nuaire.co.uk
029 2085 8200
BOXER BPS
ECOSMART CONNECT CONTROL (CO)
Description
Controller Terminal No Din Rail Terminal No
DI
AI
Relay
Output
AO (0-10v)
Fresh Air Sensor
IN1
1
Supply Air Sensor
IN2
1
Return/Room Air Sensor
IN3
30,31
1
Input 4 (Pressure Sensor)
IN4
1
Input 5
IN5
36,37
1
Alarm Circuit 1 (Fan, Heater)
IN6
32,33
1
Alarm Circuit 2 (Pump, Filter,
Thermal Wheel, IO Damper)
IN7
34,35
1
Enable Input Signal
IN8
38,39
1
Configurable Input Signal
(SL2)
IN9
40,41
1
Extract Fan 0-10V
OUT1
1
Supply Fan 0-10V
OUT2
1
Heat Demand 0-10V
OUT3
1
Cool/Reverse-Cycle Demand
0-10V
OUT4
1
HX BYpass Relay
OUT5
1
Fault Relay (De-energise on
fault)
OUT6
1
Fan Run Relay
OUT7
1
Cool/Reverse-Cycle Demand
Relay
OUT8
1
Recirculation Damper Relay
OUT9
1
230V Enable Input
10
230V Configurable Input
11
7.8 Connection Chart
Note that the volt free contacts are not fused. If these are used to power
any external equipment, the installer must provide adequate fusing or other
protections.
These contacts are rated at 3A resistive, 0.5A inductive.
Fault connections
- No fault = the relay is powered.
Fault
= the relay is unpowered.
Heat demand
- the relay is powered when heating is selected.
Cool demand
- the relay is powered when cooling is selected.
A fan start delay can be imposed to allow the damper time to open. This is
adjustable via display screens or commissioning tools.
If an I/O damper is fitted, it must be wired to the fan run relay, and the relay
supplied with the relevant supply voltage.
If required the damper end point relay can be connected in series with alarm
circuit 2 to monitor for damper faults. The multi-state value ‘IO Damper Fitted’
must be set to yes. This will allow the system to ignore alarm circuit 2 if the fans
are not running and dampers are closed.
See I/O Damper connection diagram for details.
Switch Live (SL) terminal - A signal of 100-230V a.c. will activate the switched
live signal.
Switch Live 2 (SL2) terminal - A signal of 100-230V a.c. will activate the
switched live 2 (Fan Boost) signal.
Note that a signal from an isolating transformer will produce an unpredictable
result and is not recommended.
Extra low voltage versions of the switched live signals are also available. Link two
contacts to activate the signal.
7.4 Volt Free Contacts
7.6 Volt Free Contacts
7.5 Switched Live
7.7 Network Settings
Default MS/TP Address: 4
BACnet Instance Number: Randomised &
Unique for each controller (0 to 4,194,304)
Summary of Contents for ecosmart CONNECT BPS
Page 19: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 19...
Page 21: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 21...
Page 25: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 25...
Page 33: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 33...
Page 45: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 45...
Page 55: ...05 11 20 Leaflet Number 671828 BOXER BPS ECOSMART CONNECT CONTROL CO 55 NOTES...