MRXBOX(AB)-ECO2-AE

Installation Manual

3.3 Condensate Drain

The MVHR unit inside the enclosure is fitted with a straight coupling to 
allow 21.5mm overflow pipe (not supplied) to be attached using solvent 
cement, the pipe should be passed through the flexible adhesive backed 
cover plate before the solvent cement is applied.

The pipe can then be inserted into the coupling of the MVHR unit and 
the cover plate slid along the length to bond against the base panel of 
the enclosure preventing noise breakout (Figure 7).

1. The condensate must be discharged under a water level in a U-trap 

drainpipe or an alternative drain method which acts as an airlock. 

2. This condensate discharge connection is suitable for 21.5mm 

diameter overflow pipe. Solvent cement should be used to make the 
joint. 

3. If using a U-trap please ensure the U-trap has been filled to a 

suitable level of water to avoid any air locks.

4. If the condensation pipe is fitted in an unheated space the pipe 

should be in insulated to prevent freezing.

Nuaire recommend MVHR-DRAIN be used as the primary 
condensate take-off (Figures 9 and 10). 

Wall Bracket Dimensions

Solvent cement to be applied

Flexible adhesive backed 
cover plate

Overflow pipe

Min 5

Drop

Condensate Drain - Wet Connection: Unit Pipe Connection To 
Typical “U” Trap Drainpipe Example

Collar

Condensate Drain - MVHR-DRAIN: Condensate Drain, 

Uninsulated Drain Pipe With Min 5° Fall Running To SVP.

3.2.1 Solid Wall Mounting (Recommended)

The MVHR unit fixed to a solid wall construction using the 
mounting bracket provided.

 

Ducting in the 
ceiling void.

Side view of unit 
mounted on the
block wall in a 
cupboard using 

MVHR-DRAIN

the wall brackets.

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 45kG

Cupboard Mounted Unit Fixed to Block Work Wall Example

3.2.2 Stud Partition Wall Mounting (Alternative)

If it is not practical to use a solid wall, the unit should be fixed to a 
stud partition with a 25mm minimum thickness MDF panel solidly 
fixed behind the plasterboard.

If fixing to a stud wall the MDF panel should extend, width wise, over 
a minimum of 3 vertical studs with centres of no more than 400mm. 
A vertical stud should be located to correspond with the position each 
mounting bracket is to be fixed to provide additional support.

Add additional vertical supports if necessary. Height wise, the MDF 
panel should extend from floor to ceiling.

Fix the mounting bracket to the wall (Figure 4) and use the wall 
mounted bracket to mount the unit on (as shown in Figure 6).

 

 

Ducting in the 
ceiling void.

Side view of unit 
mounted in a 

with the 25mm 

cupboard fixed to 
a stud partition

MDF fixed behind 
the plasterboard
using the wall 

MVHR-DRAIN

brackets. 

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 45kG

Cupboard Mounted Unit Fixed to Stud Partition Wall Reinforced 
With MDF Panel Example

 

Summary of Contents for MRXBOX-ECO2-AE

Page 1: ...unless they have been given supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user m...

Page 2: ...ON Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations All mains wiring must be in accordance wit...

Page 3: ...e Collar 9 Condensate Drain MVHR DRAIN Condensate Drain Uninsulated Drain Pipe With Min 5 Fall Running To SVP 3 2 1 Solid Wall Mounting Recommended The MVHR unit fixed to a solid wall construction usi...

Page 4: ...40 series of British Standards deals with this issue and currently states that an air intake must be at a minimum distance of 300mm from a gas boiler balanced flue Installers are advised to be aware o...

Page 5: ...very high moisture levels are likely to occur Therefore it is advisable that if the installation and building works are complete the unit is left running If the building works are not complete please...

Page 6: ...n pipe with min 5 o fall running to SVP Insulated extract duct 12 Typical Ducted Arrangement For A Wall Mounted Unit Using Circular Ducting 3 10 2 Rectangular Ducting Exhaust air from kitchen bathroom...

Page 7: ...panel of the enclosure should be removed by loosening the two screws the Ecosmart cable can then be connected to the underside of the MVHR unit within The cable should be fed through rubber blanking...

Page 8: ...ms 6 3 Status Indication The status of the unit is indicated by a series of LED s on the front cover The variants are listed below The display on the unit control panel will not indicate when a higher...

Page 9: ...ing nylon corner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other...

Page 10: ...10 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Page 11: ...11 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Page 12: ...12 04 12 20 Document Number 671824 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO2 AE Installation Manual NOTES...

Reviews: