NuAire Ecosmart Connect ESCO-CO2D Installation And Maintenance Download Page 2

2

nuaire.co.uk 

029 2085 8400

08. 03. 18. Document Number  671870

Installation and Maintenance

Ecosmart Connect Duct Mounted CO

2

 Sensor

0

Shared
Common
Line

Supply
Voltage

24 VAC

CO2 Sensor

Supply
Voltage

Output
Signals

CO2 Sensor

Controller

~

+

~

-

~

+

~

-

V

0

mA

or

V

mA

or

m

A

V

0

+

X3

V7 V10

0/

4m

A

X7

X6

X5

SERIAL COM

Figure 4. Connecting One AC Supply to Several Sensors (Not 
Recommended)

Figure 6. Sensor PCB.

3.3 Connecting the Conduit Adaptor

Align the nut with the opening inside the enclosure, and hold it in 
place.

Insert the adaptor body into the sensor conduit opening.

Manually tighten the adaptor into the nut, turning in a clockwise 
direction (see Figure 5).

Insert the wires through the conduit adaptor body opening.

Tighten the adaptor onto the adaptor body by turning the adaptor 
in a clockwise direction.

IMPORTANT

Do not overtighten the conduit adaptor, doing so could cause damage 

to or displacement of the PCB.

Nut

Adaptor Body
Adaptor 

Figure 5. Inserting the Conduit Adaptor.

3.4 Wiring the PCB

To wire the PCB’s input and output connections:

Open the sensor cover.

Insert the wire carefully through the conduit adapter and then strip 
6.35 mm of the wire insulation to prepare the wire for connection 
to the terminal block.

Connect the 24V supply between the positive (+) and negative (-) 
terminals as shown in Figure 6.

Connect the common wire to Terminal 0.

Connect the other wire to Terminal V (for voltage output).

4.0 Sensor Calibration

Nuaire’s carbon dioxide (CO2) sensors come from the factory calibrated 
for the following:

Output signal (0 to 10V) proportional to CO2 concentration (0 to 

2,000 parts per million [ppm]).

Altitude range of 0 to 600m above sea level without 

compensation.

Default relay output trigger point of 1,000 ppm.

5.0 Troubleshooting

The sensor is not field repairable. 

In the event the unit is not functioning properly, use the following 
checklist to identify the symptoms and determine a solution.

Verify that all wiring is correct.

Verify that the power supply voltage level is 20 to 30 VAC or 18 to 
30 VDC.

Note: The diagnostic Light-Emitting Diodes (LEDs) shown in the lower 
right-hand corner of Figure 6 indicate operational status:

V7 lights up if the self-diagnostics procedure detects an 
abnormality.

V10 pulses to indicate that the device is operational.

If the sensor will not operate after completing these steps, replace the 
unit.

Reviews: