MRXBOXAB-ECO4-1Z(SC/SW)

Installation Manual

2.0 INTRODUCTION

The ECO4-1Z wall mounted range of units are designed to offer 
improved sound levels and an aesthetically pleasing installation by 
housing a Mechanical Ventilation with Heat Recovery (MVHR) unit and 
attenuator inside an acoustically lined enclosure. 

The MVHR unit is fitted with two independent fans to provide 
mechanical supply and extract ventilation, each fan has full speed 
control for background and boost ventilation rates. To recover heat 
from the extract air, the heat exchanger block is utilised. The heat 
exchanger can recover up to 95% of the normally wasted heat. The 
units also incorporate an integral humidistat and frost protection.

Bypass operation can be disabled via a manual switch in colder months 
so the unit recovers heat continually.

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Airflow Through unit (Standard Hand Unit)

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Airflow Through OH unit (Opposite Hand Unit)

3.0 MECHANICAL INSTALLATION

Installation must be carried out by competent personnel in accordance 
with the appropriate authority and conforming to all statutory 
governing regulations. All mains wiring must be in accordance with the 
current I.E.E. Regulations, or the appropriate standards. Ensure that the 
mains supply (Voltage, Frequency and Phase) complies with the rating 
label. 
A clear working space is required around the installed unit to allow the 

cover to be removed and provide sufficient access for maintenance 

such as filter change. 

A minimum of 480mm is required in front of 

the unit.

The fan must be installed indoors, on a suitable wall away from direct 

sources of frost, heat and water spray or moisture generation. For a 

vibration-free result the unit must be mounted to a solid wall.

The unit must remain switched on at all times to maintain 
ventilation within the dwelling. Turning the unit off will cause long 
term damage to the unit and building fabric.

This appliance is not intended for use by persons (including 
children) with reduced physical, sensory or mental capabilities, 
or lack of experience and knowledge, unless they have been given 
supervision or instruction concerning the use of the appliance by a 
person for their safety. Children should be supervised so that they 
do not play with the appliance.

3.1 Transport Fixings

To prevent damage during transit and installation, the product is 
shipped with two transportation brackets, these are attached to the 
upper screws of the MVHR front panel (Figure 3).  These brackets must 
be removed before use, failure to do so will result in excessive vibration 
and noise. The screws securing the bracket to the side panel of the 
enclosure can be removed and discarded, the remaining screws securing 
the bracket to the MVHR unit can be loosened allowing the bracket to 
be removed before fully tightened to secure the panel in place.

A

A

Transportation 
bracket

Transportation Fixings

3.2 Floor Mounting (Recommended)

Due to the size and weight of the unit, floor mounting is the preferred 

mounting method, if this is not possible a solid wall is required. A 

gypsum block/plasterboard wall will not suffice, examples of suitable 

installations are shown in this document. 
The unit is not supplied with any mounting brackets; a suitable 

mounting structure with means of securing the unit in place is required.  

Four female M8 fixing points are available in the base panel of the 

enclosure to be used to secure the unit in place, for details of these 

along with compulsory support areas and features that should be 

accommodated within the mounting structure (Figure 5).
No part of the enclosure should be in contact with the building 

structure, the only components that should be in contact are those 

used to provide the mounting structure.

Care must be taken to ensure the unit is installed true in all 3 

dimensions. Failure to do so may result in overflow from the 

internal condensation drip tray.

3.3 Optional Solid Wall Mounting

The MVHR unit fixed to a solid wall construction using a suitable 
mounting structure (supplied by others). 

Ducting in the 

ceiling void.

Side view of unit 

mounted on the

solid wall in a 

cupboard using 

MVHR-DRAIN

suitable mounting 
structure.

Condensate drain,

uninsulated drain 

pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 115kG

Mounting frame 
not supplied

Typical example of a cupboard mounted unit (Standard 
unit) fixed to a block work wall.

Summary of Contents for MRXBOXAB-ECO4-1ZOHSC

Page 1: ...y a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information This manual contains important information on the safe and ap...

Page 2: ...use long term damage to the unit and building fabric This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety Children should be supervised so that they do not play with the appli...

Page 3: ... in insulated to prevent freezing Nuaire recommend MVHR DRAIN be used as the primary condensate take off Figures 8 and 9 3 5 Extract Input Areas The unit is designed to extract air from all wet rooms e g bathroom kitchen en suite utility room with sink WC s do not need to be ventilated if openable windows are fitted Supply air should be to all habitable rooms e g bedrooms and lounge Extract input ...

Page 4: ...t and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 150mm diameter or 220 x 90mm rectangular ducting should be used refer to dwelling design drawing Figures 11 12 Duct...

Page 5: ...te e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in ADF 2010 Extract Ventilation Rates table The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further information refer to Domestic Ventilation Compliance Guide ww...

Page 6: ...ipe with min 5 o fall running to SVP MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP 3 10 2 Rectangular Ducting 12 Typical Rectangular Ducting Arrangement For Wall Mounted Units Air supply to lounge in ceilings via AirValve Extract air from kitchen bathroom in ceilings via AirValve Exhaust air from kitchen bathroom to outside via louvre grille M...

Page 7: ...the fixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm 4 2 1 Unit Only MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 5A Fuse BS1362 2 Pole Isolator 14 Wiring Diagram Unit Only 4 2 2 Unit Serving One Bathroom 15 Wiring Diagram One Bathroom 5A Fuse BS1362 MAIN...

Page 8: ...cover 6 0 CONTROLS 6 1 Humidity Adjustment This product contains an internal humidity sensor fitted into the air flow extracting from the wet rooms When the unit senses that the humidity exceeds the set point the unit will boost to that set by the commissioned boost speed The set point can be found on the front of the unit Figure 18 and is at its least sensitive when turned fully clockwise Note th...

Page 9: ...ication plate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk Technical or commercial considerations may from time to time make it necessary to alter the design performance and dimensions of equipment and the right is reserved to make such changes without prior notice 7 0 MAINTENANCE It is important that maintenance checks are recorded and that the schedule is always ad...

Page 10: ...10 30 06 21 Document Number 671864 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 1Z SC SW Installation Manual NOTES ...

Page 11: ...11 30 06 21 Document Number 671864 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 1Z SC SW Installation Manual NOTES ...

Page 12: ...12 30 06 21 Document Number 671864 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 1Z SC SW Installation Manual NOTES ...

Reviews: