HIAQM

Installation Manual

Refit switch cover. 

 
 
 

Schematic Diagram

Pressure Sensor Internals

2 - NO

3 - C

1 - NC

3 - C Contacts 2 - NO
when the difference between 
positive & negative pressure 
is equal to the set pressure.

Customer 240 V
Connection

Customer 240V
Connection

Internal Connection
Customer Connection

*Note 1: NC has been 
blanked off.

*Note 2: Pressure setting 
of 125Pa above clean filter 
pressure is recommended.

*Note 3: If a different 
arrangement is required, 
then the internal LED con-
nections can be removed.

240 V
Indicator

240 V

Indicator

Sensor Diagram

2 - NO

1 - NC

*Note 2

*Note 3

*Note 1

Differential 

Pressure 

Setting 

3 - C

12 

Dirty Filter Switch Wiring

3.2.2 Setting Dirty Filter Switch Pressure

Nuaire recommend the pressure switch be set to trigger when the 
filters experience a 125 Pa increase above the clean filter resistance for 
the largest commissioned airflow rate. Use the adjustment dial to set 
the pressure at which the switch will trip. When the pressure falls below 
this set value, the switch returns to its resting position.

4.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

4.1 Carbon Filter Maintenance

After a period of time, activated carbon in filter cells will become 
saturated by odour, gas and chemical vapour contaminants and will 
require replacement in order to maintain the filtration efficiency of the 
carbon filter. HIAQM Carbon Filters have a lifespan of 2 years under 
normal conditions. However, under certain circumstances, such as 
highly polluted air, carbon filters may need to be replaced on a more 
frequent basis. Contact Nuaire for accurate assessments of carbon filter 
lifespans.

4.2 Routine Maintenance

Clean all areas of unit and treat any areas of corrosion.

Check all access doors for leakage and if necessary locks should be 
adjusted and any replacement gasket materials should be replaced 
as required. 

4.3 Every 3 Months 

Check filters and change/clean if required, failure to do so may 
impair the performance and energy efficiency of this unit.

4.4 Annually 

Thoroughly inspect the unit and its components for corrosion, 

acting immediately to treat/restore any damaged areas. 

4.5 Replacement Filters

To check the filter type within a unit refer to the module product label. 
Replacement filters can be purchased direct from Nuaire using the 
below code format.

1

-

2

-

3

4

-

5

HIAQM

-

015

-

1

D

-

FILTER

1. Range:  

 

HIAQM  

= Haven Indoor Air Quality    

 

   Filter 

Module

2. Reference Flowrate: 

015

  

= 0.15m

3

/s 

  

 

025  

= 0.26m

3

/s 

  

 

045

  

= 0.35m

3

/s 

  

 

055  

= 0.48m

3

/s 

  

 

065

  

= 0.58m

3

/s

3. Filter Position:   

1  

= Primary Panel Filter 

  

 

2  

= Secondary Bag Filter

4. Filter Grade: 

 

A

  

= G4 / ISO Coarse 

  

 

B

  

= M5 / PM10 50% 

  

 

C

  

= M6 / PM2.5 50% 

  

 

D

  

= F7 / PM1 50% 

  

 

E

  

= F8 / PM1 70% 

  

 

F

  

= F9 / PM1 80% 

  

 

G

  

= Rigid Carbon Panel Unit  

 

 

   (RCP)

For reference on the filter type required please refer to the module 
product label e.g. The codes required to order both filters of a  

HIAQM-025-S-D-G-11 

would be:

HIAQM-015-1D-FILTER 

HIAQM-015-2G-FILTER

5.0 WARRANTY

The 5 year warranty starts from the day of delivery and includes parts 
and labour for the first year. The remaining period covers replacement 
parts only (replacement filters not included).

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or not 
installed, commissioned and maintained in accordance with the details 
contained in this manual and general good practice.

The product warranty applies to the UK mainland and in accordance 
with Clause 14 of our Conditions of Sale. Customers purchasing from 
outside of the UK should contact Nuaire International Sales office for 
further details.

Failure to maintain the unit as recommended will invalidate the 

Summary of Contents for HIAQM

Page 1: ...ely electrically isolated before any panels are removed Check mains supply and control connections REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information This manual contains important information on the safe and appropriate assembly transport commissioning operation maintenance disas...

Page 2: ...age Filter A G4 ISO Coarse Panel B M5 PM10 50 C M6 PM2 5 50 D F7 PM1 50 E F8 PM1 70 F F9 PM1 80 H No Filter 5 Secondary Stage Filter A G4 ISO Coarse Bag B M5 PM10 50 C M6 PM2 5 50 D F7 PM1 50 E F8 PM1 70 F F9 PM1 80 G Rigid Carbon Panel Unit RCP 6 Unit Finish 1 Standard 4 Coastal C4 7 Unit Roof 1 Standard Unit No Roof W Twin Pitched Roof Factory Fitted This units coastal finish has been designed t...

Page 3: ...rd to access and maintenance requirements and the objective of minimising the system ductwork resistance The units are heavy and should be mounted using the fixing brackets supplied or other suitable methods of support The supporting structure must be assessed for structural suitability The recommended installation method is to use standard Unistrut channel secured to the slab steelwork above the ...

Page 4: ...e To aid in installation where IAQM units are to be close coupled to a matching size XBC unit the double Supply Extract flange connector of the XBC unit should be removed from the XBC and fitted to the IAQM unit s inlet along with the extract leg ducting The full assembly of IAQM unit XBC flange connector and extract ducting can then be raised and connected to the XBC unit For further details see ...

Page 5: ... carbon filter lifespans 4 2 Routine Maintenance Clean all areas of unit and treat any areas of corrosion Check all access doors for leakage and if necessary locks should be adjusted and any replacement gasket materials should be replaced as required 4 3 Every 3 Months Check filters and change clean if required failure to do so may impair the performance and energy efficiency of this unit 4 4 Annu...

Page 6: ...ed in energy from waste centres Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy Please call After Sales Support for further information on items not listed above Ensure that Nuaire product is made safe from any electrical water refrigerant supplies before dismantling commences This work should only be undertaken by a qualified person in accordanc...

Page 7: ...7 16 04 21 Document Number 671965 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk HIAQM Installation Manual NOTES ...

Page 8: ...8 16 04 21 Document Number 671965 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk HIAQM Installation Manual NOTES ...

Reviews: