Installation and Maintenance

MRXBOXAB-ECO-LP1SW Mechanical Ventilation Unit with Heat Recovery

EXTRA

EXTRA

CT F

CT F

AN

 

LI

AF

 

   

 

Supply  Extract  Supply  Extract  Supply  Extract

SPEED 1 

SPEED 2  

SPEED 3

3

2

7.0 ELECTRICAL CONNECTION

IMPORTANT

For good EMC engineering practice, any sensor cables or switched live 

cables should not be placed within 50mm of other cables or on the same 

metal cable tray as other cables.

Please note: the electrical connection of the unit 
must be carried out by a qualified electrician. 
The unit is supplied with a flexible cord for 
connection to the mains supply.

Electrical details:- 
Voltage: 240V 1ph 50Hz 
Consumption: LP1 - 1.3 Amps 
Fuse rating: 3 Amps

NOTE: This unit must be earthed. 
The cable from the mains power supply should 
be connected to a fixed wiring installation, via 
a fused isolator, in accordance with current IEE 
wiring regulations.

Note: Wiring is for reference 

purposes only as the 

connections above are 

factory fitted. 

Connection to Remote Fail 

Indicator Ref: MRXBOX95-RFI 

(optional).

Fuse 2A

MAINS

230V

50Hz

light

Room

Light

switch

(Double

Pole)

N

L

3 Pole

isolator

Kitchen switch

Blue

Brown

Black

Optional speed 3 switch

Supply cord

from unit

Grey

Green/yellow

Fuse 2A

MAINS

230V

50Hz

Room

lights

Light

switches

(Double

Pole)

N

L

3 Pole

isolator

Kitchen switch

Blue

Green/yellow

Brown

Black

Supply cord

from unit

Optional speed 3 switch

Grey

Unit serving kitchen and bathroom

Unit serving kitchen and two bathrooms

Figure 11. PCB Details

Figure 12.  

Figure 13.  

Disconnection from the supply mains 
must be incorporated within the fixed 
wiring in accordance with the wiring 
regulations and shall have a minimum 
contact separation of 3mm.

Disconnection from the supply mains 
must be incorporated within the fixed 
wiring in accordance with the wiring 
regulations and shall have a minimum 
contact separation of 3mm.

Figure 14.  

Connection of summer/winter switch

Black

2 core cable
from unit

Red

Volt free Summer / Winter Switch (supplied with unit)
Polarity is inconsequential
Warning! - Do not connect to mains! 

7.1 Examples of Typical Wiring Layouts

Summary of Contents for MRXBOXAB-ECO-LP1-OHSW

Page 1: ...that they do not play with the appliance 2 0 INSTALLATION Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing...

Page 2: ...pipe cutter 2 Remove any swarf from the end of the plastic pipe Ream the copper pipe end to remove any burr and file if necessary to remove any external sharp edges Mark the socket depth on the pipe a...

Page 3: ...imum high rate from Table 1 For sanitary accommodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high ex...

Page 4: ...1 2 3 735 Filter access distance Removable access filter Removable access filter 69 96 4 342 Required working space Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in ceil...

Page 5: ...mper 1 2 3 735 Filter access distance Removable access filter Removable access filter 69 96 4 342 Required working space Supply air to lounge via in ceilings Air Valve Extract air from kitchen via in...

Page 6: ...only as the connections above are factory fitted Connection to Remote Fail Indicator Ref MRXBOX95 RFI optional Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitchen...

Page 7: ...Intake and extract temperatures are monitored at the point the airflows enter the unit if the range falls within the set parameters the bypass damper is opened automatically to target an indoor comfo...

Page 8: ...on planned maintenance being undertaken This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintaine...

Reviews: