3.5 Status Screen
This is the default screen showing on the display during
normal operation.
The first two items are for information only.
System:
shows the name of the control system.
Status:
shows the current status of the system.
The options are:
OK
– system is fully operational.
Fault
– there is a fault in the system; generally means
a fan has failed.
Frost
– if a LPHW heater is fitted the downstream
temperature is 4
o
C or below. When this occurs; the fan
is switched off and the coil’s control valve is switched
to the fully open position. Select heating mode, check
that the boiler and circulating pump is running and that
hot water is reaching the coil.
Heater fault
– the over-temperature protection of the
electric heater battery has tripped.
This must be investigated and manually reset at the
fan unit.
Comms error
– problem communicating with Ecosmart
fan unit.
Op. Mode:
this shows the current operating mode.
The options are:
Off
– the fan system is switched off manually.
Manual
– the fan system is running under manual
control.
Default Program
– this provides basic ventilation
with fan running at speed 5 between 8:00 and 18:00
(i.e. 8am to 6pm). The fan will be off at other times.
Custom Program A
– custom program A as set up
by the user.
Custom Program B
– custom program B as set up
by the user.
To select a different operating mode, highlight the item
and use the adjustment keys ‘<’ & ‘>’ to change.
Function:
this shows the current selected function of the
fan system either selected manually or via the program.
The options are:
Off
– the fan is switched off.
Ventilation
– ventilation only is selected.
Venti heating
– both ventilation and heating
are selected.
Venti cooling
– both ventilation and cooling
are selected.
Fan Speed:
this shows the current selected fan speed either
selected manually or via the program.
The options are:
1 to 10
– speed 1 to 10.
Auto
– speed will be dictated by an Ecosmart sensor.
Trickle
– locked in minimum speed by the program
(this is not selectable manually, see below).
To change the function and/or speed; highlight the item by
pressing it once and use the ‘<’ and ‘>’ to change the values.
Please note if the operating mode (Op. Mode) is one of the
programs then any changes to function and speed is
temporary. The changes will be overridden when the program
enters its next programmed period. The only exception will be
the speed if the program calls for manual speed setting.
Clean:
Press this to enter safe cleaning mode before
attempting to clean the control.
Menu:
This will bring up the menu to allow access to change
day & time etc.
3.6 Menu screen
This screen allows access to the various screen modes
mentioned in previous sections.
1. Set Day/Time:
see 3.1.
2. Initial System Set Up:
see 3.2.
3. Set Programme:
see 3.3.
4. Contact Details:
gives the contact detail for
sales and service.
5. Safe Cleaning mode:
see 3.7
Press ‘Exit’ to return to Status Screen.
7
Installation and Operating Instructions
ES-LCD User Control
11. 05. 17. Leaflet Number 671415