11.0 FILTER MAINTENANCE AND REPLACEMENT

The filters are required to be changed every five years, the display will show the 
letter ‘C’ once this time has elapsed. New filters can be purchased direct from 
Nuaire using the following code number: 

DRIPOS2001-FILTERKIT

 (five year 

filter). To reset the change filter message, press and hold BOTH “up and “down” 
button until the letter ‘C’ starts to flash then release and press the “down” 
button. 
Note: If the units’ performance has been reduced dramatically or black dust 
becomes visible around the outlet diffuser, check that the filter has not become 
dislodged in any way.

12.4 Unit Binding Mode

Where wireless sensors/switches are present, they must first be bound to the fan 
unit before it can work. In order to bind to the switches/sensors the fan must be 
in binding mode. The steps required to enter binding mode are shown below.

1. 

Ensure the fan unit is powered on. 

2. 

Unit will enter the start-up sequence for 2 minutes when first powered on. 

Press the down button on the ceiling diffuser control panel once, to exit the 
start-up sequence.

3. 

Press and hold both the UP and DOWN buttons for 20-30 seconds then 

release, a single horizontal bar on the display flashes. 

4. 

Press "down" to enter binding mode (binding mode last for 5 minutes). The 

unit will now display a flashing ‘b’ to indicate it has entered binding mode.

Note: Solid “P” indicates boost, flashing “b” indicates binding mode.      

12.5 Binding a 4 Way Switch

Once the fan unit is in binding mode a switch may now be bound.

 Press and hold the ‘Boost’ & 'Heater off' button for 2-5 seconds.

 The LED will flash GREEN twice when bound.

To check the the binding of a switch, press “boost”. A green LED denotes that the 

switch is bound and the fan should run at full speed. A red LED denotes that the 

switch is not bound. 

Note: if “b” and “P” are flashing on the display, the unit is in binding mode 

and purge (full speed).

The switch is provided with an adhesive foam pad to allow quick and easy 
mounting to the wall. Alternatively the switch may be mounted to the wall using 
the fixing plate (screws are not provided). 
Remove the switch fixing plate by inserting a flat head screwdriver in the rear of 
the switch on the left or right side, underneath the fixing plate and gently lever 
up the plate until the fixing lug releases. Repeat for the opposite side. This will 
give access to the battery compartment on the rear of the PCB and release the 
fixing plate. Reassemble the remaining components and press into place, an 
audible click will be heard. 1x CR 2032 battery is provided and expected lifetime 
is 10 years under normal use.  

Normal - 

If the normal button is used the unit will return to its standard 

operation programmed at the diffuser.

Boost (Purge) - 

If the boost button is used, the fan speed will increase to 

maximum and a ‘P’ will be shown in the display.

Heater auto - 

If the heater auto button is used, the heater switches on/off 

automatically as needed.

Heater off - 

If the heater off button is used 'Heater auto' will be disabled and 

the heater switches off.

The CO

2

 sensor requires a 230V power supply. Remove the front panel as per 

the  humidity sensor above and release the terminal cover via a fixing lug on the 
rear of the sensor. Refer to the wiring diagram below and connect the supply to 
the terminal box. Finally the sensor may be mounted to the wall (screws are not 
provided).

12.6 Binding a Sensor

Putting the unit into binding (see 12.4) before powering the sensors will 
automatically bind the sensors to the unit. However if they do not bind follow 
the below steps.

1. 

Put the unit into binding mode (see 12.4).

2. 

Power up sensors (insert batteries for humidity, mains for CO2).

3. 

Tap indented button then hold until left hand LED flashes red/green (ignore 

red/blue and continue to hold). Release button whilst flashing.

4. 

Tap indented button again, whilst red/green LED is still flashing.

5. 

Close binding window on fan control panel by holding both “up” and “down” 

for 5 seconds and release.

6. 

Check sensor has bound by tapping indented button and look for the left 

hand LED to go green. If it displays red, repeat from step 1.

12.7 Setting the Sensor Set Point

 

The sensors will automatically trigger the fan to increase speed once the sensor 
set point has been exceeded. To change the sensor set point, press and hold the 
indent button for 5 seconds until the status indication LED flashes BLUE/RED 
release, the green LED’s illuminate to show the current sensor set point. Press 
the button to cycle through all allowed values, and press and hold for 3 seconds 
to confirm choice. If the button is not operated for 10 seconds the set point 
currently selected is stored.

The front panel of the sensor must first be released by pressing in the plastic 
fixing lug located on the bottom edge of the sensor. The panel may now be 
removed and the sensor mounted on the wall in a suitable location (screws not 
provided). 2x AA batteries are provided.

12.2 Installing a Humidity Sensor (DRI-ECO-RH)

12.3 Installing a CO

Sensor (DRI-ECO-CO2)

Indent  
Button

Indent  
Button

L

N

CO2

 

Sensor

Mains

230V

50Hz

4VA

N

L

12.0 WIRELESS SENSORS & SWITCHES

12.1 Installing a 4 Way Switch (DRI-ECO-4S)