4
16. 10. 20. Document Number 670901
Nuaire |
Western Industrial Estate
|
Caerphilly
|
CF83 1NA
|
nuaire.co.uk
FLAT2000 L/R
Installation Manual
8
Side Input Installation (Front View)
Alternative
spigot positions
(inlet only)
FLATMASTER
Input grille (louvres
slant downwards)
100mm dia / 121x60mm rectangular ducting
(note input side kept as short as possible)
100mm dia / 121x60mm
rectangular ducting
Outside wall
Room
(typical)
Hallway
(typical)
Discharge
grille (note
louvres
slant
upwards)
Minimum
height 1.8m
9
Rear Input Installation (Top View)
FLATMASTER
Note alternative
inlet spigot positions
Outside wall
Hallway
(typical)
Air input
100mm dia ducting
Air
discharge
Minimum
height 1.8m
3.5 Inlet / Outlet Grille Installation
If a fly screen is fitted it should be removed from both the internal and
external grille.
When installing the internal grille, the louvres must slant
upwards to ensure the correct air circulation and the avoidance of
unpleasant down draughts. The outside wall input grille louvres
must slant downwards.
Standard 100mm diameter ducting or 121 x 60mm ducting is used to
connect the Flatmaster to the input and discharge grilles.
Any air intake terminal MUST be installed in accordance with the
appropriate regulation.
As a guide, the BS5440 series of British Standards deals with this
issue and currently states that an air intake must be at a minimum
distance of 300mm from a gas boiler balanced flue. Installers are
advised to be aware of the requirements of this standard when
installing ‘through the wall’ supply air ducting. Similarly, supply
and extract air grilles should be at least 300mm apart.
The internal grille must not be placed within 1.5m of a smoke
alarm.
4.0 DIMENSIONS(mm)
Dimensions for the space required can be determined from the
dimensions shown in Figure 10 below.
Allow an additional 32mm for the length of each end spigot and any
additional room for installation and maintenance e.g. access to screws
on top and bottom of unit for front cover.
10
Unit Dimensions
485
100mm dia. or 121 x 60mm
interchangeable spigots supplied with unit
Alternative inlet
end spigots
320
160
Alternative end
spigot panels
100mm dia.
spigot shown
121 x 60mm rectangular
spigot indicated
Alternative (knock out)
spigot positions
on rear face 100mm dia. only
15mm
100mm dia. spigot
(103mm dia. x 6mm
shoudler at base of spigot)
32
32mm from edge
of spigot shoulder
186.5
148
241
52
267mm
between
feet
Front view
End view
Back view