Installation Manual

NOXMASTER

6.2 Speed Selection

When power to the unit is switched on the display will show LED start-
up pattern for 2 minutes. Once the start-up pattern has completed 
you may now press the “up” or “down” switch to choose the flow rate 
appropriate to the property you are installing the unit in.

6.3 Change Carbon Filter Alert

The carbon filters are required to be changed every five years, the 
display on the ceiling diffuser will show the letter ‘C’ once this time has 
elapsed. New filters can be purchased direct from Nuaire (please refer 
to Section 8.0 below for further details). 

To reset the change filter message on the display, press and hold both 
“up and “down” button until the letter ‘C’ starts to flash then release 
and press the “down” button to confirm.

6.4 Setting the Temperature Speed Control Option

The unit has been designed to continuously run 24 hours a day, 365 
days a year (provided the unit is ducted to the outside). 

If an alternative temperature control is needed due to excessive heat in 
the property, please contact after sales to discuss your requirements.

6.5 Setting the Thermostat

The thermostat controls the front damper which determines where 
the air supply is drawn from (either loft space or external). It’s 
recommended that the thermostat is set to 24°C. This setting would 
enable the unit to automatically switch from the loft intake (warm air) 
to external air once the loft space reached 24°C, provided the unit is 
ducted to the outside of the property.

6.6 Time Clock

The time clock controlling the carbon filter bypass is pre-programmed 
to operate the bypass (controller must be in "run" mode). 

Air passes through the Carbon filter between 6.00AM & 8.00PM. 
Between 8.00PM and 6.00AM the air flow is directed through the 
bypass.    

Unit Code

Replacement  

Filter Code

Filter Description

NOXMASTER

NOXMASTER-CF

Carbon Filters (x2)

NOXMASTER-HEAT

NOXMASTER-CF

Carbon Filters (x2)

NOXMASTER-PM2.5

NOXMASTER-CF

Carbon Filters (x2)

NOXMASTER-HEAT-
PM2.5

NOXMASTER-CF

Carbon Filters (x2)

IMPORTANT

In the event of RF interference between 84MHz to 89MHz 

the fan speed may increase to full speed. Operation will return 

to normal when the interference stops.

7.0 HEATER CONTROL (Heater Versions Only)

When the orange LED on the diffuser control panel is illuminated, the heater is 
active in autoheat mode and is controlled by the temperature setpoint. When 
the orange LED is not lit, the heater is off.

In order to enable the heater, press the DOWN button for five seconds and 
release. The orange LED will illuminate indicating that the heater is active and in 
auto heat mode.

To turn the heater off, press the DOWN button for five seconds and release. The 
Orange LED will no longer be illuminated, indicating that the heater is off.

7.1 Setting the Temperature Set Point

A temperature sensor is fitted to the outlet of the heater and will control the 
heater output to maintain the set point. The set point ranges between 5˚C (fully 
anti-clockwise) and 15˚C (fully clockwise) and can be adjusted via the min/max 
commissioning pot located on the ceiling vent diffuser.

8.0 MAINTENANCE

Appropriate PPE (Personal Protective Equipment) should be worn 
during maintenance. Precautions may also be needed to protect the 
surrounding area from excess carbon residue.

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

8.1 Routine Maintenance

Check filters and change/clean if required, failure to do so may 
impair the performance and energy efficiency of this unit.

8.2 Annually 

Thoroughly inspect the unit and its components for corrosion, 
acting immediately to treat/restore any damaged areas. 

All electrical terminals within the unit should be tightened. 

Check all earth connections. 

Check control dampers blades. 

Check operation of damper actuators and linkages and adjust as 
necessary. 

8.3 Replacement Filter Codes

To ensure the carbon filter maintains its high reduction of NO2 the 
filter must be replaced once the end of its lifespan has been reached. 

The lifespan of the carbon filter in normal circumstances is shown in 
the table below. 

Unit Code

Carbon Filter 

Lifespan

Carbon Filter  

Weight

NOXMASTER 

RANGE

5 years

2 x 6Kg

To ensure effective particulate filtration and low system resistance, 
air filters must be replaced every 12 months. Replacement filters are 
available for purchase direct from Nuaire, with the relevant part codes 
shown in this document.

 

Alternatively the product website can be 

accessed directly via the QR code below.

Product Code

Replacement  

Filter Code

Filter 

Description

NOXMASTER

NOXMASTER-FR-

PM10

ePM10 (Pre) &  

ISO COARSE 75% 

(Post) Filter 

NOXMASTER-HEAT

NOXMASTER-FR-

PM10

ePM10 (Pre) &  

ISO COARSE 75% 

(Post) Filter

NOXMASTER-PM2.5

NOXMASTER-FR-

PM2.5

ePM2.5 (Pre) & 

ISO COARSE 75% 

(Post) Filter

NOXMASTER-HEAT-

PM2.5

NOXMASTER-FR-

PM2.5

ePM2.5 (Pre) & 

ISO COARSE 75% 

(Post) Filter

IMPORTANT

Isolation - Before commencing work make sure that the unit and 

Nuaire control are electrically isolated from the mains supply and 

switched live supply.

Summary of Contents for NOXMASTER Series

Page 1: ...module The unit must be situated in a dry environment that avoids dripping water and installed fully level in the horizontal plane It is important to ensure that the diffuser is NOT placed within 1 m...

Page 2: ...ack of experience and knowledge unless they have been given supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with th...

Page 3: ...800 Delivery Option P Three Individual Boxes BOX 1 362 981 585 22 BOX 2 362 685 685 12 BOX 3 340 535 230 6 POD A Carbon Filter Weight 22Kg AIRFLOW POD B Blower Weight 12Kg 1371 463 168 PLEASE ALLOW 3...

Page 4: ...the duct will be held on securely check all duct joints are air tight FURTHER MEASURES MAY BE REQUIRED 3 3 NOXMASTER Installation 3 3 1 Connecting Sections The unit is delivered in two sections pod A...

Page 5: ...NOXMASTER Modules Fitting Dual Inlets Ceiling Joist Metal Mounting Bracket A V Mount A V Mount Washer 3 Woodscrew 50mm Min 12mm Clearance Hole Spigot Guard Punched out and removed 150mm inlet duct to...

Page 6: ...s IMPORTANT Disconnection from mains must be incorporated within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with latest edition of the wiring regulations NOXMAST...

Page 7: ...orange LED is not lit the heater is off In order to enable the heater press the DOWN button for five seconds and release The orange LED will illuminate indicating that the heater is active and in aut...

Page 8: ...ted in Pod A larger section Isolate the unit from mains power supply Unscrew the fixings securing the lid in place and remove lid from unit Figure 8 Remove the Carbon filter s by lifting vertically Re...

Reviews: