3

10. 05. 17. Leaflet number 671174

Installation and Maintenance

AIRMOVER  Supply & Extract Fans

MIN 

=  Minimum speed adjustment

MAX 

=  Maximum speed adjustment

SL Run on =  Switched Live Run-On 

 

Timer adjustment

TRICKLE 

=  Selects trickle running:  

    0 = off,  1 = selected

TEST 

=  Test button

LED indicators

Min  

  Max     SL run on

Trickle

Test

0        1

Pwr

Standby

Fan 1

Fan 2

Heating

Cooling

Fault

Frost

Tx

Rx

  E     N    L1   L2   L3  

To Fan 

Main Supply      400V 3ph 50Hz

  U     V    W   E  

  U     V    W   E  

LED Indication

PWR         GREEN: Power on & OK. 

Standby   LED on when fan is not running. (Not applicable)

Fan 1         GREEN: Fan 1 is running, RED: Fan 1 faulty.

Fan 2        GREEN: Fan 2 is running, RED: Fan 2 faulty. 

(Not applicable)

Heating*   Not applicable. See note.

Cooling*   Not applicable. See note.

Fault         LED on when a fault is present on unit.

Frost*       Not applicable. See note.

Tx

LED on when the controller is transmitting data.

Rx

LED on when the controller is receiving data.

*Note: the control panel is common to all the Ecosmart 

products. Indicators for functions that are not available

in this particular fan will not be illuminated.

Connection to

fan must use

screened power

cable, max

length 30m.

Screening must

be earthed at

both ends.

BMS Signal

The system’s response to a 0-10V dc BMS signal is

given in the following table. Note the BMS signal will

override any sensors and user control connected in the

system. The voltage tolerance is +/_ 125mV and is 

measured at the fans terminal.

Ventilation mode  Cooling mode*  Heating mode*

Local control     0.00

-                          -

OFF / trickle     0.25

-                          -

Speed 1

0.50

0.75

1.00

Speed 2

1.50

1.75

2.00

Speed 3

2.50

2.75

3.00

Speed 4             3.50

3.75

4.00

Speed 5             4.50

4.75

5.00

Speed 6             5.50

5.75

6.00

Speed 7

6.50

6.75

7.00

Speed 8             7.50

7.75

8.00

Speed 9             8.50

8.75

9.00

Speed 10            9.50

9.75

10.00

* Only available on relevant unit

Enabling    Sensors   User Control

ES - PIR       ES - TEMP ES - UCF

ES - TC         ES - RH

ES - CO2

Damper Connections (if required)

OP 

-  230V 50Hz 1A max supply to open the damper

CL

 -  230V 50Hz 1A max supply to close the damper

N     

-  Neutral supply to damper

RET

- 230V ac return signal from damper limit switch to

indicate the damper has reached its operating position. 

If the return signal is not present, the fan will wait for 

1 minute before starting.

Note: If a damper is not fitted, connect a link wire from OP

to RET. This will cancel the delay.

Glands supplied.

Warning - 

When the fan is isolated, allow 

5 minutes for the capacitors in the inverter to 

discharge before commencing work on the unit.

Important! This product 

must be earthed

5.0 Wiring Connections 

Settings cont.

Setting the minimum trickle airflow (nominal 40%)

i) Repeat the same procedure as for maximum airflow

above but without the link wire between supply L and SL

terminal. Ensure the trickle switch is in the ‘ON’ position.

The adjustment must be made on the pot marked ‘Min’

ii) Note that the minimum setting (nominally 40%) must be

below the maximum setting, otherwise minimum setting will

be automatically set to be the same as the maximum.

Summary of Contents for ECOSMART AIRMOVER

Page 1: ...atutory and governing regulations e g I E E CIBSE COHSE etc Units are suitable for internal use unless it has a optional outdoor cover Please refer to section 3 0 for outdoor weather cover details Prior to installation the impeller should be rotated by hand to check for smooth rotation and that no transit damage has occurred It is advisable to fit flexible connectors on either side of the fan unle...

Page 2: ... volt free contacts are not fused If these are used to power any external equipment the installer must provide adequate fusing or other protections These contacts are rated at 5A resistive 0 5A inductive Run connections These contacts are closed when the fan is running Fault connections No fault the contacts are closed Fault the contacts are opened this includes no power supply at the unit 4 4 Dat...

Page 3: ...mV and is measured at the fans terminal Ventilation mode Cooling mode Heating mode Local control 0 00 OFF trickle 0 25 Speed 1 0 50 0 75 1 00 Speed 2 1 50 1 75 2 00 Speed 3 2 50 2 75 3 00 Speed 4 3 50 3 75 4 00 Speed 5 4 50 4 75 5 00 Speed 6 5 50 5 75 6 00 Speed 7 6 50 6 75 7 00 Speed 8 7 50 7 75 8 00 Speed 9 8 50 8 75 9 00 Speed 10 9 50 9 75 10 00 Only available on relevant unit Enabling Sensors ...

Page 4: ... speed motors DOL starting on both speeds 3 phase units up to 3KW 3 phase units with matched frequency inverter 3 phase units 4KW and above Set up Commissioning Box 3 phase motors are connected directly to the Motor Terminal Box Observe the motor plate and connection details 3 phase two speed tap pam wound motors require a three contactor control 3 phase Dual wound motors require a two contactor c...

Page 5: ...rying out any work When ordering spare parts please quote the serial number of the unit and the ARC number of the purchase if possible This information will be available on the fan label 8 0 Warranty The Airmover has a 3 year warranty and Ecosmart Airmover has a 5 year warranty The warranty starts from the day of delivery and includes parts and labour for the first year The remaining years covers ...

Page 6: ...o the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any cables not intended for use with this product 6 0 COMMISSIONI...

Reviews: