NuAire MRXBOX95B-450 WC Installation And Maintenance Manual Download Page 1

The EMC Directive 

2014/30/EU  

The Low Voltage 

Directive 

20

14

/35/E

U

The unit must remain switched on at all times to maintain ventilation
within the dwelling. Turning the unit off will cause long term damage to
the unit and building fabric.

This appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of 
experience and knowledge, unless they have been given supervision or
instruction concerning the use of the appliance by a person for their
safety. Children should be supervised so that they do not play with 
the appliance.

MRXBOX95B-450 WC and 450

Mechanical Ventilation Unit with Heat Recovery and 
Summer Bypass for Wall Mounting

Installation and Maintenance

27. 11. 17. Leaflet number 671617

Ducting in 
ceiling void.

Side view of unit 
mounted on the
wall in a cupboard in
upright position as 
shown to comply 
with safety regulations.

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to a soil 
vent pipe.

Valve in ceiling.

Extract air 
from house

Intake air 
from outside

Exhaust air 
from house
to outside

Supply air 
to house

Unit weight is 30kg.

1.0 Introduction

The MRXBOX95B-450 WC and MRXBOX95B-450 wall mounted
units are designed to provide mechanical supply and extract 
ventilation with heat recovery and summer bypass. 
It also incorporates an integral humidistat and frost protection 
(-5 degrees C as standard).

The unit is supplied with independent control for both supply and 
extract for 3 speeds. 
To recover heat from the extract air the heat exchanger block is
utilised. The heat exchanger can recover up to 95% of the normally
wasted heat.

Figure 1. Airflow through unit in standard configuration.

2.0 Installation

Installation must be carried out by competent personnel in 
accordance with the appropriate authority and conforming 
to all statutory governing regulations. All mains wiring must be in
accordance with the current I.E.E. Regulations, or the appropriate
standards. Ensure that the mains supply (Voltage, Frequency and
Phase) complies with the rating label. 

Please note a clear working space is required around the installed unit
to allow the cover to be removed and provide sufficient access for
maintenance such as filter change.
Please allow a minimum of 600mm in front of the unit and 200mm
on the humidistat adjustment side. The (450 WC unit only) will also 
require a minimum of 400mm above the unit for access to the 
receiver in its standard position. Alternatively, the receiver may be 
fitted away from the unit as it is wired with a flying lead.

The fan must be installed indoors, on a suitable wall away from direct

sources of frost, heat, water spray or moisture generation. 
For a vibration-free result the unit must be mounted to a solid wall.

The unit is designed for wall mounting only on a solid wall, a gypsum
block or a stud wall will not suffice. Additional measures such as
extra studs or double panelling using 20mm MDF is required.
1.

One part of the mounting bracket should be offered up to the
wall, ensuring it’s located horizontally. Mark the fixing points
through the pre drilled holes in the bracket and install with screws
(by others), ensuring the interlock side is at the top, (fig. 2). 

2.

Install the unit on the wall by ensuring the bracket on the unit
interlocks over the wall mounted bracket (fig. 3).

Note: Care must be taken to ensure the unit is installed true in 
all 3 dimensions. Failure to do so may result in overflow from the
internal condensation drip tray.

Figure 2. Fixing the mounting bracket to the wall.

Figure 3. Mounting the unit on the wall mounted bracket.

Figure 4. Typical example of a cupboard mounted unit on a wall using 
the bracket.

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

1

Summary of Contents for MRXBOX95B-450 WC

Page 1: ...g to all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter ch...

Page 2: ...tested 2 5 Handing The unit may be handed to switch the supply and extract spigot positions this can be done by following the steps below and are shown in fig 6 Note This process should only be carried out by a competent and qualified person Step 1 Remove the front cover and inner panel followed by the rear panel to gain access to the inside of the unit Step 2 Partially pull out the metal tray to ...

Page 3: ...0 69 58 53 46 43 67 45 Open Outlet 63 57 57 64 51 46 39 36 62 30 Open Outlet 60 54 51 56 40 35 28 25 54 Supply Full Speed Open Outlet 59 62 65 71 65 63 57 53 71 90 Open Outlet 59 61 64 70 63 61 55 51 70 80 Open Outlet 58 61 63 68 61 59 53 49 68 65 Open Outlet 57 59 60 65 55 53 47 43 64 45 Open Outlet 55 56 57 60 48 46 40 36 59 30 Open Outlet 52 53 51 52 37 35 29 25 51 Breakout Sound Pressure Level...

Page 4: ...ensions for unit wall mounting bracket position on 450WC 450 units 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing Points Bracket to be fitted to the wall 40 0 CRS 86 0 Front view Side view 86 0 15 0 23 0 Flush mounting face to wall or back box View from back 86 0 Front view Side view 86 0 11 0 Figure 8a Dimensions 450WC unit switch Figure 9a Dimensions MRXBOX95 3SWITCH 4 x Spigots 180mm Internal Diam...

Page 5: ...connections Humidistat connections Fuse 5A MAINS 230V 50Hz N L MAINS 230V 50Hz N L 2 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Brown Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Grey Green yellow L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Green yellow Blue Brown Black Supply cord from u...

Page 6: ... to a wall or back box remove the front fascia by inserting a terminal screwdriver into the two openings along the bottom edge and prize open gently The fixing points on the back plate can then be accessed once the switch has been secured the front fascia can then be re fitted Note The wireless switch will typically operate up to a distance of 30m inside a building however this is dependent on the...

Page 7: ...check for damage and security of components The heat exchanger should be fitted in the same orientation as originally assembled e g front label facing removable cover and top label nearest PCB Figure 15 Removing the two filter covers on the front panel of the unit Figure 16 The filters can be removed by pulling on the black tab on the visible end of the filters Telephone 02920 858 400 7 27 11 17 L...

Reviews: