NuAire AV55-MSS Installation And Maintenance Manual Download Page 7

7

24. 02. 22. Document Number  671572

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

AVS

Installation Manual

5.0 ELECTRICAL INSTALLATION

Before commencing work make sure that the unit, switched live 
and Nuaire control are electrically isolated from the mains supply.

Because the run and start currents depend upon the duty and 
associated ductwork of an individual unit, run currents will  be 
exceeded if the unit is operated with its cover removed. It is therefore 
recommended that the unit is not run for prolonged periods in this 
condition.

5.1 Wiring Diagrams

All inter-connections between circuit boards, blowers and sensors 
are made at the factory. These diagrams only show the essential 
field wiring points for clarity. 

*Remove link wire if switched live signal, an enabler or BMS signal is 
connected.

5.1.1 AVS1-8

 
 

20 

AVS1-8 Wiring Diagram

230V -  50Hz Supply

Local isolator (by others)

L

N

N

L

Damper Connections

Run 

Signal

Fault 

Signal

NET 

connections 

for Ecosmart 

devices

Min     Max    SL run 

  on

Trickle           

0  

1

Test

Link wire see note*

ES-CO2

Connection

BMS

Input

Signal

0-10V

0V

Ecosmart

Pwr
Standby
Fan 1

Heating

Fan 2

Cooling
Fault

TX
RX

Frost

N

L

SL

DP

CL

N

RET

Heat

Demand   Run        Fault

E

5.1.2 AVS9

 
 

Damper Connections

Heat Demand 

Signal

Run 

Signal

Fault 

Signal

NET 

connections 

for Ecosmart 

devices

Min        Max    SL run 

  on

Trickle  

0  

1

Link wire see note*

  Test

Connection

ES-CO2

BMS

Input

Signal

0V

0-10V

Ecosmart

Pwr
Standby
Fan 1

Heating

Fan 2

Cooling
Fault

TX
RX

Frost

N

L

SL

DP

CL

N

RET

Heat

Demand   Run        Fault

N  L1  

L3

L2   L3

L2

L1
N

400V -  3ph 50Hz Supply

Local isolator (by others)

E

21 

AVS9 Wiring Diagram

5.1.3 Control Module 

 

 

Volt Free 

Contact  

RUN signal

0.5A inductive

5A resistive

Volt Free 

Contact  

Connections 

FAULT signal

to Damper

N
L
SL

RUN      

FA

U

LT

DP
CL
N
RET

 400V 3ph 50Hz supply

Switch live signal

(if required)

connections

No user 

NET connections for 

ECOSMART devices

connections

CO

2

 sensor

0  

+ve signal

from BMS

Remove this link wire if 

a switched live signal is 

connected to terminal SL

NOTE: Also remove link if a 

BMS is connected.

Also remove link if an enabling 

device is connected in the 'NET'

EC

OSMART NET

L3

L2  

L1   

  

N   

Ribbon cable

to commissioning

box

      

N   L1   L2  L3

22 

Control Module Wiring Diagram

5.2 Post Installation Testing

Ensure that the fan unit and any specified controls are fitted 
securely according to the instructions. 

Switch on the mains supply.

Push the test button to run the unit fan and check it runs 
satisfactorily.

If a switched live signal is used, activate this signal and check that 
the fan runs. De-activate the switched live signal and check the 
run-on time; adjust if necessary.

Adjust the set point of any sensors and PIR; check they function 
correctly. 

Adjust the maximum and minimum airflow (if required) by 
following the commissioning procedures.

Summary of Contents for AV55-MSS

Page 1: ...l not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Symbols GENERAL WARNING Signifies a general warning regarding hazard specified by supplementary information ELECTRIC SHOCK This unit must be completely electrically isolated before any panels are removed Check mains supply and control connections ROTATING PARTS This unit contains fast moving rotati...

Page 2: ...sembly positioned in series for optimum performance Units incorporate fully detachable top or bottom panels for maintenance and inspection purposes AVS 1 units have a loose control module for surface mounting up to 1 metre away from main unit AVS 8 and 9 units incorporate split access panels 2 1 Code Description 1 2 3 4 AV S CP 1 1 Range Aire Volve 2 Fan Type S Single Fan 3 Constant Pressure CP Co...

Page 3: ...mounting feet supplied with access panel positioned for underside access Figure 2 3 4 5 Vertically Wall Mounted Rigid Units Utilising the Aire Volve Vertical Hanging Bracket kit that includes wall hanging brackets and hinges Figures 5 and 6 The unit case has captive M8 nuts which can be used after removing the M8 plugging screws Units should always be positioned with sufficient space to allow the ...

Page 4: ...talled NAV 2 5 Floor Mounted Application 4 7 Dimensions mm Weights kg 4 7 1 AVS Units 12 AVS Dimensions A C D B B1 A1 Unit Code A A1 Bracket Centre Points B B1 Bracket Centre Points C D Weight kg AVS1 580 344 535 576 246 200 27 AVS2 615 380 535 646 281 200 24 AVS3 745 510 672 713 329 250 43 AVS4 788 553 672 713 373 315 47 AVS4L 914 678 818 860 391 315 67 AVS5 914 678 818 860 428 315 66 AVS6 1087 8...

Page 5: ...3 AVS7 MSS Standard 1000 1013 575 41 AVS7 MSL Large 1500 1013 575 98 AVS8 AVS8 MSM Mini 500 1237 615 51 AVS8 MSS Standard 1000 1237 615 83 AVS8 MSL Large 1500 1237 615 114 AVS9 AVS9 MSM Mini 500 1237 615 51 AVS9 MSS Standard 1000 1237 615 92 AVS9 MSL Large 1500 1237 615 125 4 8 Unit Access Unit can be installed inverted for ease of access to control e g control opposite side If inverted it will re...

Page 6: ...ncer Floor Mounted Unit And Inlet Silencer 17 Silencer Alignment Brackets 18 Installed AVS Silencer 4 10 AVSCP Constant Pressure Range Ecosmart constant pressure extract fans are supplied to control the static pressure at the fan inlet This set up is suitable for the majority of applications However when ancillaries with high pressure losses are fitted to the fan s inlet side the low pressure tapp...

Page 7: ... Ecosmart devices Min Max SL run on Trickle 0 1 Link wire see note Test Connection ES CO2 BMS Input Signal 0V 0 10V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX RX Frost N L SL DP CL N RET Heat Demand Run Fault N L1 L3 L2 L3 L2 L1 N 400V 3ph 50Hz Supply Local isolator by others E 21 AVS9 Wiring Diagram 5 1 3 Control Module Volt Free Contact RUN signal 0 5A inductive 5A resistive Volt ...

Page 8: ... minute before starting If a damper is not fitted connect a link wire from OP to RET This will cancel the delay 25 Drive Open Drive Close Damper Connection All wiring is 1PH 230V 50Hz A fan starting delay of 1 minute is imposed to the enable the damper to open To override the delay fit a link here 230V motor OP CL N RET 2 S4 S6 1 26 Drive Open Spring Close Damper Connection All wiring is 1PH 230V ...

Page 9: ...cosmart products and will have indicators for functions that are not available in this particular fan However these indicators will not be illuminated A Commissioning Procedure document Document No 671153 is available on request from Nuaire 29 Commissioning Panel Details LED indicators Max Min Trickle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx MIN Minimum speed adjustment M...

Page 10: ...Annually Thoroughly inspect the unit and its components for corrosion acting immediately to treat restore any damaged areas All electrical terminals within the unit should be tightened Check all earth connections Check control dampers blades Check operation of damper actuators and linkages and adjust as necessary 8 0 WARRANTY The 5 year warranty starts from the day of delivery and includes parts a...

Page 11: ...11 24 02 22 Document Number 671572 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk AVS Installation Manual NOTES ...

Page 12: ...12 24 02 22 Document Number 671572 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk AVS Installation Manual NOTES ...

Reviews: