BACnet Object

Product

ESCO-CO2D Duct Mounted CO2 Sensor

Measuring Range 

0 to 2,000 ppm CO2

Accuracy at 25°C

< ±[30 ppm CO2 + 2.0% of reading] (includes manufacturing deviation and drift). All accuracy 
specifications reflect testing the transmitters using high-grade, certified gases. Transmitters are 
intended for an altitude range of 0 to 600 m above sea level without compensation.

Non-Linearity 

< 0.5% of Full Scale

Temperature Dependence of Output

< 0.1% of Full Scale/C°

Long-Term Stability 

< ±5.0% of Full Scale/5 Years

Response Time (0 to 63%) 

1 Minute

Operating Temperature Range

-5 to 45°C

Storage Temperature Range 

-20 to 70°C

Humidity Range 

0 to 85% RH (non-condensing)

Transmitter Output Signal CO2 

Jumper Selectable:  0 to 10 VDC (Default) 
Maximum Output Voltage: 12.5V

Relay Output (Optional) 

Maximum 30V, 0.5A, Class 2

Recommended External Load 

Current Output: Maximum 500 ohms Load Resistance 
Voltage Output: Minimum 1,000 ohms Load Resistance

Power Supply Range 

20 to 30 VAC (18 to 30 VDC), Class 2

Power Consumption 

< 2.5 W Average, 4.1 VA

Warm-up Time 

< 5 Minutes

Air Flow Range 

0 to 2,286 m/Minute

Duct Probe Material 

Duct Probe Meets Plenum Rating Requirements of UL 1995, Heating and Cooling Equipment

Housing Material 

ABS Plastic

Dimensions (H x W x D) 

80 x 81 x 204 (mm)

Shipping Weight 

0.14 Kg

6.0 Technical Data

7.0 Warranty

The 5 year warranty starts from the day of delivery and includes parts 
and labour for the first year. The remaining 4 years covers replacement 
parts only.

The labour element of the warranty is subject to full, free and safe 
access to the equipment as recommended by CDM regulations.

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or not 
installed, commissioned and maintained in accordance with the details 
contained in this manual and general good practice. 

The product warranty applies to the UK mainland and in accordance 
with Clause 14 of our Conditions of Sale. Customers purchasing from 
outside of the UK should contact Nuaire International Sales office for 
further details.

The performance specifications are nominal and conform to acceptable industry standards.

Reviews: