NuAire MRXBOX95B-450 WC Installation And Maintenance Manual Download Page 2

Any air intake terminal MUST be installed in accordance 

with the appropriate regulation. Installers are advised to be 

aware of the requirements of this standard when installing 

‘through the wall’ supply air ducting.

2.1 Condensate Drain

1.

If using a U-trap please ensure the U-trap has been filled to a
suitable level of water to avoid any air locks.

2.

If the condensation pipe is fitted in an unheated space the pipe
should be in insulated to prevent freezing. 

Figure 5a. Wet option. 
Condensate pipe connection 
to unit and a typical example 
of a “U” trap drainpipe.

2.2 Extract/input areas

The unit is designed to extract air from all wet rooms e.g. bathroom,
kitchen, en-suite, utility room (with sink) and WC’s. 

Supply air should be to all habitable rooms e.g. bedrooms and lounge.
Extract / input grilles should be adjustable valve types (not supplied).

2.3 Ducting

It is recommended that rigid ducting be used it all times.  
Flexible ducting has a very high resistance and it is impossible to 
calculate how much resistance will be on a system if used.

If used, the flexible ducting must be kept to a minimum and should 
always be pulled taut. A maximum of 300mm should be used on 
each leg.

To prevent condensation on the exterior of the outside air inlet duct
and the air outlet duct from the unit, these ducts should be insulated
with material having a thermal resistance of >0.625m

2

K/w. 

Ducting must be installed in such a way that resistance to airflow is
minimised. Bends should be kept to a minimum.

A minimum distance of 200mm between the appliance and any bends
in ductwork is recommended. Ideally 200mm diameter or 204 x 60mm
rectangular ducting should be used. 

Ducting joints must be sealed with silicone type sealant and shall be
adequately and reliably fixed to the appliance.

2.4 Ventilation flow rates

Flow rates applicable to local market. Meets EPBD 
requirements / EN308 tested.

2.5 Handing

The unit may be handed to switch the supply and extract spigot 
positions, this can be done by following the steps below and are
shown in fig. 6.

Note:  This process should only be carried out by a competent and
qualified person. 

Step 1.

Remove the front cover and inner panel followed by the rear

panel to gain access to the inside of the unit

Step 2.

Partially pull out the metal tray to access the circuit board

and cable connections.  All connections are required to be 
disconnected and although assistance has been given to allow correct
reconnection please familiarise yourself with the layout before doing
so.  Once all connections are disconnected the PCB tray can then be
fully removed, at this point the cables should be pulled through to the
other side of the unit.  Then slide the PCB tray partially into the unit
ensuring the stand offs are on the side the front cover is going to be
fixed and that no cables are trapped.  All cables can then be 
re-connected to the PCB as per the original arrangement, note the 
following cables have been tagged with a cable tie approximately
25mm from its termination point for identification as there are two
identical components.  These are supply control cables, supply power
cables, TH1 and SWL1.  

Once complete the PCB tray can be slid in the remainder of the way.

Step 3.

The filter should be reversed so the pull tab is at the side the

front cover is to be attached

Step 4.

The panels and cover removed in step 1 can then be 

re-assembled to the opposing sides that they were removed, care
should be taken to ensure a good seal is achieved.

Figure 6. Unit handing view.

Figure 7. Airflow through unit in handed configuration.

2

27. 11. 17. Leaflet number 671617

Installation and Maintenance

MRXBOX95B-450 WC and MRXBOX95B-450

Figure 5b. MVHR-DRAIN option.
Condensate drain, uninsulated
drain pipe with min 5

o

fall running 

to soil vent pipe.

Min 5

Drop

Collar

PCB

Front cover

Inner panel

Filter x 2

Rear panel

PCB tray

Exhaust air from 
house to outside

Supply air 
to house

Extract air 
from house

Intake air 
from outside

Summary of Contents for MRXBOX95B-450 WC

Page 1: ...g to all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter ch...

Page 2: ...tested 2 5 Handing The unit may be handed to switch the supply and extract spigot positions this can be done by following the steps below and are shown in fig 6 Note This process should only be carried out by a competent and qualified person Step 1 Remove the front cover and inner panel followed by the rear panel to gain access to the inside of the unit Step 2 Partially pull out the metal tray to ...

Page 3: ...0 69 58 53 46 43 67 45 Open Outlet 63 57 57 64 51 46 39 36 62 30 Open Outlet 60 54 51 56 40 35 28 25 54 Supply Full Speed Open Outlet 59 62 65 71 65 63 57 53 71 90 Open Outlet 59 61 64 70 63 61 55 51 70 80 Open Outlet 58 61 63 68 61 59 53 49 68 65 Open Outlet 57 59 60 65 55 53 47 43 64 45 Open Outlet 55 56 57 60 48 46 40 36 59 30 Open Outlet 52 53 51 52 37 35 29 25 51 Breakout Sound Pressure Level...

Page 4: ...ensions for unit wall mounting bracket position on 450WC 450 units 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing Points Bracket to be fitted to the wall 40 0 CRS 86 0 Front view Side view 86 0 15 0 23 0 Flush mounting face to wall or back box View from back 86 0 Front view Side view 86 0 11 0 Figure 8a Dimensions 450WC unit switch Figure 9a Dimensions MRXBOX95 3SWITCH 4 x Spigots 180mm Internal Diam...

Page 5: ...connections Humidistat connections Fuse 5A MAINS 230V 50Hz N L MAINS 230V 50Hz N L 2 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Brown Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Grey Green yellow L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Green yellow Blue Brown Black Supply cord from u...

Page 6: ... to a wall or back box remove the front fascia by inserting a terminal screwdriver into the two openings along the bottom edge and prize open gently The fixing points on the back plate can then be accessed once the switch has been secured the front fascia can then be re fitted Note The wireless switch will typically operate up to a distance of 30m inside a building however this is dependent on the...

Page 7: ...check for damage and security of components The heat exchanger should be fitted in the same orientation as originally assembled e g front label facing removable cover and top label nearest PCB Figure 15 Removing the two filter covers on the front panel of the unit Figure 16 The filters can be removed by pulling on the black tab on the visible end of the filters Telephone 02920 858 400 7 27 11 17 L...

Reviews: