NuAire MRXBOX95B-450 WC Installation And Maintenance Manual Download Page 7

Isolation - Before commencing work make sure that the 

unit, switched live and Nuaire control are electrically 

isolated from the mains supply and switched live supply. 

6.1 Humidity adjustment

This product contains an internal humidity sensor fitted into the 
airflow extracting from the wet rooms. When the unit senses that the
humidity exceeds the set point the unit will boost to that set by the
commissioned boost speed. The set point can be found on the side of
the unit (see fig 8) and is at its most sensitive when turned fully 
clockwise. Note that the sensor is measuring humidity from all the
wet rooms at the same time and should not be relied on to solely
boost the unit. 

Additional switch should be used local to the wet rooms (see wiring
diagrams).

7.0 Maintenance/Cleaning

We recommend that the two G

4

 filters are inspected and cleaned

after 6 months and replaced every 12 months. This will be indicated
by the first LED from the right hand side flashing, the LED will flash
for a two week period and then reset itself.

The filters can be removed from the unit by removing the two filter
covers on the front panel of the unit. Take hold of the two circular
tabs either end of the filter covers and pull out.

The filter can now be extracted by pulling the removal loop on the
front edge of the filter. Once the filters have been inspected return 
or replace them as necessary.

Inspect the heat exchanger every 5 years. Generally check for damage
and security of components. The heat exchanger should be fitted in
the same orientation as originally assembled e.g. front label facing 
removable cover and top label nearest PCB.

Figure 15. Removing the two filter covers on the front panel 
of the unit.

Figure 16. The filters can be removed by pulling on the black tab on the
visible end of the filters.

Telephone 02920 858 400

7

27. 11. 17. Leaflet number 671617

Installation and Maintenance

MRXBOX95B-450 WC and MRXBOX95B-450

Filter covers

Filter being 
removed

Filter cover

8.0 Replacement of Parts

Should any component need replacing Nuaire keep extensive 
stocks for quick  delivery. Ensure  that  the  unit  is electrically 
isolated,  before  carrying  out  any  work.

Note: The supply cable must be replaced by an electrically 
competent person. 

When  ordering  spare  parts,  please  quote  the  serial  number 
of  the  unit  and  the  ARC number of  the  purchase  if  possible.

(This information will be available on the fan label).

9.0 Warranty

MRXBOX95B-450 WC and MRXBOX95B-450 have a 1 year 
warranty.

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or 
not installed, commissioned and maintained in accordance with 
the details contained in this manual and general good practice. 

The product warranty applies to the UK mainland and in 
accordance with Clause 14 of our Conditions of Sale. Customers 
purchasing from outside of the UK should contact Nuaire 
International Sales office for further details.

10.0 After Sales Enquiries

For technical assistance or further product information, please 
contact the After Sales Department.

Summary of Contents for MRXBOX95B-450 WC

Page 1: ...g to all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter ch...

Page 2: ...tested 2 5 Handing The unit may be handed to switch the supply and extract spigot positions this can be done by following the steps below and are shown in fig 6 Note This process should only be carried out by a competent and qualified person Step 1 Remove the front cover and inner panel followed by the rear panel to gain access to the inside of the unit Step 2 Partially pull out the metal tray to ...

Page 3: ...0 69 58 53 46 43 67 45 Open Outlet 63 57 57 64 51 46 39 36 62 30 Open Outlet 60 54 51 56 40 35 28 25 54 Supply Full Speed Open Outlet 59 62 65 71 65 63 57 53 71 90 Open Outlet 59 61 64 70 63 61 55 51 70 80 Open Outlet 58 61 63 68 61 59 53 49 68 65 Open Outlet 57 59 60 65 55 53 47 43 64 45 Open Outlet 55 56 57 60 48 46 40 36 59 30 Open Outlet 52 53 51 52 37 35 29 25 51 Breakout Sound Pressure Level...

Page 4: ...ensions for unit wall mounting bracket position on 450WC 450 units 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing Points Bracket to be fitted to the wall 40 0 CRS 86 0 Front view Side view 86 0 15 0 23 0 Flush mounting face to wall or back box View from back 86 0 Front view Side view 86 0 11 0 Figure 8a Dimensions 450WC unit switch Figure 9a Dimensions MRXBOX95 3SWITCH 4 x Spigots 180mm Internal Diam...

Page 5: ...connections Humidistat connections Fuse 5A MAINS 230V 50Hz N L MAINS 230V 50Hz N L 2 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Brown Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Grey Green yellow L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Green yellow Blue Brown Black Supply cord from u...

Page 6: ... to a wall or back box remove the front fascia by inserting a terminal screwdriver into the two openings along the bottom edge and prize open gently The fixing points on the back plate can then be accessed once the switch has been secured the front fascia can then be re fitted Note The wireless switch will typically operate up to a distance of 30m inside a building however this is dependent on the...

Page 7: ...check for damage and security of components The heat exchanger should be fitted in the same orientation as originally assembled e g front label facing removable cover and top label nearest PCB Figure 15 Removing the two filter covers on the front panel of the unit Figure 16 The filters can be removed by pulling on the black tab on the visible end of the filters Telephone 02920 858 400 7 27 11 17 L...

Reviews: