225
0.55
3.4
9.3
82.4
QTR*A 14-3*
1225
0.55
1.7
6.8
82.4
QTR*A 15-3*
1225
0.75
2.1
9.5
84.4
QTR*A 16-3*
1225
1.1
2.9
13.0
90.4
QTR*A 17-1*
1335
0.55
3.4
9.3
82.4
QTR*A 17-3*
1335
0.55
1.7
6.8
82.4
QTR*A 18-3*
1335
0.75
2.1
9.5
84.4
QTR*A 19-3*
1335
1.1
2.9
13.0
90.4
QTR*A 20-1*
1400
0.55
3.4
9.3
82.4
QTR*A 20-3*
1400
0.55
1.7
6.8
82.4
QTR*A 21-3*
1400
0.75
2.1
9.5
84.4
QTR*A 22-3*
1400
1.1
2.9
13.0
90.4
QTR*A 23-3*
1400
1.5
3.7
18.5
96.4
CASE SIZE ‘A’
Table 4. Start & Run currents etc.
Electrical Details
(See table 3, 4 & 5).
Because the run and start currents depend upon the duty and asso-
ciated ductwork of an individual unit, the values quoted in the
table are nominal.
Run currents will be exceeded if the unit is operated with its cover
removed. It is therefore recommended that the unit is not run for
prolonged periods in this condition.
QTRB D BOTTOM / END INLET
Size: D only.
Rect Spigot
Unit
A
B
C
E F
QTRR D
2315
2500
1230
1200
700
QTRB D
2315
2500
1230
1200
700
Table 3.
DIMENSIONS (mm)
For unit weights
see table 7
Louvred
end outlet
Bottom rectangular inlet spigot
Code: QTRB
F
E
B
A
C
F
E
End inlet rectangular spigot
Code: QTRR
Fig. 4.
Testing after Installation
Ensure that the Fan unit and Control and particular control
ancillaries if specified eg PIR, Run/Fail indicators, timeclock etc.
are fitted.
Switch on and check that the fan unit runs satisfactorily.
Using your chosen control, switch over to the standby fan by
means of the control's fan selection switch.
Check that the change-over occurs.
Switch off. If a Run-on Timer is fitted, check that the fan contin-
ues to run.
Time the run-on period, which is adjustable between 5 and 60
minutes nominal.
Timer controls are set at the works to the shortest period.
For speed controls follow the installation set-up procedure
provided with the control.
QTE*B1-3* = Quietwin, duct mounted, external use,
case size B, performance curve 1,
3 phase electrical supply
Control choice ‘M’ or ‘C’
Spigot location choice (see page 1)
** CODING eg.