NuAire MRXBOX95AB-WM2 Installation And Maintenance Manual Download Page 6

Isolation - Before commencing work make sure that the 

unit, switched live and Nuaire control are electrically 

isolated from the mains supply and switched live supply. 

6

08. 05. 14. Leaflet Number 671640

Installation and Maintenance

MRXBOX95AB-WM2 Mechanical Ventilation with Heat Recovery & Summer Bypass

The filters fitted inside the unit are protected with a 

plastic film. Prior to commissioning remove the covers

(fig 13), take off the film and replace.

Filter covers

 

 

 

Figure 12. Removing

the two filter covers

on the front panel of

the unit.

 

Filter being 

removed

Filter cover

Figure 13.The filters

can be removed by

pulling on the black

tab on the visible end

of the filters.

Figure 11. Detail of unit control

on front panel.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

Humidity

adjustment.

6.0 Commissioning

1.

For the required air flow rates please refer to the design 

specification for the property, follow 2.4, or refer to building 

regulations ADF 2006/2010.

2. The unit is supplied with independent control for both normal 

and boost airflows. (see fig. 11). 

3. Correct commissioning is essential to ensure the ventilation 

air flowrates are met. It also ensures the unit is not over 

ventilating and causing excessive power consumption. 

4. Commissioning should be carried out in accordance with 

building regulations document “Domestic ventilation 

compliance guide”. A calibrated moving vane anemometer 

and hood will be required to carry out commissioning.

5. Adjustment valves should be locked in place to prevent 

further adjustment. 

6. Once commissioned the home owner / tenant should be 

informed that the unit should not be adjusted as it will have 

a detrimental effect on the indoor air quality and could result 

in condensation and mould growth. The label covering the 

control has an adhesive panel which should be removed post 

commissioning to prevent tampering.

6.1 Summertime boost facility

The unit has to ability to override both the trickle and boost

speeds to operate the fan to maximum airflow. See wiring 

diagram for details of operating this facility.

6.2 Humidity adjustment

This product contains an internal humidity sensor fitted into the

airflow extracting from the wet rooms. When the unit senses

that the humidity exceeds the set point the unit will boost to

that set by the commissioned boost speed. The set point can 

be found on the front of the unit (see Fig 11) and is at its least

sensitive when turned fully clockwise. Note that the sensor is

measuring humidity from all the wet rooms at the same time

and should not be relied on to solely boost the unit. Additional

switch should be used local to the wet rooms (see wiring 

diagrams).

7.0 Status Indication

The status of the unit is indicated by a series of LED’s on the

front cover. The varients are listed below.

8.0 Maintenance/Cleaning

We recommend that the two G3 fiters are inspected after 

6 months, and replaced every 12 to 18 months.

The filters can be removed from the unit by removing the two

filter covers on the front panel of the unit. Take hold of the two

circular tabs either end of the filter covers and pull out.

The filter can now be extracted by pulling the removal loop on

the front edge of the filter. Once the filters have been inspected

return or replace them as necessary.

Inspect the heat exchanger every 5 years. Generally check 

for damage and security of components. Refit cover.

Normal Mode

Supply Fan Fault

Extract Fan Fault

Boost

Summer Boost

Frost Protection

Filter Change

Summer Bypass

060923

 

 

 

 

 

 

 

 

Summary of Contents for MRXBOX95AB-WM2

Page 1: ...d provide sufficient access for maintenance such as filter change Please allow a minimum of 350mm in front of the unit The fan must be installed indoors on a suitable wall away from direct sources of...

Page 2: ...nded Ideally 150mm diameter or 204 x 60mm rectangular ducting should be used Refer to dwelling design drawing figure 7a and 7b on page 4 for further information Ducting joints must be sealed with sili...

Page 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate n the minimum air supply ra...

Page 4: ...Minimum 300mm Air supply to lounge via Air Valve Part no VS125 in ceilings Extract air from kitchen bathroom via Air Valve Part no VS125 in ceilings Air supply to bedrooms via Air Valve Part no VS125...

Page 5: ...Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Optional summer boos...

Page 6: ...indoor air quality and could result in condensation and mould growth The label covering the control has an adhesive panel which should be removed post commissioning to prevent tampering 6 1 Summertim...

Page 7: ...ated before carrying out any work Note The supply cable must be replaced by an electrically competent person When ordering spare parts please quote the serial number of the unit and the ARC number of...

Page 8: ...have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requirements given for the individual...

Page 9: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Page 10: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Page 11: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Page 12: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Page 13: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Page 14: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Reviews: