Installation and Maintenance

AXUS Circular Long Cased Axial Flow Fans

4.4 Control Connections

4.4.1 Mains Connections

Mains cables should be suitably sized and terminated at terminals 
shown on the appropriate diagram.

4.4.2 Control Connections

4.4.3 Switched Live (SL) terminal at the PCB

4.4.4 Damper Connections

OP - 

230V 50Hz 1A max supply to open the damper. 

CL - 

230V 50Hz 1A max supply to close the damper. 

N - 

Neutral supply to damper. 

RET - 

230V ac return signal from the damper limit switch indicates the 

damper has reached its operating position. If the return signal is not 
present, the fan will wait for 1 minute before starting.

Note: If a damper is not fitted, connect a link wire from OP to RET. This 
will cancel the delay.

4.4.5 Volt Free Relay Contacts

4.4.6 Data Cable Installation

A 4-core SELV data cable is used to connect devices.

Do not run data cable in the same conduit as the mains cables and 
ensure there is a 50mm separation between the data cable and other 
cables. The maximum cable run between any two devices is 300m 
when it is installed in accordance with the instructions.

Please note that the total data cable length used in any system must 
be less than 1000m. Keep the number of cable joints to a minimum to 
ensure the best data transmission efficiency between devices.

4.4.7 Maximum Number Of Devices

The maximum number of devices (including fans) that can be 
connected together via the cable is 32, irrespective of their functions.

4.4.8 Other Low Voltage Cables e.g. BMS Signal

Follow

 the basic principle (as per section 4.4.6). Keep the

 cable run as 

short as possible, maximum cable length of 50m. If the cable is longer 
than 12m, Nuaire recommend using screened cable with the screening 
grounded at one end only (preferably at the inverter end).

4.4.9 Other Low Voltage Cables e.g. BMS Signal

Follow the basic principle (as per section 4.4.6). K

eep the cable run as 

short as possible, maximum cable length of 50m. If the cable is longer 
than 12m, Nuaire recommend using screened cable with the screening 
grounded at one end only (preferably at the inverter end).

4.4.10 BMS Input Signals

The BMS connection is made with a plug-in connector 
via the socket (see fig. 11).

To ensure the connection is made only by suitably 
qualified and authorised personnel the plug is not 
supplied.

It is available from R S Components,  
Part No. 403-875 or Farnell, Part No. 963-021.

The system’s response to a 0-10V dc BMS signal is given in the 
following table.

Note: 
The BMS signal will override any sensors and user control connected in 
the system. The voltage tolerance is +/- 125mV and is measured at the 
fans terminal.

IMPORTANT

Reversal of the BMS connection will damage the 

control.

Mains Connection
230V 50Hz 1 phase

N E

L

SL

Remove link if switched live signal,
an enabler or BMS signal is connected. 

All wiring is 1Ph 230V 50Hz

230V 

motor

S4

2

S6

1

RET

OP       CL         N       

All wiring is 1Ph 230V 50Hz

230V 

motor

RET

N       

CL        

OP      

White      

Brown      

Blue     

A fan starting
delay of 1 minute
is imposed to 
enable the damper
to open.
To override the 
delay, fit a link here  

A fan starting
delay of 1 minute
is imposed to 
enable the damper
to open.
To override the 
delay, fit a link here  

Fault Signal

FAULT

Run Signal

RUN

0V

0 -

 10

V

BMS

Figure 6. ‘Net’ 
connection 
for Ecosmart 
devices.

Figure 7.  

Net -

 The 4 IDC plug-in connectors are provided for the connection of 

compatible sensors, manual controls and for linking the fans together 
under a common control. If more than 4 connections are required, 
the junction box (product code ES-JB) should be used (data cable 
installation).

A signal of 100-230V a.c. will activate the fan from either its off state 
or trickle state (see setting to work-trickle switch). When the SL is 
disconnected the fan will over-run for 1

 – 60 minutes (see fig. 12).

Do not take this signal from an isolating transformer.

Figure 8. Drive 
Open / Spring close.

Figure 9. Drive 
Open / Drive Close

Figure 10.  

Note that the volt free contacts are not fused. If these are used to 
power any external equipment, the installer must provide adequate 
fusing or other protections. 
These contacts are rated at 5A resistive, 0.5A inductive.

Run connections - 

These contacts are closed when the fan is running.

Fault connections -

 No fault = the contacts are closed.

 

   

Fault = the contacts are opened.

Figure 11.  

Summary of Contents for Ecosmart

Page 1: ...referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating plate 2 0 Handling The fan impeller is carefully balanced and centralised in the fan case it is therefore essential that great care is exercised when handling the unit Check the weight on the rating plate de...

Page 2: ...ppropriate fasteners and for ease of installation the cover should be removed and the casing separated from the base If cooling fans are fitted they should be disconnected while installation takes place The cable connecting the Ecosmart control and the fan must be a screened power cable not exceeding 30 metres The screening must be earthed at both ends using the special cable glands supplied Bridg...

Page 3: ...ELTA 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply 1U 1V 1W 2U 2V 2W Motor terminal box NOTE HIGH SPEED Supply 2U 2V 2W LINK 1U 1V 1W LOW SPEED Supply 1U 1V 1W Note individual wiring instructions are included with each unit 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 Low Speed High Speed L3 L1 L2 L3 460V 3 phase 60Hz supply 380V 3 p...

Page 4: ...e Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5 2 4 6 U V W CONTACTER A1 A2 0V 0 10V BMS signal NET connection U V W E DP CL Connections to fan via screened power cable Purpose made glands are provided to earth the screening N RET Note Internal conn...

Page 5: ...eened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensure the connection is made only by suitably qualified and authorised personnel the plug is not supplied It is available from R S Components Part No 403 875 or Farnell Part No 963 021 The system s response...

Page 6: ...red airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire between supply L and SL terminal Ensure the trickle switch is in the ON position Adjustment must be made on the pot marked Min Note that the minimum setting nominally 20 must be below the maximum setting oth...

Page 7: ...K mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales For technical assistance or further product information including spare parts and replacement components please contact the After Sales Department 6 1 Maintenance Intervals Maintenance should be carrie...

Page 8: ...ne contaminants and unit orientation 4 2 Where installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4...

Reviews: