OPERATION RULES

  

The fan is rated for connection to single-phase 

 220–240 V / 50/60 Hz power mains.  

AC

The fan is designed for continuous operation always connected to power mains.  
Air motion direction in the system must match the pointer on the fan casing.  
Ingress protection rating IPX4.  
The fan is rated for operation at the ambient temperature ranging from +1 °C 

 +45 °C. 

up to

The transporting medium temperature must not exceed  +60 °C. 
 
 

ELECTRONICS CONTROL LOGIC  

The fan with the timer T is turned into operation after control voltage is supplied by the external switch 
(e.g., by the light switch)  to the input terminal LT. After the control voltage is off the fan continues to 
operate within the timer period set by the timer from 2 to 30 minutes. 
To adjust there off-delay timer rotate the potentiometer control knob T clockwise to increase and 
counter-clockwise to decrease the  off-delay time respectively (fig. 3 ).  

0

Warning! The timer circuit is under mains voltage. All adjustments are allowed after disconnection from 
power mains. The fan  delivery set includes a specially designed plastic screwdriver for fan settings 
adjustments. Use the screwdriver to alter the turn-off delay time  or the humidity threshold. 
Do not use a screwdriver, knife, etc. for adjustment operations not to damage the circuit board.  
The fan model 

 U(U1) (fig. 3 ) is equipped with electronic TSC module (speed controller with 

ILM

+

2

electronic thermostat) for automatic fan speed (air flow) control depending on air temperature.  
The electrical compartment incorporates 2 control knobs:  
for setting the motor speed; 
for setting the electronic thermostat.  
The fan cover incorporates a LED-light thermostat indicator.  
To adjust the thermostat set point rotate the thermostat control knob clockwise to increase  the set 
point and counter clockwise to decrease the thermostat set point. To adjust the fan speed (air flow) rotate 
the speed control knob in the same way.   
The fan has two operating logics - temperature-based and timer-based operating logics. 
temperature-based operating logic 

 U):  

( LM

I

+

This logic is used to keep air temperature to within 2 °C. In this case the fan switches are rare. 
The motor sets to maximum speed as the temperature reaches the thermostat set point. 
The fan runs with the speed set by the speed controller if the temperature drops 2 °C below the set point or 
if the initial temperature us below the set point. 

4

Summary of Contents for ILM+ P Series

Page 1: ...IN LINE MIXED FLOW FANS Nuaire ILM USER S MANUAL www nuaire co uk 2017...

Page 2: ...hysical mental or sensory capacities without proper practical experience or expertise unless they are controlled or instructed on the product operation by the person s responsible for their safety Do...

Page 3: ...rom 2 to 30 minutes fig 30 ILM XXX U U1 modification with a speed controller with electronic thermostat built in temperature sensor and power cable with a plug fig 32 ILM XXX Un U1n modification with...

Page 4: ...ver for fan settings adjustments Use the screwdriver to alter the turn off delay time or the humidity threshold Do not use a screwdriver knife etc for adjustment operations not to damage the circuit b...

Page 5: ...G The fan is suitable both for horizontal or vertical mounting on the floor on the wall or on the ceiling fig 2 as one unit or included into connected in parallel In case of the horizontal fan mountin...

Page 6: ...acid or alkali vapours that may cause corrosion of the product parts WARRANTY ILM units have a 1 year warranty The warranty starts from the day of delivery and includes parts and labour for the first...

Page 7: ...e product in case of replacing and using parts units and components of the product not prescribed by the manufacturing company in case of other use of the product other than intended use in case of th...

Page 8: ...tions of third persons an accident or force majeure circumstances The manufacturing company shall not be responsible for damage to health and property of the customer caused by the customer s violatin...

Page 9: ...9 2 min 1 m...

Page 10: ...10 5 3 6 4 MOUNTING QF...

Page 11: ...9 7 8 11 10 11...

Page 12: ...13 14 15 16 17 18 19 ILM 100 125 ILM 150 160 200 250 315 MAX MIN MAX MIN MAX MIN MAX MIN N L2 N L QF X N L1 N L QF X QF N L1 L2 S N L X L2 L L1 N X N L2 X N L QF N L1 X N L QF QF N L1 L2 S N L X L2 L...

Page 13: ...k for 5 contacts terminal block for 4 contacts N L ST QF N L LT L1 X S N L ST QF N L LT L1 X L2 N L ST QF N L LT X N L ST QF N L LT L1 X S N L ST QF N L LT L1 X N L ST QF N L LT L2 X terminal block fo...

Page 14: ...14 27 24 25 26 28 29 QF...

Page 15: ...15 31 30 30 min 2 min X MIN MAX STOP...

Page 16: ...16 33 32 speed control knob thermostat control knob min max ILM U U1 ILM Un U1n speed control knob...

Page 17: ...36 34 37 35 17...

Page 18: ...18 40 38 41 39...

Page 19: ......

Page 20: ...0 315 V RV T U P 1 n ACCEPTANCE INFORMATION Fan is ready for using Acceptance stamp Date of production Sold name of trade enterprise and stamp of the shop Date of sale mark the proper model only www n...

Reviews: