MRXBOX95AB-WM2 Mechanical Ventilation with Heat Recovery & Summer Bypass

For good EMC engineering practice, any sensor cables 

or switched live cables should not be 

placed within 50mm of other cables or on the same 

metal cable tray as other cables.

5.0  Electrical Connection

Please note: the electrical connection of the unit must be be carried

out by a qualified electrician.

The unit is supplied with a flexible cord for connection to the mains

supply.

Electrical details:-

Voltage:

240V  1ph  50Hz

Consumption:  WM2 - 1.3 Amp 

Fuse rating: 

3 Amp

NOTE This unit must be earthed.

The three core cable from the mains power supply should be 

connected to a fixed wiring installation, via a fused isolator, in

accordance with current IEE wiring regulations.

     

    

 

  

 

  

 

 

   

 

 

 

 

 

   

 

   

     

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

Fuse 2A

MAINS

230V

50Hz

Room

light

Light 

switch 

(Double 

Pole)

N

L

Fuse 2A

MAINS

230V

50Hz

Room

lights

Light 

switches 

(Double 

Pole)

N

L

3 Pole

isolator

3 Pole
isolator

Kitchen switch

Kitchen switch

Blue

Brown

Black

Optional summer boost switch

Supply cord

from unit

Green/yellow

Blue

Brown

Black

Supply cord

from unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

Optional summer boost switch

Grey

Grey

Green/yellow

Unit serving kitchen and bathroom

Unit serving kitchen and two bathrooms

Figure 9. 

Figure 10. 

S

WL

    

   S

WL1 

  L 

  N

C

N
7

 E

X

T

R

A

C

T

C

N
6

 S

U

P

P

L

Y

BLU

WHI

YEL

RED

   

S

UPPL

Y

B

YP

ASS

SU

PPL

Y FAN

EXTRA

CT F

AN

B

L

U

B

R

N

B

R

N

B

L

U

EX

TRACT F

AN

B

L

U

B

R

N

EXTERN

AL PUMP

BLU

WHI

YELI

RED

 F

A

IL

CN8

TH1    TH2

L   

     

 N

  Supply  Supply  Extract  Extract

  Trickle 

Boost   Trickle 

Boost

CN5

Connection to Remote Fail 

Indicator Ref: MRXBOX95LH-RFI

3

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Wiring is for reference 

purposes only as the connections 

above are factory fitted.

The unit is pre-wired with a 

2 metre fly lead.

 

 

 

Figure 8.

Disconnection from

the supply mains must

be incorporated within

the fixed wiring in

accordance with the

wiring regulations and

shall have a minimum

contact separation 

of 3mm.

Disconnection from

the supply mains must

be incorporated within

the fixed wiring in

accordance with the

wiring regulations and

shall have a minimum

contact separation 

of 3mm.

Summary of Contents for MRXBOX95AB-WM2

Page 1: ...d provide sufficient access for maintenance such as filter change Please allow a minimum of 350mm in front of the unit The fan must be installed indoors on a suitable wall away from direct sources of...

Page 2: ...nded Ideally 150mm diameter or 204 x 60mm rectangular ducting should be used Refer to dwelling design drawing figure 7a and 7b on page 4 for further information Ducting joints must be sealed with sili...

Page 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate n the minimum air supply ra...

Page 4: ...Minimum 300mm Air supply to lounge via Air Valve Part no VS125 in ceilings Extract air from kitchen bathroom via Air Valve Part no VS125 in ceilings Air supply to bedrooms via Air Valve Part no VS125...

Page 5: ...Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Optional summer boos...

Page 6: ...indoor air quality and could result in condensation and mould growth The label covering the control has an adhesive panel which should be removed post commissioning to prevent tampering 6 1 Summertim...

Page 7: ...ated before carrying out any work Note The supply cable must be replaced by an electrically competent person When ordering spare parts please quote the serial number of the unit and the ARC number of...

Page 8: ...have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requirements given for the individual...

Page 9: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Page 10: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Page 11: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Page 12: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Page 13: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Page 14: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Reviews: