NuAire MRXBOX-ECO2-AE Installation Manual Download Page 8

8

04. 12. 20. Document Number  671824

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOX(AB)-ECO2-AE

Installation Manual

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 20, take off the 
film and replace.

For the required air flow rates please refer to the design 
specification for the property, follow Scetion 3.7, or refer to 
building regulations ADF 2010.

The unit is supplied with independent control for both normal and 
boost airflows (Figure 18). 

Correct commissioning is essential to ensure the ventilation air 
flow rates are met. It also ensures the unit is not over ventilating 
and causing excessive power consumption. 

Commissioning should be carried out in accordance with building 
regulations document “Domestic ventilation compliance guide”. 
www.planningportal.gov.uk/building regulations/approved 
documents/partf/associated 
A calibrated moving vane anemometer and hood will be required 
to carry out commissioning.

Adjustment valves should be locked in place to prevent further 
adjustment. 

Once commissioned the home owner / tenant should be informed 
that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation 
and mould growth. The clear panel covering the control has 
an adhesive panel which should be exposed and sealed post 
commissioning to prevent tampering.

Speed 1 is limited to never exceed speed 2, when commissioning 
speed 2 should always be set first.

 

18 

Front Panel Unit Control Detail

Humidity 

adjustment.

(AB unit only).

Speed 2

Speed 1

Speed 2

Speed 1

6.0 CONTROLS

6.1 Speed 3

The unit has the ability to override both speed 1 and speed 2 to operate 
the fan to maximum airflow. See wiring diagram for details of operating 
this facility.

6.2 Humidity Adjustment (AB Unit Only)

This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the 
humidity exceeds the set point the unit will boost to that set by the 
commissioned boost speed. The set point can be found on the front 
of the unit (Figure 18) and is at its least sensitive when turned fully 
clockwise. Note that the sensor is measuring humidity from all the wet 
rooms at the same time and should not be relied on to solely boost 
the unit. Additional switch should be used local to the wet rooms (see 
wiring diagrams).

6.3 Status Indication

The status of the unit is indicated by a series of LED’s on the front cover. 
The variants are listed below.

The display on the unit control panel will not indicate when a 
higher speed setting has been triggered by an external source, such 
as an ES-PIR2 etc.

19 

LED Indicators

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

6.4 Integral Automatic HX Bypass (AB Unit Only) 

Intake and extract temperatures are monitored at the point the 
airflows enter the unit, if the range falls within the set parameters the 
bypass damper is opened automatically to target an indoor comfort 
temperature all year round.

The extract temperature is an average from all wet rooms. If this 
exceeds 25°C the unit may go into bypass depending on outside 
temperatures.

6.5 Thermal Bypass (Non-AB Unit Only)

In the event of excessive outside temperatures, and to help prevent 

over-heating, the supply fan will automatically reduce to a trickle 

speed. Under these circumstances additional ventilation measures may 
be required e.g. open windows or trickle vents (if fitted).

6.6 Frost Protection

In the event of the intake air temperature at the unit dropping below 
the predetermined set point (-5°C as standard) the supply fan will 
reduce to minimum speed, once the temperature rises above the set 
point the fan will return to its commissioned speed.

Please note this mode will only activate after ten days of continuous 
run time. If commissioning of the unit is outside of this time frame 
please notify the after sales department prior to site visit.

7.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

Isolation - Before commencing work make sure that the unit, 
switched live and control are electrically isolated from the mains 
supply and switched live supply.

7.1 Routine Maintenance

Nuaire recommend that filters are inspected every 6 months and 
replaced every 12 months. A flashing LED (Section 6.3) will indicate that 
a filter change is required. This indication repeats every 12 months and 
will turn off automatically after 5 Days.

Remove the filter covers on the front panel of the unit by gripping the 
two circular tabs either end of the filter covers and pulling away from 
the unit. The filter can now be extracted by pulling the removal loop on 
the front edge of the filter. Once the filters have been inspected return 
or replace them as necessary. 

Inspect the heat exchanger every 5 years. Generally check for damage 
and security of components. Refit cover.

Summary of Contents for MRXBOX-ECO2-AE

Page 1: ...unless they have been given supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user m...

Page 2: ...ON Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations All mains wiring must be in accordance wit...

Page 3: ...e Collar 9 Condensate Drain MVHR DRAIN Condensate Drain Uninsulated Drain Pipe With Min 5 Fall Running To SVP 3 2 1 Solid Wall Mounting Recommended The MVHR unit fixed to a solid wall construction usi...

Page 4: ...40 series of British Standards deals with this issue and currently states that an air intake must be at a minimum distance of 300mm from a gas boiler balanced flue Installers are advised to be aware o...

Page 5: ...very high moisture levels are likely to occur Therefore it is advisable that if the installation and building works are complete the unit is left running If the building works are not complete please...

Page 6: ...n pipe with min 5 o fall running to SVP Insulated extract duct 12 Typical Ducted Arrangement For A Wall Mounted Unit Using Circular Ducting 3 10 2 Rectangular Ducting Exhaust air from kitchen bathroom...

Page 7: ...panel of the enclosure should be removed by loosening the two screws the Ecosmart cable can then be connected to the underside of the MVHR unit within The cable should be fed through rubber blanking...

Page 8: ...ms 6 3 Status Indication The status of the unit is indicated by a series of LED s on the front cover The variants are listed below The display on the unit control panel will not indicate when a higher...

Page 9: ...ing nylon corner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other...

Page 10: ...10 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Page 11: ...11 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Page 12: ...12 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Reviews: